Gas Burner Safety Control DKG 972
For 2-stage atmospheric gas burners
Flame detection:
— Ionisation probe
— Infrared-flicker detector IRD 1020.1
— UV flame sensor UVD 971
INTRODUCTION
The burner control box DKG 972 controls and supervises
atmospheric burners for gas. They are approved and certified
according to the applicable European standards and
regulations.
The microprocessor-based programming sequence ensu-
res extremely stable timings independent of voltage varia-
tions, ambient temperature and/or switch-on cycles. The
built-in information system not only provides a continuous
monitoring of the actual state of the box (very helpful es-
pecially for monitoring the start-up phase) but also informs
about the cause of a possible lock out. The lock out cause
is stored in such a way that it can be retrieved even after a
power failure.
The control box is designed for maximum safety in case of
fluctuations in the voltage supply. If the mains voltage drops
below the permitted level, operation is interrupted and the
control box automatically prevents the start sequence from
being repeated. In this way, the safety of the system is not
put at risk by a drop in the mains voltage. This low-voltage
protection works not only during start-up but also perma-
nently during operation.
CONSTRUCTIONAL FEATURES
The control box circuitry is protected by a flame resistant,
transparent plug-in type plastic housing. A central fixing
screw locks the control box to the wiring base.
The plug-in control box incorporates the microprocessor
based timer, flame check and reset circuits.
Manual reset from lock out and set to lock out is provided by
a push button with an integrated LED information system.
A variety of cable entry points provides complete flexibility
for electrical wiring.
The wiring base S98 is equipped with spare- and extraterminals
and allows together with a variety of cable entry points utmost
flexibility of electrical wiring.
The DKG 972 are compatible with the TFI 812.
Different are only the pre- and post-ignition times.
Max. heating power according the limits in the Gas Appliance
Directive.
Table of timings (sec.)
Model
waiting time start
tw
05
12
10
12
pre-ignition time
Stray light monitoring
tvz
3
3
TECHNICAL DATA
Operating voltage
or
Fuse rating
Power consumption
Max. load per output
— term. 3 ignition trafo
— term. 5 + 6 solenoid valves
— term. 7 alarm indicator
— term. 4 auxiliary blower
total load
Reset time from lock out
Re-cycling / repetition (max. 4x) after a loss-of-flame during
operation
Sensitivity
min. ionisation current required
Sensitivity for stray light
Ionisation probe insulation
Stray capacitance
max. cable length
Flame detectors
IRD 1020.1
UVD 971
Weight incl. Wiring base
Mounting position
Protection class
Approved ambient parameter
for control and flame detector
— for operation
— for storage
Build-up of ice, penetration of
water and condensing water are
Approvals according
to European standards
Classified acc. to EN 298
safety time
tf
ts
5
5
5
10
1
220 / 240 V (-15… +10%)
50 Hz (±5%)
110 / 120 V (-15… +10%)
60 Hz (±5%)
10 A fast, 6 A slow
ca. 12 VA
1.0 A, cos ϕ 0.2
0.5 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
2.0 A, cos ϕ 0.4
4.0 A, cos ϕ 0.4
max. 16 A during 0,5 sec
none
1 µA
1.5 µA
0.4 µA
probe — earth
greater than 50 MΩ
probe- earth
less then 1000 pF
< 3 m
side-on or end-on viewing
end-on viewing
190 g
any
IP 40
max. 95% at 30° C
-20° C… +60° C
-20° C… +80° C
inadmissible
EN 298 and EN 230, as
well as all other relevant
Directives and standards
ATLLXN
post-ignition time
delay 2nd-stage
tn
tv2
4
25
9
25
Gas Burner Safety Control DKG 972
For 2-stage atmospheric gas burners
Flame detection:
— Ionisation probe
— Infrared-flicker detector IRD 1020.1
— UV flame sensor UVD 971
INTRODUCTION
The burner control box DKG 972 controls and supervises
atmospheric burners for gas. They are approved and certified
according to the applicable European standards and
regulations.
The microprocessor-based programming sequence ensu-
res extremely stable timings independent of voltage varia-
tions, ambient temperature and/or switch-on cycles. The
built-in information system not only provides a continuous
monitoring of the actual state of the box (very helpful es-
pecially for monitoring the start-up phase) but also informs
about the cause of a possible lock out. The lock out cause
is stored in such a way that it can be retrieved even after a
power failure.
The control box is designed for maximum safety in case of
fluctuations in the voltage supply. If the mains voltage drops
below the permitted level, operation is interrupted and the
control box automatically prevents the start sequence from
being repeated. In this way, the safety of the system is not
put at risk by a drop in the mains voltage. This low-voltage
protection works not only during start-up but also perma-
nently during operation.
CONSTRUCTIONAL FEATURES
The control box circuitry is protected by a flame resistant,
transparent plug-in type plastic housing. A central fixing
screw locks the control box to the wiring base.
The plug-in control box incorporates the microprocessor
based timer, flame check and reset circuits.
Manual reset from lock out and set to lock out is provided by
a push button with an integrated LED information system.
A variety of cable entry points provides complete flexibility
for electrical wiring.
The wiring base S98 is equipped with spare- and extraterminals
and allows together with a variety of cable entry points utmost
flexibility of electrical wiring.
The DKG 972 are compatible with the TFI 812.
Different are only the pre- and post-ignition times.
Max. heating power according the limits in the Gas Appliance
Directive.
Table of timings (sec.)
Model
waiting time start
tw
05
12
10
12
pre-ignition time
Stray light monitoring
tvz
3
3
TECHNICAL DATA
Operating voltage
or
Fuse rating
Power consumption
Max. load per output
— term. 3 ignition trafo
— term. 5 + 6 solenoid valves
— term. 7 alarm indicator
— term. 4 auxiliary blower
total load
Reset time from lock out
Re-cycling / repetition (max. 4x) after a loss-of-flame during
operation
Sensitivity
min. ionisation current required
Sensitivity for stray light
Ionisation probe insulation
Stray capacitance
max. cable length
Flame detectors
IRD 1020.1
UVD 971
Weight incl. Wiring base
Mounting position
Protection class
Approved ambient parameter
for control and flame detector
— for operation
— for storage
Build-up of ice, penetration of
water and condensing water are
Approvals according
to European standards
Classified acc. to EN 298
safety time
tf
ts
5
5
5
10
1
220 / 240 V (-15… +10%)
50 Hz (±5%)
110 / 120 V (-15… +10%)
60 Hz (±5%)
10 A fast, 6 A slow
ca. 12 VA
1.0 A, cos ϕ 0.2
0.5 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
2.0 A, cos ϕ 0.4
4.0 A, cos ϕ 0.4
max. 16 A during 0,5 sec
none
1 µA
1.5 µA
0.4 µA
probe — earth
greater than 50 MΩ
probe- earth
less then 1000 pF
< 3 m
side-on or end-on viewing
end-on viewing
190 g
any
IP 40
max. 95% at 30° C
-20° C… +60° C
-20° C… +80° C
inadmissible
EN 298 and EN 230, as
well as all other relevant
Directives and standards
ATLLXN
post-ignition time
delay 2nd-stage
tn
tv2
4
25
9
25
-
- Регистрация:
- 17.03.19
- Сообщения:
-
3
- Благодарности:
- 0
nafsinai
Новичок
- Регистрация:
- 17.03.19
- Сообщения:
- 3
- Благодарности:
- 0
Buderus Logano G234X (WS) + Logamatic 2109, сгорел Автомат горения DKG 972-N Mod. 21Уважаемы специалисты не могли бы Вы дать совет, суть вопроса в чем, год назад установил в частные дом газовый котел Buderus Logano G234X (WS) -60kw с системой управления Logamatic 2109 работало все без нареканий, не давно начались скачки напряжения, после чего котел перестал работать (к дому подведена только 1 фаза, и стоит стабилизатор напряжения РЕСАНТА спн 13500 вход 90-260B, реле-прерывателей нет) Посмотрев систему управления Logamatic выяснил, что все предохранители в целости и сохранности, покопавшись дальше, увидел следы копати на автомате горения, сгорел варистор, выпаяв его результата не дало, котел не запустился, не найдя подробной схемы автомата горения мои скудные знания на этом иссякли я не стал копаться в нем дальше, и заказал новый автомат горения DKG 972-N Mod. 21. После установки нового автомата горения, котел снова заработал. Но вчера произошло опять скачек напряжения, при том что напряжение полностью отключилось и резко появилось. Я сразу пошел проверить котел и опять такая же ситуация, только еще хуже автомат горения пришлось буквально выдирать из котла, клемы пришлось выкусывать так как посадочные места просто расплавились, а в самом автомате горения помимо варистора оплавилась сама плата да так, что я ее из защитного корпуса вытащить не смог. После пошел и проверил всю технику в доме и она вся была целая. Почему при стабилизаторе сгорает только сам автомат горения а все остальное остается целым в том числи и все предохранители в котле? Не уж то данная система настолько уязвима к перепадам напряжения.
-
- Регистрация:
- 19.11.13
- Сообщения:
-
746
- Благодарности:
- 159
ГеннадийВС
Живу здесь
- Регистрация:
- 19.11.13
- Сообщения:
- 746
- Благодарности:
- 159
- Адрес:
- Минеральные Воды
Тут врядли кто даст четкий ответ на причину. Стабилизатор, а тем более Ресанта, не защищает приборы от импульсных помех (скачкообразных) и сам тоже не защищен, отработать их тем более не сможет, предохранители не успеют перегореть, не всегда успеет защитить варистор, есть более быстрые приборы, например супрессоры, а лучше установить на дом устройство молниезащиты соответствующей мощности для вашего дома. Должно присутствоать правильное заземление. Ваш первый блок управления, думаю, возможно восстановить ищите в своем регионе спеца.
А регион — Россия, шифруемся? -
- Регистрация:
- 17.03.19
- Сообщения:
-
3
- Благодарности:
- 0
nafsinai
Новичок
- Регистрация:
- 17.03.19
- Сообщения:
- 3
- Благодарности:
- 0
Просто быстро регистрацию проходил, а так со станицы Тамань Краснодарского края. А по поводу спеца наверное в самом Краснодаре искать нужно, так как сам автомата горения ближайшее только с Москвы заказывать пришлось.
Да просто быстро регистрацию проходил, а так со станицы Тамань. Краснодарского края. А по поводу спеца наверное где то в Краснодаре искать нужно, так как автомата горения ближайший с Москвы заказывать пришлось. Сам котел в Краснодаре покупался в еще в 2014 и гарантия уже не действительна(
-
- Регистрация:
- 19.11.13
- Сообщения:
-
746
- Благодарности:
- 159
ГеннадийВС
Живу здесь
- Регистрация:
- 19.11.13
- Сообщения:
- 746
- Благодарности:
- 159
- Адрес:
- Минеральные Воды
Есть в ваших краях люди способные восстановить. Знаю в Сочах, читал были и ближе. Клич брось, мож кто отзовется. Я с таким блоком не возился, начинать не хочется. Думаютебе, еще клапан надо проверять.
-
- Регистрация:
- 19.11.13
- Сообщения:
-
746
- Благодарности:
- 159
ГеннадийВС
Живу здесь
- Регистрация:
- 19.11.13
- Сообщения:
- 746
- Благодарности:
- 159
- Адрес:
- Минеральные Воды
Котлы нужно покупать те которые распространены в вашем регионе, и развита сеть сервиса, во многих местах продают зч, не гнаться за брендом и не слушать продавца во все уши… .
-
- Регистрация:
- 20.09.10
- Сообщения:
-
2.795
- Благодарности:
- 877
dxpoha
Живу здесь
- Регистрация:
- 20.09.10
- Сообщения:
- 2.795
- Благодарности:
- 877
- Адрес:
- Самара
Стаб поменять. Ставь штиль is 550.
-
- Регистрация:
- 13.11.18
- Сообщения:
-
3.826
- Благодарности:
- 1.674
Партизан32
Живу здесь
- Регистрация:
- 13.11.18
- Сообщения:
- 3.826
- Благодарности:
- 1.674
- Адрес:
- Брянск
Там у вас конец света и зимой и летом. Хотите жить спокойно, поставьте хотя бы РНПП. Стабилизатор — вещь бесполезная в вашем случае.
Да и Анапы хватит, если поискать.
-
- Регистрация:
- 28.03.18
- Сообщения:
-
134
- Благодарности:
- 250
BoschClimate
Живу здесь
- Регистрация:
- 28.03.18
- Сообщения:
- 134
- Благодарности:
- 250
- Адрес:
- 141400, г.Химки, Вашутинское шоссе, дом 24
Добрый день!
Дело в том, что стабилизатор работает в определенном диапазоне напряжений, а также, в зависимости от модели, имеет время реакции. У одних он меньше, у других больше.
А варистор — это элемент защиты от превышения напряжения, и он срабатывает при напряжении 275В, т. е. это напряжение находится за пределами рабочих параметров Вашего стабилизатора. К тому же отличается время реакции. Типовое значение времени срабатывания варисторов при воздействии перенапряжения составляет не более 25 наносекунд (нс).
А согласно инструкции к Вашему стабилизатору, его время реакции 5-7 мсек. Поэтому в данном случае говорить о ненадежности оборудования или его уязвимости нельзя — параметры электросети далеко за пределами допустимого напряжения. И это вопрос к поставщику электроэнергии.
Для дополнительной защиты оборудования, например, можно установить внешний блок с варисторами, как вариант, Теплоком Альбатрос. -
- Регистрация:
- 17.03.19
- Сообщения:
-
3
- Благодарности:
- 0
nafsinai
Новичок
- Регистрация:
- 17.03.19
- Сообщения:
- 3
- Благодарности:
- 0
Я уже не знаю что делать… опять заказал новый автомат горения, поставил РНПП после счетчика (только потом пришлось переделывать, и ставить не посредственно перед самим котлом, так как скачки были за 250 В, а ночью за 260 было и постоянные перебои со светом мешали) поставил новый стабилизатор, поставил дополнительное устройство от скачков напряжения, даже установил громоотвод как и советовали, проработало все нормально 4 дня и опять скачек напряжения и опять выгорает только автомат горения на газовом котле. При этом за минуты 3-4 до случившегося я проверял котел и он был выключен так ка работал РНПП, я на срабатывание выставил 250 В приходило 250-255 В, после пошел обедать. Разогревал себе еду в микроволновке и она на доли секунды остановилась и снова запустилась, я сразу в котельную а там только запах гари и выгоренный автомат горения. Опять обошел всю технику в доме и ни одного признака сгорания и выгорания… я не понимаю по чему сгорает только автомат горения, просто не понимаю…
-
- Регистрация:
- 06.09.16
- Сообщения:
-
2.023
- Благодарности:
- 1.045
Dmitribir
Живу здесь
- Регистрация:
- 06.09.16
- Сообщения:
- 2.023
- Благодарности:
- 1.045
- Адрес:
- Москва и МО Север, Тверская область, Зубцов.
Попробуйте найти и поставить топочник TFI 812.2, они устанавливались ранее. Переделок никаких не потребуется, все встает на штатные места.
-
- Регистрация:
- 13.11.18
- Сообщения:
-
3.826
- Благодарности:
- 1.674
Партизан32
Живу здесь
- Регистрация:
- 13.11.18
- Сообщения:
- 3.826
- Благодарности:
- 1.674
- Адрес:
- Брянск
Уважаемый, вы в своём уме ? Какие 250, если 242 должно отключаться. Не, ну если вы хотите, можете 300 поставить и продолжать тут жаловаться.
Проблема не к форуму, а к энергоснабжающей организации. Им же и счёт выставить надо, за уничтоженное оборудование.
Описание товара
Топочный автомат Satronic / Honeywell DKG 972-N Mod.21 артикул 0432021 применяется в составе атмосферных котлов. Функция менеджера горения – контроль и управление двухступенчатыми горелками. Комплектация не включает цоколь. Аппарат успешно протестирован и сертифицирован по европейским нормам.
Важные параметры:
- Предохранительное время: 10 секунд.
- Время перед розжигом: 3 сек.
- Режим функционирования: прерывистый.
- Источник электропитания: 220/240 В, 50/60 Гц.
Особенности:
Управляет программным обеспечением встроенный микропроцессор. Автомат обеспечивает высокую стабильность запуска, вне зависимости от бросков в сети, циклов включения, эксплуатационной температуры.
Программа постоянно отслеживает все стадии работы устройства (включая этап запуска), оповещает о причинах аварийного отключения. Благодаря наличию энергонезависимой памяти данные о причинах автовыключения не утрачивается даже при обесточивании автомата.
SATRONIC DKG имеет встроенную защиту от низкого напряжения, что обеспечивает высокий уровень безопасности при работе горелки. При достижении минимального уровня напряжения в сети, автомат отключается и препятствует повторному запуску до восстановления рабочих параметров электропитания. Автоматическая защита работает постоянно, а не только при запуске горелки.
Контроль наличия пламени происходит при помощи ионизационного электрода/ УФ-датчика/ инфракрасного детектора.
Конструкция
SATRONIC DKG имеет пластиковый огнестойкий корпус, устанавливаемый с щелчком. Для монтажа прибора на цоколь предусмотрен центральный винт. Цоколь не входит в базовый комплект.
Электрозащита корпуса отвечает стандарту IP40. Внутри размещен датчик пламени, микропроцессор, электросхемы сброса.
На корпусе находится кнопка ручной блокировки/ перезапуска со световой индикацией.
Достоинства:
- надежное функционирование горелки;
- самодиагностика неполадок;
- оповещение о причинах выключения;
- действенная защита от низкого напряжения;
- энергонезависимая память;
- кожух из огнестойкого материала.
На нашем сайте можно купить топочный автомат Satronic / Honeywell DKG 972-N Mod.21 по приемлемой цене, оформив заказ через виртуальную корзину. Полную информацию об устройстве уточняйте у сотрудника «АНКАС».
CIRCUIT AND TIMING DIAGRAM DKG 972
Ph
max. 10 A fast
HS
6 A slow
1
2
3
4
5
V1
M
IS
Z
N
IRD- OR UVD CONNECTION
IRD 1020.1
UVD 971
BLOCK DIAGRAM DKG 972
Oscillator
µC
Watchdog
Reset
Flame
amplifier
RZ
rz
1
3
4
ST
GW
RT
EV
6
7
8
9
A
V2
SA
tw tf tvz tn ts tv2
term. 8
blue
term. 1
black
term. 9
brown
Fault display
Information
EEPROM
system
µC
RV1
RV2
RS
rs
rv1
rv2
5
6
7
HS
Mains switch
GW
Gas proving switch
ST
Limit thermostat
RT
Control thermostat
EV
External reset and lock out button
IS
Ionisation probe
(IRD 1020.1, UVD 971see separate diagram)
Z
Ignition
V1
Solenoid valve, 1st-stage
V2
Solenoid valve, 2nd-stage
SA
External lock out signal
M
Auxiliary blower
tw
Waiting time
tf
Stray light monitoring
tvz
Pre-ignition time
tn
Post-ignition
ts
Safety time
tv2
2nd-stage delay
Reset and
lock out
Mains
monitoring
Power
supply
monitoring
Power
supply
8
9
A
5
Блок управления Satronic DKG 972-N Mod21 Honeywell 0432021
Топочный контроллер Honeywell Satronic DKG972-N mod.21 используют для 2-х ступенчатых атмосферных горелок с возможностью контроля, и наличия пламени с помощью:
- Ультрафиолетового датчика пламени UVD971.
- Ионизационного электрода.
- Инфракрасного детектора пламени IRD1020.
Применяется в составе атмосферных котлов. Функция менеджера горения – контроль и управление двухступенчатыми горелками. Комплектация не включает цоколь. Аппарат успешно протестирован и сертифицирован по европейским нормам.
Важные параметры:
- Предохранительное время: 10 секунд.
- Время перед розжигом: 3 сек.
- Режим функционирования: прерывистый.
- Источник электропитания: 220/240 В, 50/60 Гц.
Маркировка товара:
— Honeywell
— DKG 972-N Mod.21
— 220/240V
— 50/60Hz 12VA
— ts 10 sec.
— 4A cos 0.4
Производитель: Honeywell
Отзывы про Блок управления Satronic DKG 972-N Mod21 Honeywell 0432021
ВАРИАНТЫ ОПЛАТЫ:
- Наложенный платеж.
- Безналичный расчет.
- Предоплата на расчетный счет.
РЕКВИЗИТЫ ДЛЯ ОПЛАТЫ:
Реквизиты для оплаты вы получите в счёте на оплату.
ВАРИАНТЫ ДОСТАВКИ:
1 Доставка Блок управления Satronic DKG 972-N Mod21 Honeywell 0432021 в отделение транспортной компании «СДЭК»:
Оплату услуг перевозчика осуществляет покупатель.
Отгрузка осуществляется с понедельника по субботу.
2 Самовывоз.
Можете самостоятельно забрать Блок управления Satronic DKG 972-N Mod21 Honeywell 0432021 по цене 26 000 руб. со склада по адресу:
г. Москва, район Южное Бутово, ул. Венёвская 2А, метро «Бульвар Адмирала Ушакова».
А ещё у нас на сайте большой выбор Теплообменников Baxi, Датчиков температуры Protherm, Коаксиальных дымоходов Baxi.
1 Gas Burner Safety Control DKG 972 INTRODUCTION The burner control box DKG 972 controls and supervises atmospheric burners for gas. They are approved and certified according to the applicable European standards and regulations. The microprocessor-based programming sequence ensu- res extremely stable timings independent of voltage varia- tions, ambient temperature and/or switch-on cycles. The built-in information system not only provides a continuous monitoring of the actual state of the box (very helpful es- pecially for monitoring the start-up phase) but also informs about the cause of a possible lock out. The lock out cause is stored in such a way that it can be retrieved even after a power failure. The control box is designed for maximum safety in case of fluctuations in the voltage supply. If the mains voltage drops below the permitted level, operation is interrupted and the control box automatically prevents the start sequence from being repeated. In this way, the safety of the system is not put at risk by a drop in the mains voltage. This low-voltage protection works not only during start-up but also perma- nently during operation. CONSTRUCTIONAL FEATURES The control box circuitry is protected by a flame resistant, transparent plug-in type plastic housing. A central fixing screw locks the control box to the wiring base. The plug-in control box incorporates the microprocessor based timer, flame check and reset circuits. Manual reset from lock out and set to lock out is provided by a push button with an integrated LED information system. A variety of cable entry points provides complete flexibility for electrical wiring. The wiring base S98 is equipped with spare- and extraterminals and allows together with a variety of cable entry points utmost flexibility of electrical wiring. The DKG 972 are compatible with the TFI 812. Different are only the pre- and post-ignition times. Max. heating power according the limits in the Gas Appliance Directive. TECHNICAL DATA Operating voltage 220 / 240 V (-15... +10%) 50 Hz (±5%) or 110 / 120 V (-15... +10%) 60 Hz (±5%) Fuse rating 10 A fast, 6 A slow Power consumption ca. 12 VA Max. load per output - term. 3 ignition trafo 1.0 A, cos ϕ 0.2 - term. 5 + 6 solenoid valves 0.5 A, cos ϕ 0.4 - term. 7 alarm indicator 0.5 A, cos ϕ 0.4 - term. 4 auxiliary blower 2.0 A, cos ϕ 0.4 total load 4.0 A, cos ϕ 0.4 max. 16 A during 0,5 sec Reset time from lock out none Re-cycling / repetition (max. 4x) after a loss-of-flame during operation Sensitivity 1 µA min. ionisation current required 1.5 µA Sensitivity for stray light 0.4 µA Ionisation probe insulation probe - earth greater than 50 MΩ Stray capacitance probe- earth less then 1000 pF max. cable length < 3 m Flame detectors IRD 1020.1 side-on or end-on viewing UVD 971 end-on viewing Weight incl. Wiring base 190 g Mounting position any Protection class IP 40 Approved ambient parameter for control and flame detector max. 95% at 30° C - for operation -20° C... +60° C - for storage -20° C... +80° C Build-up of ice, penetration of water and condensing water are inadmissible Approvals according to European standards EN 298 and EN 230, as well as all other relevant Directives and standards Classified acc. to EN 298 ATLLXN For 2-stage atmospheric gas burners Flame detection: - Ionisation probe - Infrared-flicker detector IRD 1020.1 - UV flame sensor UVD 971 Model waiting time start pre-ignition time Stray light monitoring safety time post-ignition time delay 2nd-stage tw tvz tf ts tn tv2 05 12 3 5 5 4 25 10 12 3 5 10 9 25 Table of timings (sec.) EN1C-0127SZ20 R0305 2 1.2 Lock-out diagnoses In case of a failure the LED is permanently illuminated. Every 10 seconds the illumination is interrupted by a flash code, which indicates the cause of the error. Therefore the following sequence is performed which is repeated as long as the unit is not reset. Sequence: illuminated phase dark phase Flash-Code dark phase ❘ ❚ ❚ ❚ ❚ for 10 sec for 0.6 sec for 1.2 sec Error diagnosis Error message Flash-Code Possible fault lockout ❘ ❚ ❚ ❚ ❚ within lock out safety time no flame establishment stray light ❘ ❘ ❚ ❚ ❚ stray light during monitored phase, detector may be faulty Flash-Code for manual lock out manual/external ❘ ❘ ❚ ❚ ❚ ❚ ❚ ❚ ❚ ❚ lock out (see also 3. lock out and reset) 2. Flame detection The following types of flame detectors are suitable: – Ionisation probe, temperature resistant material, well insulated (material and insulation same as for ignition electrode). – Infrared-flicker detector type IRD 1020.1 with mounting flange M 93 or the UV solid state flame sensor UVD 971. Flame detection using an ionisation probe is only possible in conjunction with mains supplies which provides a neu- tral earth connection. Connecting the IRD 1020.1 or UVD 971 the correct wiring has to be observed. 2.1 Stray light monitoring The stray light check is performed at the end of the pre- purge time for thr duration as mentioned in the table of timings. APPLICATION FEATURES 1. Information system The information system is microprocessor based and re- ports on all aspects of burner control box operation and flame supervision. It informs continuously about the actual programming sequence the unit is just performing. Besides monitoring of the programming sequence it also allows to identify errors during start-up of operation without any additional testing devices. The automatically performed diagnosis is a valuable tool which facilitates service/ maintenance work and therefore saves costs. The analyses of the error cause can be done directly on stage or if not possible afterwards as the lock out reason is stored in a non- volatile lock out mode memory. The information system communicates with the outside world using a LED (the used Flash-Code is similar to the Morse-Code). The messages are optically transmitted by a appropriately flashing LED. Using an additional terminal (optional), the messages can be recorded and displayed in easy readable form. 1.1 Programming sequence display The built-in microprocessor controls not only the pro- gramming sequence but the information system too. The individual phases of the programming sequence are displayed as Flash-Code. The following messages can be distinguished: Message Flash-Code waiting time ❘ ❘ ❘ . tw pre-ignition ❘ ❘ ❘ ❘ . tvz safety time ts ❚ ❘ . post ignition tn delay time to valve V2 ❚ ❘ ❘ . tv2 running ❘ _ low mains voltage ❘ ❚ ❚ _ Internal fuse defect ❘ ❚ _ > control box defect Description ❘ = short pulse ❚ = long pulse . = short pause _ = long pause DKG 972 3 DKG 972 3. Lock out and reset The unit can be reset or brought into lock out mode in two different ways: Internal In the lock out case the unit can be reset by pushing the built- in button meaning a new start-up cycle is performed. External Instead of using the built-in lock out button the same function can be achieved by using an external button which connects terminal 9 with A (see also circuit and block diagram). If the pushputton (internal or external) is pressed during normal operation or during the start sequence for more then 3 sec. and afterwards released, the control box will perform a shutdown. Please note The unit can only be brought to lockout mode or be reseted if power is applied to the unit. 4. Low-voltage protection at 220 / 240V (110 / 120V) nominal voltage The mains voltage has to be more than 187 V eff (94 V eff ) in order to allow the unit to perform a start-up. The mains voltage is not only monitored in the start-up phase but also permanently during operation. If the voltage drops below < 160 V eff (80 V eff ) during start-up or run time the control box proceed to safety shut-down and goes into a waiting status. If the voltage rises again, the control box performs automatically a start-up as soon as the mains voltage is > 187 V eff (94 V eff ) . 5. Safety The design and control sequence of the DKG 972 controls will comply with the currently applicable standards and regulations (see also TECHNICAL DATA). 6. Mounting and electrical wiring Wiring base: – 3 earth terminals with additional terminal for burner earthing – 3 neutral terminals with internal permanent connection to neutral terminal 8 – 2 independant spare terminals (S1 and S2) – extra terminals A, B and C are standard (wiring base S98 12-pin) – 2 slide-in plates and 2 easy knock out holes plus 2 knock out holes in the base bottom faciliate the base wiring Please note To assist trouble-free operation the main neutral connection terminal 8 in the wiring base must be fully tightened. The terminal screws are already in the undone position. To connect a wire to the terminal, the screw only needs to be fastened. General: The control box and detector probes should not be subjected to excessive vibration. 4 INSTALLATION INSTRUCTIONS AND MAINTENANCE 1. Important notes – The controls must be installed by qualified personnel only. The relevant national regulations have to be observed. – On commissioning the wiring has to be carefully check- ed according the appropriate diagram, Incorrect wiring can damage the unit and endanger the installation. – The fuse rating has to ensure that the limits specified in TECHNICAL DATA will not be exceeded. If these precau- tions are not observed, the effect of a short circuit can cause severe damage to the control and installation. – For safety reasons a minimum of one control shutdown every 24 hours has to be observed. – Disconnect the mains before the control box is plugged in or out. – The control box is a safety device and must not be opened! 2. Function control For safety reasons the flame detection system should be tested on commissioning the installation as well as after a service or longer shut-down. a) Attempt to start with gas valve closed: – At the end of the safety interval -> Lockout b) After a normal start, with the burner in operation, close the gas valve: – After restart at the end of the safety interval -> Lockout DKG 972 3. Fault finding The built-in information system facilitate the trouble shooting in the case of problems occurring during start-up or during operation. A list of possible lock out messages can be found in APPLICATION FEATURES chapter 1.2. Please note: The control box is locked in lock out mode and the reasen for the lock out is displayed until the control box is reset, either by an internal or external reset (see also subject “3. Lock out and reset"). Removing the control box from its wiring base or by interrupting the supply line may not reset a lock out. Therefore, by applying power, it needs 2-3 secs. before the control box goes to lock out again and the cause of the last lock out. Error Possible fault Burner not working - Thermostat circuit open - Faulty electrical wiring - Mains voltage < 187 V (< 80 V) - Terminal A continuously on power (e.g. terminal A is used as a support terminal) After 2-3 secs. after applying - Control box has not been reseted power. the unit goes to lock out Burner starts, - stray light signal during waiting flame not established, time lock out - no ignition or no fuel Burner starts, - no or too low flame signal (min. flame established, valves see TECHNICAL DATA) after safety time, - wrongly wired, phase and neutral lock out reversed - Ionisation probe dirty, broken or has contact to frame ground - too little light on flame sensIor (IRD) 5 BLOCK DIAGRAM DKG 972 DKG 972 CIRCUIT AND TIMING DIAGRAM DKG 972 term. 8 term. 1 term. 9 blue black brown IRD 1020.1 UVD 971 IRD- OR UVD CONNECTION max. 10 A fast 6 A slow Ph IS N 123456789 A HS ST RT EV Z V1 SA Flame amplifier Reset µC Reset and lock out Power supply monitoring 13456789A rz rv1 rv2 rs RZ RV1 RV2 RS Fault display Information system EEPROM Oscillator tw tf tvz tn ts tv2 HS Mains switch GW Gas proving switch ST Limit thermostat RT Control thermostat EV External reset and lock out button IS Ionisation probe (IRD 1020.1, UVD 971see separate diagram) Z Ignition V1 Solenoid valve, 1st-stage V2 Solenoid valve, 2nd-stage SA External lock out signal M Auxiliary blower tw Waiting time tf Stray light monitoring tvz Pre-ignition time tn Post-ignition ts Safety time tv2 2nd-stage delay µC Watchdog Mains monitoring Power supply GW V2 M DKG 972 AND SOCKET 62,5 4,5 38,5 24 86 60 24 30 30 44 M4 Earth Reset button 57-60 25 35 30 Underside cable entry ø16 mm 16 ORDERING INFORMATION ITEM DESIGNATION ITEM NO. Control box DKG 972 Mod. 5 0332005 Control box DKG 972 Mod. 10 0332010 Control box DKG 972 Mod. 10 110 / 120V 50Hz 0332310 Control box DKG 972 Mod. 10 110 / 120V 60Hz 0332410 Socket Wiring base S98 12-pin 75310 Insert plate PG-Plate 70502 optional Cable entry plate 70503 Flame detector IRD 1020.1 end-on 16532 Flame detector IRD 1020.1 left 16533 Flame detector IRD 1020.1 right 16531 optional UVD 971 16722 Support for IRD Holder M93 for IRD 1020 59093 Support for UVD Holder M74 for UVD 59074 Connection cable Plug type, 3 core cable, 0.6 m with tag wire ends 7236001 The above ordering information refers to the standard version. Special versions are also included in our product range. Specifications subject to change without notice Slide-in plate VARIATION IRD right left axial UVD 971 IRD 1020.1 29 50 UVD = 29 IRD = 44 21,8 ø13,5 UVD = 89 IRD = 104 29 21,8 HOLDER M 93 FOR IRD 35 3 14 4.5 26 15.1 48 17 ø20.5 4 HOLDER M 74 FOR UVD ø 14 35 3 ø20 4,5 26 4 48 7 Combustion Controls EMEA - Local Honeywell Sales Offices France Spain Honeywell SA Honeywell S.A. Parc Technologique de St. Aubin Josefa Valcárcel, 24 Bâtiment Mercury – BP87 28027 Madrid 91193 Gif-Sur-Yvette Cedex SPAIN FRANCE Phone: (33) 1 60 19 80 00 Phone: (34) 9 13136100 Fax: (33) 1 60 19 81 81 Fax: (34) 9 13 13 61 27 internet: www.honeywell.fr internet: www.honeywell.es Eastern Europe United Kingdom Honeywell s.r.o. Honeywell Control Systems Ltd Mlynske Nivy 73 Honeywell House, Arlington Business Park PO Box 75 Bracknell 82007 Bratislava 27 Berkshire, RG12 1EB SLOVAKIA UNITED KINGDOM Phone: (421) 2 58247 400 Switchboard +44 (0)1344 656000 Fax: (421) 2 58247 415 Information Centre Tel +44 (0)1344 656235 Information Centre Fax +44 (0)1344 656240 e-mail: [email protected] Email: [email protected] internet: www.honeywelluk.com Germany, Austria, Switzerland Benelux Honeywell GmbH Honeywell B.V. Kaiserleistrasse 39 Laarderhoogtweg 18 63067 Offenbach 1101 EA Amsterdam Z.O. DEUTSCHLAND THE NETHERLANDS Phone: (49) 6 980640 Phone: (31) 2 05656911 Fax: (49) 69 81 86 20 Fax: (31) 2 05 65 66 00 internet: www.honeywell.de internet: www.honeywell.nl Italy Honeywell S.r.l. Via P. Gobetti, 2/B 20063 Cernusco sul Naviglio (MI) ITALY Phone: 39 02 92146 1 Fax: 39 02 92146 888 internet: http://www.honeywell.com/sites/it/