Hy,
I have a problem with my WinCC 7.
I made a little program in PCS7 and I create an OS directly in the Project (for use PLCSIM). I compiled the OS and when a want to activate the runtime in loading process I got the following error:
«Unhandled exception was raised. Look file «script.log» for details.»
— This error comes from C:WINDOWSsystem32nrdll.dll
After I clicked OK, my project it’s [Active] but no picture is showed.
If I click on the WinCC icon from the toolbar, and click Start Graphics RunTime I got an error
«The system cannot find the file specified.»
, if I clicked OK I got another error
«Keine Verbindung zur Aktionssteuerung».
If I try to deactivate the project my computer stuck.
I tried to make a simple project only in WinCC and the Runtime works.
In the SCRIPT.LOG I have the following information:
Code: Select all
//====================================================================
// WinCC reported exception with code: C0000005 ACCESS_VIOLATION
// Date: 18.4.2011 - Time: 22.27. 0
// Caused at logical address 7C934322 01:00033322
//====================================================================
// FAULTING MODULE: C:WINDOWSsystem32ntdll.dll
//====================================================================
// Registers:
// ----------
// EAX:00000001
// EBX:00000015
// ECX:7C91003D
// EDX:00150608
// ESI:00000015
// EDI:7FFDC000
// CS:EIP:001B:7C934322
// SS:ESP:0023:0150FF24 EBP:0150FF64
// DS:0023 ES:0023 FS:003B GS:0000
// Flags:00010202
//
// Call stack:
// -----------
// Address | Frame |
// ---------+----------+----------------------------------------------
// 7C934322 | 0150FF64 | RtlDeleteAtomFromAtomTable+2D4
// 78543412 | 0150FF70 | endthreadex+23
// 78543439 | 0150FFA8 | endthreadex+4A
// 785434C7 | 0150FFB4 | endthreadex+D8
// 7C80B713 | 0150FFEC | GetModuleFileNameA+1B4
//====================================================================
If anyone have an idea about what can be, please post an answer.
Thank you!
Question: |
What does this error message mean? |
---|---|
Context: |
All versions of PVSS. |
Version: |
1.26 |
WinCC-OA/PVSS sometimes gives cryptic errors! Here is an explanation of the ones we’ve come across. If you have a message to add, please feel free to contact us by following the Feedback link below.
IMPORTANT: ETM have recently started their own list of cryptic messages. If you cannot find your message in this Cern list, look at the messages page on the ETM Portal.
Our message explanations are in alphabetical order. Don’t forget you can search for a string within the page when using most web-browsers.
Please note that the «NV» manager messages can also be produced by the «UI» manager (as of PVSS 3.6).
Message Text |
Explanation |
|
Remarks: Seen in the PVSS Console Log file. Cause: When two managers’ Remedy: Use a unique |
Cannot open >< for cerr/cout! (Message 1) |
Remarks: These messages have only been seen occurring together and then only on Windows. Explanation 1: There was an incompatibility between PVSS and the setting of the Windows environment variable TEMP on the machine. Normally TEMP points to just one single directory. If you point TEMP to a path of directories, PVSS cannot cope. (The problem was reported to ETM in Nov. 2005.) |
|
This message can appear when starting the Project Administrator (PA). It means that your username does not have sufficient privilege to run this particular project, possibly because this project was created by someone else. For a full discussion of this message see the FAQ Which Windows privileges do I need to run PVSS-II V3.* ? |
|
Remarks: Produced by the valarch task at startup. Click for a Full explanation |
On Linux: Can’t fetchpvsspath , exiting On Windows with WinCC-OA >= 3.12: Cannot fetch installation path from «C:ProgramDataSiemensWinCC_OApvssInst.conf»! Either the file doesn’t exist or isn’t readable or there is some error in file content or it is locked? («C:/ProgramData/Siemens/WinCC_OA/pvssInst.conf.lck») Exiting… |
${PVSS_II_ROOT}/ Alternative explanation 2: WinCC OA 3.15 — Installation, Distribution |
Checking environment … |
From PVSStoolSyncTypes. See the note in the FAQ. |
CreateDbResources::makeConfigFileWithoutLang rename failederrno: 2 (1), <dateTime> exit(1) called! |
This message can appear when trying to create a new project in a path which contains space characters — as in «Documents and Settings». The workaround is to create your project in a path with no embedded space characters. |
|
Means «PVSS project name is already running.»Error appears in German by default. The new instance cannot even get started well enough to identify your preferred language! |
Driver number 1 is not running! |
Seen when PARA starts up. Reason: The Simulation Driver with number 1 is not running. This driver is created automatically in every project. If you have deleted it, put it back! |
|
Click for a full explanation |
Error creating Project! For further information see the log file: WINCCOA_PATH/log/PVSS_II.log |
Have a look in the logfilein the «system tree» i.e. where WinCC-OA itself was installed (for example C:SiemensAutomationWinCC_OA3.11logPVSS_II.log) for additional diagnostics. Then come back here and look in the list below for those new messages! NB There is, of course, nologfilein your project folder that you can inspect — as your project failed to create! If there is no file WINCCOA_PATH/log/PVSS_II.log in the system tree either, then this certainly means that your username is running without the necessary privileges. Please review the WinCC-OA installation instructions (ie get Local Admin privs). |
WCCOAui (0), 2014.11.26 10:51:21.974, SYS, SEVERE, 7/pa, paCreateProjExtend, Error when creating the project ‘C:/Projects/sillyProject’ |
You are trying to create a project on a machine where another project is already running. Stop the running project; Delete the files ofyournew (incompletely created) project and try again. |
|
Your username does not have sufficient privilege to create a new project. For a full discussion of this message see the FAQ Which Windows privileges do I need to run PVSS-II V3.* ? |
|
You have no privilege to write into the project folder. For a full discussion of this message see the FAQ Which Windows privileges do I need to run PVSS-II V3.* ? |
Error writing to the temporary location |
Popup window message. Typically observed during installation of PVSS. Occurs when you do not have administrator privileges on your computer. (You need local admin privilege!) |
|
This popup can appear when starting a project from the PVSS console. You may safely ignore it and proceed as if nothing had happened! Yes, really! For a full discussion of this message see the FAQ Which Windows privileges do I need to run PVSS-II V3.* ? |
Lost connection to Event Manager. Please save all data and restart this manager. Be aware that some actions might not work properly or even fail completely without communication to the Event Manager! <Quit now> <Try to continue> |
Message from a dangling UI. In nearly 100% of all casesyou really will want to press «Quit Now!» Believeme. See also How do I avoid crash notification dialogs? |
|
This message can appear when you choose a project in the Project Administrator (PA). It can mean that your username does not have sufficient privilege to run this particular project, possibly because this project was created by someone else. For a full discussion of this message see the FAQ Which Windows privileges do I need to run PVSS-II V3.* ? |
|
Click for a full explanation |
PVSS00xxx (0), <TIMESTAMP>, SYS, FATAL, 158, Could not create the server socket on port = nnnn: Permission denied |
See the FAQ Windows Port Allocation issue for a full explanation. |
PVSS00<manager> (<num>), <TIMESTAMP-X>, <TYPE>, <PRIO>, <error-num>, info-text and PVSS00<manager> (<num>), <TIMESTAMP>, SYS, INFO, 119, Last error |
In order to avoid filling the logfilewith endlessrepeated messages, PVSS will suppress adjacent repeats. Outputwill resume when a different message is written to the logfile. The message pair shown on the left is recorded in the logfile when output resumes. |
PVSS00data0:PVSS00data(0), <TIMESTAMP>:error allocating 550134892 bytes of memory! exiting … |
The PVSS Data Manager (DM) has crashed because your database is corrupt. This can happen after a power cut. |
PVSS00data (0), 2005.04.12 18:05:45.297, IMPL, SEVERE, 54, Unexpected state, DataManDpIntern, refreshSaveDirList,Fehler beim lesen der Verzeichnissen! |
After a project restore, these messages will appear if these directories do not exist: <proj_path>/db/pvss/save and <proj_path>/db/pvss/alsave You should simply create them by hand. The error will then go away. |
PVSS00data (0), <TIMESTAMP>, IMPL, WARNING, 54, Unexpected state, |
Click for a full explanation |
PVSS00data (0), <TIMESTAMP>, IMPL, WARNING, 54, dist_1:myValue.C2.AVG_WT0:_original.._value (Type: 70 Sys: 1 Dp: 362 El: |
Your Value Archive manager is not running. (The example on the left is complaining because manager number 2 is stopped.) |
PVSS00data (0), <TIMESTAMP>, IMPL, WARNING, 54, Unexpected state, |
This message means that the dp-list in a sum-alert-handling that is configured at the dp-element <DP-Element-Name> refers to another dp-element <unknown |
PVSS00data (0), 2011.12.13 16:48:58.851, IMPL, SEVERE, 54, Unexpected state, AlertHistory, switchFiles,letzterDateiwechselnichtbeendet |
The message is saying that you cannot switch to a new alert archive file because the previous file switch operation has not yet completed. There is a known problem (at least in PVSS3.8.2) whereby the fileswitchoperation never completes. Contact us for advice. |
{{6/20/2003, 11:03:46 AM: Manager terminated unexpectedly C:ETMPVSS22.12binPVSS00valarch.exe -num 0 -log +file -config {{PVSS00data (1), 2003.06.20 11:03:46.262,SYS ,SEVERE , 63, «Connection |
Context: When a value archive manager is starting |
PVSS00data (0), 2008.12.02 22:01:22.969, SYS, SEVERE, 69, Database error, DataManTask, dbError, RAIMA Database Error *** Code:-4 (PROGRAMMER/USER error: -4 PVSS00data (0), 2008.12.02 22:01:22.969, SYS, SEVERE, 69, Database error, DataManTask, dbError, RAIMA Database Error *** Code:-906 (SYSTEM/OS error: -906 PVSS00data (0), 2008.12.02 22:01:22.969, SYS, SEVERE, 69, Database error, DataManTask, dbError, RAIMA Database Error *** Code:-906 (SYSTEM/OS error: -906 PVSS00data (0), 2008.12.02 22:01:22.969, SYS, SEVERE, 69, Database error, TypeAndIdDb, open (The above repeated 5 more times, then: ) PVSS00data (0), 2008.12.02 22:01:26.103, IMPL, SEVERE, 54, Unexpected state, DataManDpIntern, init, Datenbank konnte nicht geoeffnet werden! PVSS00data (0), 2008.12.02 22:01:26.103, SYS, INFO, 0, , Loading DpIdentification PVSS00data (0), 2008.12.02 22:01:26.120, SYS, SEVERE, 69, Database error, DataManTask, dbError, RAIMA Database Error *** Code:-1 (PROGRAMMER/USER error: -1 PVSS00data (0), 2008.12.02 22:01:26.120, SYS, SEVERE, 69, Database error, DataManTask, dbError, RAIMA Database Error *** Code:-27 (PROGRAMMER/USER error: -27 PVSS00data (0), 2008.12.02 22:01:26.120, SYS, SEVERE, 66, Error when connecting, DataManager, initialize PVSS00pmon (1), 2008.12.02 22:01:26.188, SYS, INFO, 11/pmon, Detected stopped manager PVSS00data(0) — restarting it #1 |
At project startup(project won’t start!) |
PVSS00pmon (1), <TIMESTAMP>, SYS, INFO, 20/pmon, Got START_ALL command from 127.0.0.1, starting the project PVSS00pmon (1), <TIMESTAMP>, SYS, INFO, 1, Manager Start, C:ETMPVSS23.8binPVSS00data.exe -PROJ 381SupportProject -pmonIndex 1 PVSS00data (0), <TIMESTAMP>, SYS, INFO, 1, Manager Start, PROJ, 381SupportProject, V 3.8 — 3.8 SP1 linked at Apr 2 2009 04:48:28 PVSS00data (0), <TIMESTAMP>, SYS, INFO, 0, , (Re)Opening databases in single user mode without transaction logging. PVSS00data (0), <TIMESTAMP>, SYS, SEVERE, 69, Database error, ValHistDb, open, 0000000000ValHist PVSS00data (0), <TIMESTAMP>, IMPL, SEVERE, 54, Unexpected state, DataManDpIntern, init, Datenbank konnte nicht geoeffnet werden! PVSS00data (0), <TIMESTAMP>, SYS, INFO, 0, , Loading DpIdentification PVSS00data (0), <TIMESTAMP>, SYS, SEVERE, 69, Database error, DataManTask, dbError, RAIMA Database Error *** Code:-1 (PROGRAMMER/USER error: -1 PVSS00data (0), <TIMESTAMP>, SYS, SEVERE, 69, Database error, DataManTask, dbError, RAIMA Database Error *** Code:-27 (PROGRAMMER/USER error: -27 PVSS00data (0), <TIMESTAMP>, SYS, SEVERE, 66, Error when connecting, DataManager, initialize PVSS00data (0), <TIMESTAMP>, SYS, INFO, 2, Manager Stop |
At project startup- project won’t start. You are logged in as somebody else — not the person who created and still owns this project. You do not have proper permissions on the files to start this project successfully. Logout and login again as the correct user! |
PVSS00data (0), <TIMESTAMP>, SYS, SEVERE, 69, Database error, StAHVariableUtils, loadVariable *** Code : 6 PVSS00data (0), <TIMESTAMP>, SYS, SEVERE, 69, Database error, StAlertRec, getAlertClass, Variablenicht ladbar |
These log-messagesdescribe that an alert-classwas deleted but that some alert-handling-configs still refer to this alert class. You should perform the following steps: |
PVSS00data (0), <TIMESTAMP>, SYS, SEVERE, 69, Database error, StAHVariableUtils, deleteVariable6 PVSS00data (0), <TIMESTAMP>, SYS, SEVERE, 69, Database error, AlertCacheItem, remove, Code :0 |
These messages can appear when the database for the «living»-alerts gets corrupted. The log-messagedescribes that an alert cannot be removed. Possibly you are seeing this log-messagebecause an alert is in state»gone and acknowledged» and hence is no longer shown in the «living»-alerts. You could try to solve this problem with an initialization of alliving-database: |
PVSS00data(0), 2010.12.08 17:09:01.421, SYS, SEVERE, 69, Database error, DataManTask, dbError, RAIMA Database Error *** Code:-909 (SYSTEM/OS error: -909 file record limit exceeded |
See full description here |
PVSS00databg (1), <TIMESTAMP>, IMPL, WARNING, 51, Parameter incorrect, DataBgDpIntern, openDatabases, Datenbank konnte nicht geoffnet werden, retry: 5 PVSS00databg (1), <TIMESTAMP>, SYS, SEVERE, 69, Database error, DbDirDb, open PVSS00databg (1), <TIMESTAMP>, PARAM,FATAL, 54, Unexpected state, DataBgDpIntern, init, Datenbankkonntenichtgeoeffnetwerden,bitte lm_ippruefen! |
The PVSS lock manager is not running properly. Stop the project and all PVSS tasks completely. Kill any stray PVSS lock manager («lockmgr») task. Restart the project. If this fails, try restarting the lock manager manually from your normal prompt (i.e. NOT from a root prompt!) with: <pvss_path>/bin/lm_ip -a lockmgr -f 1600 for example, with: /home/PvssSystems/3.0.1SP1/pvss2_v3.0/bin/lm_ip -a lockmgr -f 1600 |
PVSS00databg (1), <TIMESTAMP>, IMPL, SEVERE, 54, Can also be aassociated with the appearance of: PVSS00databg (1), <TIMESTAMP>, SYS, SEVERE, 69, Database error, DataBgActionManager, status record first/next-24 PVSS00databg (1), <TIMESTAMP>, SYS, SEVERE, 69, |
These lines appear in the log file every minute or so if the folders <PROJ_PATH>/db/pvss/save and <PROJ_PATH>/db/pvss/alsave do not exist. Solution: Create these directories. |
PVSS00dist (93), 2006.02.16 12:34:35.378, SYS, SEVERE, 65, Wrong destination address, (SYS: 1 Dist -num 1 CONN: 1), REDUNDANCY_SYS_MSG PVSS00dist (93), 2006.02.16 12:34:35.378, REDU, INFO, 0, , Closing connection topassiv peer (SYS: 91 Dist -num 91 CONN: 1) |
These messages appear in a distributed system scenario, in the log of a client system that is trying (and failing) to make a solid contact with another (server) system. These messages are followed by a «Connection lost» message. The message pair is often repeated as the connect operation is retried. *Explanation: *The client is specifying a target PVSS system number on the server machine. Although a PVSS system is running on the server, it does not have that corresponding system number. In the example shown, the client (system number 93) was trying to contact system number 91. This was incorrect as the system number of the system that was actually running on the remote server machine was number 1. Action: Correct the entry in the client system’s config file where it says distPeer = «sysName» sysNumber. Then you should see a much nicer message such as: PVSS00dist (93), 2006.02.16 12:38:25.237, SYS, INFO, 4, Connected to, (SYS: 1 Dist -num 1 CONN: 1) @ pcitco91.cern.ch |
PVSS00dist(n) ,SYS,SEVERE,159,Could not create the alive-server socket on port = 4500: Permission denied |
This is not a username/permission problem. Rather, someone else is using that port. (In WXPSP2 it’s the lsass task.) |
PVSS00event (0), <TIMESTAMP>, IMPL, WARNING, 54, Unexpected state, DP: (Type: 221 Sys: 7 Dp: 945182 El: 2 : _original.._stime), MAN: (SYS: 7 Event -num 0 CONN: 1), EvDpManager::getDpValueAttribut: no element |
User accidentally deleted some PVSS internal datapoints and thoroughly confused the Event Manager! |
WCCILevent (0), 2015.06.17 15:12:02.369, IMPL, SEVERE, 54, Unexpected state, ElementTable, getElementFullName, Element/Parent element not found — Type 130, Element 47, Parent element 0 WCCILevent (0), 2015.06.17 15:12:02.368,PARAM,WARNING, 8, Element does not exist, DP: (Type: 130 Sys: 47 Dp: 308 El:47 : _original.._value), MAN: (SYS: 47 Data -num 99 CONN: 1) |
You are trying to accessa aDP or DPE that no longer exists. Which one?Unfortunatelyit is not possible to retrieve the name of the DP/DPE — as it has been deleted! You may retrieve the Datapoint Type (DPT) name (which might give you a clue) by exporting everything with the Ascii Manager and looking in the .dpl file. Clearly, even that won’t work if you have deleted the DPT as well !! |
PVSS00event (1), <TIMESTAMP>,PARAM,WARNING, 54, «Unexpected state», dcs1:PLC1_AI_Val_Pression_Rich.value:_alert_hdl.3._alert_color Type: 0 Sys: 1 Dp: 8853 El: 2 Conf: 23 |
See the FAQ Too many pending alerts. |
WCCILevent (0), 2015.02.20 15:24:26.023, SYS, SEVERE, 39, Connection lost, Send buffer limit exceeded, closing connection to (SYS: 32 Ui-num 1 CONN: 1) @ pcen33889.cern.ch, [PeerItcIOHandler::sendCall] |
A similar message can be generated by any manager trying to send a message to another manager. This example was generated by the Event Manager trying to send to the UI. The UI was not absorbing messages quickly enough and the allocated EM output queue filled up. This message, its causesand your possible actions, are described at length in the ETM FAQ :https://portal.etm.at/index.php?option=com_quickfaq&view=items&cid=26:logs&id=356:wincc-oa-managers-syssevere-send-buffer-limit-exceeded-closing-connection-to-connection&Itemid=54 You should also consider:
Recall that the System Management Panel > Diagnostics tab > System Overview panel helps you tovisualiseoverall flows of message traffic in WinCC-OA. |
PVSS00event (0), <TIMESTAMP>, IMPL, SEVERE, 54, Unexpected state, ElementTable, getElementFullName, Element/Vaterelement nicht gefunden — Type 144, Element 40, Vaterelement 0 |
A DPE that used to exist cannot be found any more. |
PVSS00event (0), <TIMESTAMP>, PARAM,WARNING, 22, Internal consistency check for config failed, <DP-Element-Name>:_alert_hdl, MAN: (SYS: 1 Event -num 0 CONN: 1), SumAlert config does not have an id list nor an id |
This message says that the sum-alert-config for <DP-Element-Name> is not configured correctly as there is neither a dp-list nor a dp-pattern defined. |
PVSS00event (0), <TIMESTAMP>, PARAM,SEVERE, 92, DP functions: infinite loop found, DP: <DP-Name>:_dp_fct, EvDpManager::, handleDpFuncHL #1, check dp function |
This log-message appears in 2 situations. 1) An infinite loop really is configured. E.g. A dp-function on dpe A is set to react on a change in dpe B AND A dp-function on dpe B is set to react to a change in dpe A. 2) Yourdp-function was called more than 25 times with the same time-stamp on theinput-variables. You should check the configuration of thedp-elements which are used asinput-variables. (You should also check the configuration of where their values are coming from, eg your OPC group settings.) |
PVSS00NV(n) , IMPL, SEVERE, 54, Unexpected State |
[Click for more] |
PVSS00NV (0), SYS, WARNING, 133, Could not load shared library |
[Click for more ] |
PVSS00opc (7), <TIMESTAMP>, SYS, SEVERE, 54, Unexpected state, OPCServer, initialize, Could not get CLSID for OPC20CanOpen+ |
Your OPC client cannot connect to the OPC Server. |
WCCOAopc (7), 2014.07.09 15:14:06.024, IMPL, WARNING, 54, Unexpected state, The above message appears with: WCCOAopc (7), 2014.07.09 15:14:06.024, IMPL, SEVERE, 54, |
This is not a problem with WinCC-OA itself, but with your WinCC-OA OPC UA client trying to use the ELMB OPC Server from Atlas. The problem appears when certain libraries are not found in your installation. Please (re-)install them as follows: If your NICE PC is being managed with CMF:
If your NICE PC is not under CMF, you can access the two relevant files directly from DFS:
Important: Please install (run) vcredist2008_x64.exe first and only then install the OPC Core Components Redistributable (x64).msi. |
PVSS00opc (6), <TIMESTAMP>, IMPL, WARNING, 54, Unexpected state, OPCGroup:CAENOPCGroupIn, additem, AddItems returned Incorrect function. |
[Click for more ] |
PVSS00opc (2), 2005.07.01 10:22:41.494, IMPL, WARNING, 54, Unexpected state, OPCGroup, groupGA, Could not start Refresh on MatrikonLocalGroup:Unspecified error Accompanied with: PVSS00event (0), 2005.07.01 09:09:24.994,PARAM,WARNING, 7, Datapoint does not exist,DP: :_original, MAN: (SYS: 1 Driver -num 2 CONN: 1) |
Means that your config file refers to an OPC server but that you have not yet defined that OPC server in the PVSS panel. |
PVSS00opc ,WARNING, 54, Unexpected state,OPCGroup:MyOPCGroupName,start, No internal DP forgroup.Groupcannot be used! |
Often encountered after incorrectly installing PVSS 3.1 patch P256. Check again in the file |
|
See Why isn’t my console behaving correctly? |
{{PVSS00ui (1), <Timestamp>, CTRL, WARNING, 5/ctrl, Location of the following log entry: PVSS00ui (1), <Timestamp>, IMPL, WARNING, 0, , The parameter sNameOfChannelToBeTrended was not specified, ,}} |
This message is benign |
PVSS00ui (11), <TIMESTAMP>, PARAM,FATAL, 54, Unexpected state, initUimDpIdentifiers, _Ui_11.LayerOn.PanelName, no such name may also be seen with: PVSS00ui (11), <TIMESTAMP>, PARAM,WARNING, 7, Datapoint does not exist, CtrlDbg::init, _CtrlDebug_UI_11.Command |
You are trying to simultaneously run more UI managers than the system is configured for. Increase the number allowed by following the instructions described in this FAQ. |
PVSS00valarch(13), 2012.04.10 11:57:00.092:error allocating memory! exiting … |
Can also provoke a Data Manager crash. Try adding the following entry into your config file: [valarch] maxNumberOfReadThreads=1 See a full description in Jira case ENS-5235 . |
PVSS00valarch(11), 2012.04.10 12:00:57.516, IMPL, SEVERE, 54, Unexpected state, Didn’t get any appropriate mapping, stopping read, [ArchivSet.cpp:5323] |
Have you exceeded the Linux per-user limit on open files? See Which Operating System Settings may affect me? |
PVSS00valarch(n) ,IMPL, WARNING, 54, Unexpected state, Archive, doFileRestore, Not all files in action.files are present (ErrNum=28), Couldn’t find any from sets identified in list PVSS00valarch(n) , IMPL, SEVERE, 54, Unexpected state, Archive, doFileRestore, The action can not be started (ErrNum=31), Error encountered during processing of doFileRestore |
This message should not appear under normal circumstances. It implies that you have been fiddling around with the files in the Archive directories using Windows Explorer, i.e. without going through the PVSS panels. The message probably means that you have forgotten to copy youronline-backup(or at leastthe AR_X-files (where X is thearchive-number) from the VA-directories of an old system to the new system. (CT349326) |
PVSS00valarch(n) , Severe, Unexpected state |
[Click for more ] |
|
Remarks: This message / these messages are sometimes seen soon after installing PVSS on Windows. Cause: Lack of privilege. Remedy: Ensure you have appropriate rights on your machine. You need extensive rights to install PVSS properly. If you installed PVSS without these rights initially then you will need to re-install PVSS all over again, sorry! If PVSS was installed OK but you need to simply run, you may need different rights. See Which Windows privileges do I need to run PVSS2 V3.*? |
unspecified user id PVSS00data (0), 2007.09.17 14:03:11.068, SYS, SEVERE, 69, PVSS00data (0), 2007.09.17 14:03:11.088, IMPL, WARNING, 51, PVSS00data (0), 2007.09.17 14:03:11.098, SYS, SEVERE, 69, |
If you see a slew of messages like these, does your Windows/Linux login username contain an embedded space or other inappropriate character? See Which Windows/Linux login name restrictions exist for PVSS users? |
|
[Click for a full explanation ] |
WCCOAui (0), 2012.10.09 17:30:52.495, CTRL, WARNING, 76, Invalid argument in function, |
This happens under Windows 7 and later. It means that you were running the Project Administrator with normal privilege when you tried to create your project (rather than with admin privilege.) NB Even if you are an admin user on your machine, ie your username has general permission to invoke admin rights, you still need to explicitly invoke those rights. To always run the Project Administrator with admin rights, Right click the PA icon > Properties > Advanced > Run as administrator |
WCCOAui (0), …15:02:43.072, SYS, INFO, 1, Manager Start, PROJ, OWS_3.11-NORDB-ISO, V 3.11 — 3.11 SP1 platform Windows AMD64 linked at May 27 2015 15:48:25 |
Affects Users logging into Production systems at Cern via an Operator Workstation (OWS) application on Windows. (OWS supports a scattered UI viewer into the production system.) If you are merely seeing this message in the logfile, you can safely ignore it. Someone, somewhere, though, will be seeing the popup described above! Who? It’s impossible to say. It might be on any of the terminal servers (unlikely) or on some user’s own desktop development machine (quite likely) or even on a VM that someone happens to be using… When that someone moans that he can’t start the UI, you can now help him In the meantime, you may sleep peacefully. The production system will continue to run correctly. Explanation: The problem manifests when more than one OWS scattered viewer is run on a single machine, each connecting to a different project. WinCC-OA by default mis-diagnoses this as a problem. The corrective technical details are discussed here. |
WCCOAascii (1), 2012.10.18 07:34:14.391, SYS, INFO, 2, Manager Stop |
Error -50 means: DpIdentifier <DpId> for attribute <name> does not exist. |
WCCOAascii_log:WCCOAascii (1), 2013.05.29 16:23:28.516, SYS, INFO, 2, Manager Stop |
Error 56 means that your logfilehas at leastone line such as the following in it : Explanation: You are trying to import a DPE with an internal ID that has already been used in the current project. It’s just a warning. WinCC-OA uses a new ID. |
WCCOAascii_info:DpType (206): Element with ID 276 other than FwCaenCrateSY1527.Information.Debug.MemoryStatus.Free differs in type, given ID will be ignored |
This message is saying that you are trying to import a DPT definition but that the Event Manager already has inside it an existing DPT definition using the same DPE ID you mention in your new definition. Your new DPT definition will be skipped entirely. |
- Обязательно представиться на русском языке кириллицей (заполнить поле «Имя»).
- Фиктивные имена мы не приветствуем. Ивановых и Пупкиных здесь уже достаточно.
- Не писать свой вопрос в первую попавшуюся тему — вместо этого создать новую тему.
- За поиск и предложение пиратского ПО и средств взлома — бан без предупреждения.
- Рекламу и частные объявления «куплю/продам/есть халтура» мы не размещаем ни на каких условиях.
- Перед тем как что-то написать — читать здесь и здесь.
-
Rom
- здесь недавно
- Сообщения: 7
- Зарегистрирован: 26 окт 2019, 10:03
- Имя: Роман
Помощь с WinCC AlarmControl
Сообщение
Rom » 26 окт 2019, 10:36
Добрый день, уважаемые специалисты.
На один наш завод оборудование и программу (WinCC, как я понимаю) устанавливали китайцы и большая часть диалоговых окон на китайском. Например, окно свойств WinCC AlarmControl полностью на китайском языке. Некоторые элементы они русифицировали: рабочие сообщения, окна, схемы и диалоги, но именно настройки не зная китайского можно делать либо на ощупь, либо имея перед глазами анлоязычный аналог этих диалогов. У меня их нет.
Проблема такая: в списке сообщений Alarm Log перестали выводиться сами сообщения. В окне, где нарисована схема, ошибку видно, сигнализация срабатывает, а текст ошибки отсутствует. Возможно, что кто-то из операторов что-то поменял в настройках и сообщения перестали выводиться. Как вернуть эти сообщения?
Кто-нибудь может помочь разобраться с этой проблемой?
Думаю, что дирекция предприятия сможет оплатить расходы.
Если кому-то будет интересно, то я дам контактные телефоны.
Upd. Выяснилось, что на китайском пишет про сбой подключения ко всем серверам.
-
Rom
- здесь недавно
- Сообщения: 7
- Зарегистрирован: 26 окт 2019, 10:03
- Имя: Роман
Помощь с WinCC AlarmControl
Сообщение
Rom » 28 окт 2019, 11:22
Подскажите пожалуйста, где можно почитать про то, как и с кем обменивается данными Alarm Logging. Выяснилось, что сообщения перестали поступать после выключения компьютера и какого-то оборудования для профилактики.
-
ZuElecRu
- освоился
- Сообщения: 281
- Зарегистрирован: 09 авг 2016, 13:49
- Имя: Чистилин Андрей Анатольевич
- Страна: Россия
- город/регион: Малоярославец
- Благодарил (а): 29 раз
- Поблагодарили: 34 раза
Помощь с WinCC AlarmControl
Сообщение
ZuElecRu » 28 окт 2019, 12:27
А программа на чем крутится: это компьютер или панель оператора, если панель то надо знать фирму и заказной номер. Если компьютер, то хотя бы скрин покажите.
-
Rom
- здесь недавно
- Сообщения: 7
- Зарегистрирован: 26 окт 2019, 10:03
- Имя: Роман
Помощь с WinCC AlarmControl
Сообщение
Rom » 28 окт 2019, 12:54
Программа на компьютере. Вот скрин:
Слева внизу написано на китайском «All server connections faild.» Справа, где два сетевых мониторчика, при подведении мышки написано, что нет подключения к localhost.
На основной вкладке показания датчиков изменяются, запускаются двигатели и все действия выполняются. Все работает.
Не работает только отображение ошибок.
-
POV
- специалист
- Сообщения: 643
- Зарегистрирован: 12 авг 2008, 11:05
- Имя: Патрушев Олег Валерьевич
- Страна: Россия
- город/регион: г. Н.Новгород
- Благодарил (а): 69 раз
- Поблагодарили: 123 раза
Помощь с WinCC AlarmControl
Сообщение
POV » 28 окт 2019, 13:27
Сообщения (alarms) и отображение/управление это разные подсистемы. Поэтому первое не работает, второе работает. Так бывает.
Нет соединения с SQL сервером, который хранит сообщения. Там несколько причин может быть — вроде даже здесь обсуждалось уже.
Одна из причин, например, https://support.industry.siemens.com/cs … 0&lc=en-RU
Права пользователей, изменение имени компа или сетевых настроек…
Не сломайте чего сильнее, если не уверены — резервное копирование наше все.
-
Rom
- здесь недавно
- Сообщения: 7
- Зарегистрирован: 26 окт 2019, 10:03
- Имя: Роман
Помощь с WinCC AlarmControl
Сообщение
Rom » 28 окт 2019, 15:44
Про бакапы знаю.
Т.е., единственная причина этого всего — проблемы соединения с SQL-сервером? Тогда, если работает SQL, то можно к нему подключиться через терминал и посмотреть список ошибок прямо в базе, как я понимаю. И в этом случает надо поправить ошибку коммуникации. А если SQL-сервер не работает, то тогда его достаточно будет запустить.
Там просто еще есть KEPServerEx (что это пока не понял, думаю, что как-то связано уже с железом) и этот рабочий компьютер подключен LAN-кабелем к оборудованию в шкафу. Вот я и подумал, что та железка, к которой подключен сетевой кабель, могла начать сбоить.
И вводило в заблуждение то, что в свойствах проекта — стоит Single-User project. Я подумал, что SQL-сервер здесь не нужен.
Всем спасибо за советы и ответы.
-
POV
- специалист
- Сообщения: 643
- Зарегистрирован: 12 авг 2008, 11:05
- Имя: Патрушев Олег Валерьевич
- Страна: Россия
- город/регион: г. Н.Новгород
- Благодарил (а): 69 раз
- Поблагодарили: 123 раза
Помощь с WinCC AlarmControl
Сообщение
POV » 28 окт 2019, 18:26
Rom писал(а): ↑28 окт 2019, 15:44
Т.е., единственная причина этого всего
Только одна из возможных.
Rom писал(а): ↑28 окт 2019, 15:44
Тогда, если работает SQL, то можно к нему подключиться через терминал и посмотреть список ошибок прямо в базе, как я понимаю. И в этом случает надо поправить ошибку коммуникации. А если SQL-сервер не работает, то тогда его достаточно будет запустить.
Упрощаете сильно ситуацию, увы, там все сложнее.
Rom писал(а): ↑28 окт 2019, 15:44
Там просто еще есть KEPServerEx
Это связь с ПЛК, скорее всего, так как вы управляете объектом, то, видимо, работает.
Rom писал(а): ↑28 окт 2019, 15:44
стоит Single-User project. Я подумал, что SQL-сервер здесь не нужен
Там все через него работает, тренды еще.
-
Rom
- здесь недавно
- Сообщения: 7
- Зарегистрирован: 26 окт 2019, 10:03
- Имя: Роман
Помощь с WinCC AlarmControl
Сообщение
Rom » 28 окт 2019, 20:11
Мдя… только что было все понятно, а теперь опять ни хрена не понятно
POV, а вы не могли бы подсказать, есть ли в программе (или проекте) какой-то ini-файл или файл с настройками, где их можно было бы посмотреть (или какие-то места, куда глянуть)? То же имя компа или сетевых настройки я могу посмотреть, а какие они должны быть? Где это можно узнать?
Я не то, что чайник, я до него не дотягиваю, т.к. впервые увидел эту программу в прошедшую пятницу. Да и сам нахожусь в некотором удалении от завода, поэтому перед очередной поездкой туда надо собрать максимально информации по настройке и диагностике.
Я так понимаю, вот это руководство должно подойти? https://support.industry.siemens.com/cs … 7&lc=en-RU
-
POV
- специалист
- Сообщения: 643
- Зарегистрирован: 12 авг 2008, 11:05
- Имя: Патрушев Олег Валерьевич
- Страна: Россия
- город/регион: г. Н.Новгород
- Благодарил (а): 69 раз
- Поблагодарили: 123 раза
Помощь с WinCC AlarmControl
Сообщение
POV » 28 окт 2019, 21:03
Rom писал(а): ↑28 окт 2019, 20:11
вот это руководство должно подойти
Именно это мне не понравилось, но читал по диагонали.
Но информации очень по СС много, плюс зависит от версии. Если бы мог дать конкретный совет, то давно бы написал. Я бы поискал информацию на форуме в германии, там много всего. Форум в России пока мало наполнен, но скопируйте вопрос туда.
-
Rom
- здесь недавно
- Сообщения: 7
- Зарегистрирован: 26 окт 2019, 10:03
- Имя: Роман
Помощь с WinCC AlarmControl
Сообщение
Rom » 19 ноя 2019, 20:32
Возвращаюсь со своими баранам…
На предприятии остановили сегодня этот цех на профилактику, поэтому смог сделать нормальный бакап и начать полноценно нажимать на все подряд.
В общих чертах, что было сделано и не дало ощутимых результатов:
1. SQL-сервер работает; при запуске sql studio (без запущенного проекта) там уже торчит одна база в стадии suspect (с этим пока не разбирался, возможно завтра буду смотреть, что это и зачем), но при запуске проекта создается другая база, которая указывает на файл из папки самого проекта). Она работает, и ошибок не выдает.
2. Галочка в Computer->Computer properties ->Startup->Alarm Logging Runtime стоит, но ССAlgRtServer.exe из процессов пропадает, даже, если его запускать руками. Висит несколько секунд и закрывается.
3. Сделал Reset в Alarm Logging. (Alarm Logging Editor Select Messages
Archive Configuration
Reset)
4. Запускал Reset_WinCC.vbs in C:Program FilesSiemensWinCCBin directory? Скрипт выполняется, но так же ссылается на ошибочную базу в sql, которая находится в статусе Suspect. Вот еще интересно, а скрипт Reset_WinCC.vbs надо запускать с закрытым проектом или с запущенным?..
5. Было где-то написано, удалить <projectname>.dc* из папки проекта. Это дало то, что все датчики на предыдущих окнах перестали работать, но в окне Alarm Logging появилась связь (загорелись индикаторы Lan зелеными и подключился к чему-то — к чему не понял). В самом файле .dcf редактором видел какие-то настройки, но все они ссылаются непонятно для меня куда. Прямых путей или названий файлов/баз там нет.
Еще читал, что можно сделать:
— check the messages from CPU, using the feature «CPU Messages» on Step 7
— try to reset data from SQL server tables using «CCArchiveManager.exe -reset all»
Очень буду благодарен за любую помощь!
А всем, кто уже помогал — огромное спасибо))
-
Rom
- здесь недавно
- Сообщения: 7
- Зарегистрирован: 26 окт 2019, 10:03
- Имя: Роман
Помощь с WinCC AlarmControl
Сообщение
Rom » 22 ноя 2019, 15:13
Нашел логи, там написано следующее:
PMActivate.log
2019-11-22 14:22:33.021 — ccProjectMgr.exe *** Error: CRTApplication::StartWinCCApplication(CCAlgRtServer.exe) Status(Failed) signaled
2019-11-22 14:22:33.023 — ccProjectMgr.exe CRTApplication::StartWinCCApplication(CCAlgRtServer.exe) Status(Success)
2019-11-22 14:22:33.024 — ccProjectMgr.exe *** Error: CRTApplication::StartWinCCApplication(CCAlgRtServer.exe) failed of WinCC
PMDiagnose.log
2019-11-22 14:22:33.022 — ccProjectMgr.exe *** Error: CRTApplication::StartWinCCApplication(CCAlgRtServer.exe) Status(Failed) signaled
2019-11-22 14:22:33.024 — ccProjectMgr.exe *** Error: CRTApplication::StartWinCCApplication(CCAlgRtServer.exe) failed of WinCC
WinCC_SStart_01.log
255,22.11.2019,14:22:31:001,0,1,SYSTEM,PC2,CCProjectMgr,WinCC Project Manager : Activate Project — CCAlgRtServer.exe — Status = START
255,22.11.2019,14:22:33:021,1003005,4,SYSTEM,PC2,Alarm Logging,Error while creating the run-time databases
255,22.11.2019,14:22:33:022,0,4,SYSTEM,PC2,CCProjectMgr,WinCC Project Manager : Activate Project — CCAlgRtServer.exe — Status = APPL —> START FAILED
255,22.11.2019,14:22:33:023,0,1,SYSTEM,PC2,CCProjectMgr,WinCC Project Manager : Activate Project — CCAlgRtServer.exe — Status = SUCCESS
Поиск под ошибке выдал https://support.industry.siemens.com/tf … ageSize=10
On the other hand, you can try to make a «general» reset of the archiving system.
— have the project open in the WinCC-Explorer and execute via «Run» the following:
ccarchivemanager.exe -resetall
Но снова получил ошибку
-
quq
- здесь недавно
- Сообщения: 46
- Зарегистрирован: 08 сен 2014, 08:56
- Имя: Курочкин Петр Александрович
- Благодарил (а): 12 раз
- Поблагодарили: 6 раз
Помощь с WinCC AlarmControl
Сообщение
quq » 27 ноя 2019, 14:17
Rom писал(а): ↑19 ноя 2019, 20:32
4. Запускал Reset_WinCC.vbs in C:Program FilesSiemensWinCCBin directory? Скрипт выполняется, но так же ссылается на ошибочную базу в sql, которая находится в статусе Suspect. Вот еще интересно, а скрипт Reset_WinCC.vbs надо запускать с закрытым проектом или с запущенным?..
Я всегда сначала «убивал» WinCC.
Может почистить папку с Алармами? при отключенном SQL.
Может переустановить все, только лицензии не потеряйте, лучше новый диск и вперед!
Вернуться в «Общие вопросы»
Перейти
- Работа форума
- База знаний (Knowledge Exchange)
- ↳ Eplan Electric P8
- ↳ Общий F.A.Q.
- ↳ Общие вопросы
- ↳ Новости
- ↳ Ошибки
- ↳ Проект
- ↳ Изделия
- ↳ Устройства
- ↳ Соединения
- ↳ Кабели
- ↳ Клеммы
- ↳ ПЛК
- ↳ Компоновка 2D
- ↳ Макросы
- ↳ Eplan API
- ↳ Сценарии (Только готовые решения)
- ↳ Внешняя обработка
- ↳ ProPanel
- ↳ Инструкции ProPanel (Только готовые решения)
- ↳ Прочие направления Eplan
- ↳ FieldSys (Топология)
- ↳ Preplanning
- ↳ Harness proD
- ↳ EEC One
- ↳ Advantech
- ↳ F.A.Q., Инструкции
- ↳ Allen Bradley
- ↳ Общие вопросы
- ↳ ПЛК
- ↳ Операторские панели
- ↳ B&R Automation
- ↳ F.A.Q.
- ↳ Danfoss
- ↳ DEIF A/S
- ↳ Общие вопросы
- ↳ UNI-LINE
- ↳ MULTI-LINE
- ↳ MULTI-LINE 300
- ↳ Emerson
- ↳ Общие вопросы
- ↳ КИП и регуляторы
- ↳ DeltaV
- ↳ ОВЕН
- ↳ Прософт-Системы
- ↳ Общие вопросы
- ↳ ПЛК REGUL
- ↳ Schneider Electric
- ↳ Общие вопросы
- ↳ ПЛК
- ↳ Панели оператора
- ↳ SCADA
- ↳ Электротехника
- ↳ Приводная техника
- ↳ SIEMENS
- ↳ Общие вопросы
- ↳ LOGO!
- ↳ ПЛК SIMATIC (S7-200, S7-1200, S7-300, S7-400, S7-1500, ET200)
- ↳ Simatic Step7
- ↳ Simatic TIA Portal
- ↳ Simatic PCS 7
- ↳ Операторские панели
- ↳ WinCC
- ↳ Приводная техника (Sinamics, Micromaster, Masterdrive, Simoreg, Simotics)
- ↳ SmartGen
- ↳ Общие вопросы
- ↳ Промышленные (береговые) контроллеры
- ↳ Морские контроллеры и устройства
- ↳ WEINTEK (операторские панели)
- ↳ F.A.Q., Инструкции
- ↳ Архив
- ↳ Микроконтроллеры и электроника
- ↳ Arduino
- ↳ Другие микроконтроллеры
- ↳ Электроника
- Общие вопросы АСУТП
- ↳ Общие вопросы
- ↳ Вопросы от студентов
- ↳ Литература
- ↳ Новости и отчётность
- ↳ Нормативы, ГОСТы, стандарты
- ↳ Информационная безопасность
- ↳ Проектирование и САПР
- ↳ Системная интеграция
- ↳ Разбор полетов
- ↳ Работа
- ↳ Заготовки для базы знаний
- ↳ Производство и технология
- ↳ MES — Системы автоматизации управления производством
- ↳ Метрология, КИП и датчики
- ↳ Исполнительные устройства, регуляторы
- ↳ Средний уровень автоматизации (управляющий)
- ↳ Алгоритмы
- ↳ Операторские панели
- ↳ Верхний уровень автоматизации (отображение)
- ↳ GE iFix
- ↳ Wonderware Intouch
- ↳ MasterScada
- ↳ SCADA+
- ↳ Alpha.Platform
- ↳ Интерфейсы, протоколы, связь
- ↳ Радиосвязь
- ↳ Полезное ПО
- ↳ Электротехника, энергетика и электропривод
- ↳ Генераторы и электростанции
- ↳ Теплотехника
- ↳ Подбор аналогов
- F.A.Q. (краткая выжимка из некоторых сообщений форума)
- ↳ Электротехника и электроэнергетика
- ↳ Документация
- ↳ Общие вопросы
- ↳ Оформление документации
- ↳ Нижний уровень автоматизации
- ↳ Средний уровень автоматизации
- ↳ Верхний уровень автоматизации
- ↳ Интерфейсы, протоколы, связь
- ↳ Функциональная и промышленная безопасность
- ↳ Электротехника и энергетика
- ↳ Автоматизация предприятия
- ↳ Описания средств автоматизации
- ↳ F.A.Q. по программируемым логическим контроллерам (PLC)
- ↳ Обсуждение F.A.Q. по PLC
- ↳ F.A.Q. по выбору PLC
- ↳ F.A.Q. по аппаратной части PLC
- ↳ F.A.Q. по языкам программирования
- ↳ F.A.Q. по структуре программ
- ↳ F.A.Q. по взаимодействию PLC с HMI
- О жизни
- ↳ Для дома, для семьи
- ↳ Комната смеха
- ↳ Электродвижение