Gas Burner Safety Control DKG 972
For 2-stage atmospheric gas burners
Flame detection:
— Ionisation probe
— Infrared-flicker detector IRD 1020.1
— UV flame sensor UVD 971
INTRODUCTION
The burner control box DKG 972 controls and supervises
atmospheric burners for gas. They are approved and certified
according to the applicable European standards and
regulations.
The microprocessor-based programming sequence ensu-
res extremely stable timings independent of voltage varia-
tions, ambient temperature and/or switch-on cycles. The
built-in information system not only provides a continuous
monitoring of the actual state of the box (very helpful es-
pecially for monitoring the start-up phase) but also informs
about the cause of a possible lock out. The lock out cause
is stored in such a way that it can be retrieved even after a
power failure.
The control box is designed for maximum safety in case of
fluctuations in the voltage supply. If the mains voltage drops
below the permitted level, operation is interrupted and the
control box automatically prevents the start sequence from
being repeated. In this way, the safety of the system is not
put at risk by a drop in the mains voltage. This low-voltage
protection works not only during start-up but also perma-
nently during operation.
CONSTRUCTIONAL FEATURES
The control box circuitry is protected by a flame resistant,
transparent plug-in type plastic housing. A central fixing
screw locks the control box to the wiring base.
The plug-in control box incorporates the microprocessor
based timer, flame check and reset circuits.
Manual reset from lock out and set to lock out is provided by
a push button with an integrated LED information system.
A variety of cable entry points provides complete flexibility
for electrical wiring.
The wiring base S98 is equipped with spare- and extraterminals
and allows together with a variety of cable entry points utmost
flexibility of electrical wiring.
The DKG 972 are compatible with the TFI 812.
Different are only the pre- and post-ignition times.
Max. heating power according the limits in the Gas Appliance
Directive.
Table of timings (sec.)
Model
waiting time start
tw
05
12
10
12
pre-ignition time
Stray light monitoring
tvz
3
3
TECHNICAL DATA
Operating voltage
or
Fuse rating
Power consumption
Max. load per output
— term. 3 ignition trafo
— term. 5 + 6 solenoid valves
— term. 7 alarm indicator
— term. 4 auxiliary blower
total load
Reset time from lock out
Re-cycling / repetition (max. 4x) after a loss-of-flame during
operation
Sensitivity
min. ionisation current required
Sensitivity for stray light
Ionisation probe insulation
Stray capacitance
max. cable length
Flame detectors
IRD 1020.1
UVD 971
Weight incl. Wiring base
Mounting position
Protection class
Approved ambient parameter
for control and flame detector
— for operation
— for storage
Build-up of ice, penetration of
water and condensing water are
Approvals according
to European standards
Classified acc. to EN 298
safety time
tf
ts
5
5
5
10
1
220 / 240 V (-15… +10%)
50 Hz (±5%)
110 / 120 V (-15… +10%)
60 Hz (±5%)
10 A fast, 6 A slow
ca. 12 VA
1.0 A, cos ϕ 0.2
0.5 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
2.0 A, cos ϕ 0.4
4.0 A, cos ϕ 0.4
max. 16 A during 0,5 sec
none
1 µA
1.5 µA
0.4 µA
probe — earth
greater than 50 MΩ
probe- earth
less then 1000 pF
< 3 m
side-on or end-on viewing
end-on viewing
190 g
any
IP 40
max. 95% at 30° C
-20° C… +60° C
-20° C… +80° C
inadmissible
EN 298 and EN 230, as
well as all other relevant
Directives and standards
ATLLXN
post-ignition time
delay 2nd-stage
tn
tv2
4
25
9
25
Gas Burner Safety Control DKG 972
For 2-stage atmospheric gas burners
Flame detection:
— Ionisation probe
— Infrared-flicker detector IRD 1020.1
— UV flame sensor UVD 971
INTRODUCTION
The burner control box DKG 972 controls and supervises
atmospheric burners for gas. They are approved and certified
according to the applicable European standards and
regulations.
The microprocessor-based programming sequence ensu-
res extremely stable timings independent of voltage varia-
tions, ambient temperature and/or switch-on cycles. The
built-in information system not only provides a continuous
monitoring of the actual state of the box (very helpful es-
pecially for monitoring the start-up phase) but also informs
about the cause of a possible lock out. The lock out cause
is stored in such a way that it can be retrieved even after a
power failure.
The control box is designed for maximum safety in case of
fluctuations in the voltage supply. If the mains voltage drops
below the permitted level, operation is interrupted and the
control box automatically prevents the start sequence from
being repeated. In this way, the safety of the system is not
put at risk by a drop in the mains voltage. This low-voltage
protection works not only during start-up but also perma-
nently during operation.
CONSTRUCTIONAL FEATURES
The control box circuitry is protected by a flame resistant,
transparent plug-in type plastic housing. A central fixing
screw locks the control box to the wiring base.
The plug-in control box incorporates the microprocessor
based timer, flame check and reset circuits.
Manual reset from lock out and set to lock out is provided by
a push button with an integrated LED information system.
A variety of cable entry points provides complete flexibility
for electrical wiring.
The wiring base S98 is equipped with spare- and extraterminals
and allows together with a variety of cable entry points utmost
flexibility of electrical wiring.
The DKG 972 are compatible with the TFI 812.
Different are only the pre- and post-ignition times.
Max. heating power according the limits in the Gas Appliance
Directive.
Table of timings (sec.)
Model
waiting time start
tw
05
12
10
12
pre-ignition time
Stray light monitoring
tvz
3
3
TECHNICAL DATA
Operating voltage
or
Fuse rating
Power consumption
Max. load per output
— term. 3 ignition trafo
— term. 5 + 6 solenoid valves
— term. 7 alarm indicator
— term. 4 auxiliary blower
total load
Reset time from lock out
Re-cycling / repetition (max. 4x) after a loss-of-flame during
operation
Sensitivity
min. ionisation current required
Sensitivity for stray light
Ionisation probe insulation
Stray capacitance
max. cable length
Flame detectors
IRD 1020.1
UVD 971
Weight incl. Wiring base
Mounting position
Protection class
Approved ambient parameter
for control and flame detector
— for operation
— for storage
Build-up of ice, penetration of
water and condensing water are
Approvals according
to European standards
Classified acc. to EN 298
safety time
tf
ts
5
5
5
10
1
220 / 240 V (-15… +10%)
50 Hz (±5%)
110 / 120 V (-15… +10%)
60 Hz (±5%)
10 A fast, 6 A slow
ca. 12 VA
1.0 A, cos ϕ 0.2
0.5 A, cos ϕ 0.4
0.5 A, cos ϕ 0.4
2.0 A, cos ϕ 0.4
4.0 A, cos ϕ 0.4
max. 16 A during 0,5 sec
none
1 µA
1.5 µA
0.4 µA
probe — earth
greater than 50 MΩ
probe- earth
less then 1000 pF
< 3 m
side-on or end-on viewing
end-on viewing
190 g
any
IP 40
max. 95% at 30° C
-20° C… +60° C
-20° C… +80° C
inadmissible
EN 298 and EN 230, as
well as all other relevant
Directives and standards
ATLLXN
post-ignition time
delay 2nd-stage
tn
tv2
4
25
9
25
Страница 1 из 3
-
- Регистрация:
- 28.11.13
- Сообщения:
-
24
- Благодарности:
- 0
Grixak
Участник
- Регистрация:
- 28.11.13
- Сообщения:
- 24
- Благодарности:
- 0
- Адрес:
- Москва
Ошибка и отключение котла Buderus LoganoДобрый вечер!
Переодически котел Buderus Logano G334 с автоматикой Logomax 4211 останавливается и не запускается.
Нажимаю кнопки на устройствах Honeywell DKG 972-N и котел запускается, работает от нескольких дней до недели и опять останавливается.
Такая ситуация происходит с начала момента эксплуатации котла (3 года).
Что делать, велика опасность разморозить систему отопления.
Спасибо. -
- Регистрация:
- 10.04.12
- Сообщения:
-
22.974
- Благодарности:
- 18.015
Mijjgan
Супер-Модератор
- Регистрация:
- 10.04.12
- Сообщения:
- 22.974
- Благодарности:
- 18.015
- Адрес:
- Россия, Москва
А проверьте фазировку на всякий случай. Уж больно симптомы похожи.
-
- Регистрация:
- 06.09.16
- Сообщения:
-
2.023
- Благодарности:
- 1.045
Dmitribir
Живу здесь
- Регистрация:
- 06.09.16
- Сообщения:
- 2.023
- Благодарности:
- 1.045
- Адрес:
- Москва и МО Север, Тверская область, Зубцов.
Так когда на топочнике кнопку нажимаете она красненьким светится или нет?
-
- Регистрация:
- 29.11.13
- Сообщения:
-
120
- Благодарности:
- 33
Andross
Живу здесь
- Регистрация:
- 29.11.13
- Сообщения:
- 120
- Благодарности:
- 33
- Адрес:
- Воскресенск
А не замечали, когда чаще останавливается? Ночью или днём? При похолодании или потеплении? Какая ситуация с газом? Какая схема газоснабжения? С ДРП? Реле мин. давления газа стоит? Что с электропитанием? Когда ТО делали?
-
- Регистрация:
- 28.11.13
- Сообщения:
-
24
- Благодарности:
- 0
Grixak
Участник
- Регистрация:
- 28.11.13
- Сообщения:
- 24
- Благодарности:
- 0
- Адрес:
- Москва
Добрый день!
Фразировка правильная. Давление в трубе газа низкое без понижающего шкафа и т. д. 12 мба. Дом последний на газовой трубе. Ситуация происходит в разные времена суток.
Подозреванию временное падение газа в трубе. Реле минимального давления было установленно на 13, установили на 8. Последний раз оикючение произошло в вск с 15 до 20. Причем раньше откючалась одна горелка и котел все же как-то топил, тоиитеперь отключаются обе и сразу.
ТО не делали, я сам его пылесосил в июне. Проблеммы в работе котла происходят постоянно с момента его установки. -
- Регистрация:
- 29.01.18
- Сообщения:
-
413
- Благодарности:
- 70
vkramor
Живу здесь
- Регистрация:
- 29.01.18
- Сообщения:
- 413
- Благодарности:
- 70
- Адрес:
- Tyumen region Ishim
12 mB не маловато? хотя для этого котла и 10 должно хватать но это в режиме работы котла а не в статике.
-
- Регистрация:
- 07.11.14
- Сообщения:
-
843
- Благодарности:
- 383
игорь-химик
Живу здесь
- Регистрация:
- 07.11.14
- Сообщения:
- 843
- Благодарности:
- 383
- Адрес:
- Московская область поселок Гжель
Я бы этим нехорошим людям из Мособлгаза попробовал бы мозг повыносить, чтобы замерили давление на входе газа когда котел в работе (горелка горит). Блин сволочи, знали какой мощности будет установлен котёл и всё равно выдали ТУ на газификацию, так пусть хоть давление поднимут на ГРП до 300 мм. вод. ст. ГРПшникам это не составит большого труда.
-
- Регистрация:
- 10.04.12
- Сообщения:
-
22.974
- Благодарности:
- 18.015
Mijjgan
Супер-Модератор
- Регистрация:
- 10.04.12
- Сообщения:
- 22.974
- Благодарности:
- 18.015
- Адрес:
- Россия, Москва
Откуда уверенность, что знали? Разве топикстартер что-то говорил о «происхождении» котла? А тот факт, что с момента установки прошло несколько лет и котёл всё это время вываливается в аварию намекает на то, что ни ПНР официально не проводились (минимум — год гарантии), ни договора на ТО нету. Иначе те или другие, забодавшись ездить, уже нашли бы корень зла.
-
- Регистрация:
- 28.11.13
- Сообщения:
-
24
- Благодарности:
- 0
Grixak
Участник
- Регистрация:
- 28.11.13
- Сообщения:
- 24
- Благодарности:
- 0
- Адрес:
- Москва
Волнует больше вопрос автоматического перезапуска котла, может кто сталкивался?
-
- Регистрация:
- 16.01.13
- Сообщения:
-
4.897
- Благодарности:
- 3.165
Buderus71
Живу здесь
- Регистрация:
- 16.01.13
- Сообщения:
- 4.897
- Благодарности:
- 3.165
- Адрес:
- Тула
@Grixak, Реле давления стоит, значит при нормализации давления газа котёл сам перезапустится. Не было бы — или горелка бы прогорела, или уходил в ошибку и тогда только ручной перезапуск
-
- Регистрация:
- 29.06.13
- Сообщения:
-
39.866
- Благодарности:
- 17.057
Roaroma
чем могу
- Регистрация:
- 29.06.13
- Сообщения:
- 39.866
- Благодарности:
- 17.057
- Адрес:
- Калуга
@Buderus71, Вы хотите сказать — котел самостоятельно сбрасывает ошибки ?
-
- Регистрация:
- 16.01.13
- Сообщения:
-
4.897
- Благодарности:
- 3.165
Buderus71
Живу здесь
- Регистрация:
- 16.01.13
- Сообщения:
- 4.897
- Благодарности:
- 3.165
- Адрес:
- Тула
@Roaroma, я хочу сказать что при наличии реле давления газа он в ошибку не уходит.
-
- Регистрация:
- 02.09.15
- Сообщения:
-
3.840
- Благодарности:
- 1.519
senns
Живу здесь
- Регистрация:
- 02.09.15
- Сообщения:
- 3.840
- Благодарности:
- 1.519
- Адрес:
- Екатеринбург
Судя по ответу автора, там сплошной колхоз делается, т. е. не квалифицированная диагностика.
К тому же, грит, что одна горелка иногда работает, а это как раз нехватка давления и не факт, что хозяин выставил правильно реле давления газа.
Пусть ищет спецов -
- Регистрация:
- 29.06.13
- Сообщения:
-
39.866
- Благодарности:
- 17.057
Roaroma
чем могу
- Регистрация:
- 29.06.13
- Сообщения:
- 39.866
- Благодарности:
- 17.057
- Адрес:
- Калуга
вот это странно, можете подробнее «разжевать» ?
если нет газа или давление слабое — котел не разжигает горелку но и не показывает ошибку — я правильно понял ?
ждет появления необходимого давления и сам запускается при его появлении ? -
- Регистрация:
- 02.09.15
- Сообщения:
-
3.840
- Благодарности:
- 1.519
senns
Живу здесь
- Регистрация:
- 02.09.15
- Сообщения:
- 3.840
- Благодарности:
- 1.519
- Адрес:
- Екатеринбург
Реле давления газа отключает напряжение питания котла раньше, чем понизиться давление газа на входе до критического, тем самым котёл «не успевает отобразить» ощибку по газу