fff
Flashing
● Meaning
● Action
● Operation at
Error
—
Flashing
● Meaning
● Action
● Operation at
Error
e11
● Meaning
● Action
● Operation at
Error
Input Sensor Error (High Temperature)
(1) The process value is higher than the overflow temperature or a
sensor error has occurred when using a thermocouple input or
platinum resistance thermometer input model.
(2) The process value is higher than the control temperature range or
a
sensor
error
(thermocouple/platinum resistance thermometer) model.
Check the wiring of inputs for miswiring, disconnections, and
short-circuits and check the input type.
If no abnormality is found in the wiring and input type, turn the power
OFF then back ON again.
The error is displayed after it occurs, and the alarm output (models with
alarm function only) indicates that the upper-limit value has been
exceeded. The control outputs turn OFF.
* Input sensor error detection is not provided in thermistor models.
Input Sensor Error (Low Temperature)
(1) The process value is lower than the underflow temperature or a
sensor error has occurred when using a thermocouple input or
platinum resistance thermometer input model.
(2) The positive and negative connection of the Sensor is reversed
when using thermocouple input.
(3) The process value is lower than the control temperature range or a
sensor
error
has
(thermocouple/platinum resistance thermometer) model.
Check the wiring of inputs for miswiring, disconnections, and
short-circuits and check the input type.
If no abnormality is found in the wiring and input type, turn the power
OFF then back ON again.
The error is displayed after it occurs, and the alarm output (models with
alarm function only) indicates that the lower-limit value has been
exceeded. The control outputs turn OFF.
* Input sensor error detection is not provided in thermistor models.
Memory Error
An error has occurred in the internal memory.
Turn the power ON again. If the display remains the same, the
Controller must be repaired. If the display is restored, then the probable
cause is electrical noise affecting the control system. Check for
electrical noise.
The control outputs and alarm outputs turn OFF.
has
occurred
when
occurred
when
using
Error Displays
using
a
multi-input
a
multi-input
A-5
- Manuals
- Brands
- Omron Manuals
- Temperature Controller
- E5CSV —
- Manual
-
Contents
-
Table of Contents
-
Bookmarks
Quick Links
E5CSV temperature controller
R e a d y, s e t , g o !
P e r f e c t c o n t r o l
»
E a sy s e t t i n g u p
»
E n h a n c e d f u n c t i o n a l i t y
»
Advanced Industrial Automation
Related Manuals for Omron E5CSV
Summary of Contents for Omron E5CSV
-
Page 1
P e r f e c t c o n t r o l » E a sy s e t t i n g u p » E n h a n c e d f u n c t i o n a l i t y » Advanced Industrial Automation… -
Page 2
ON/OFF or PID control with Self-Tuning. established itself throughout the world as the ideal What’s more, it still provides an indication of output and alarm status and direction of deviation from set point. choice for simple, cost-effective temperature control. -
Page 3
E5CSV series offers much more. Like an Auto-Tune function • Easy setting-up using DIP and rotary switches and the fact that as standard you can now select multiple input • Meets broad range of basic temperature-control types (thermocouple/RTD). A new 3.5 digit display also means… -
Page 4: Model Number Structure
Functions in DIN 48 x 48 mm-size Temperature Controllers • Easy setting using DIP and rotary switches. • Multi-input (thermocouple/platinum resistance thermometer). • Clearly visible digital display with character height of 13.5 mm. • RoHS compliant. Model Number Structure ■ Model Number Legend…
-
Page 5: Specifications
Thermocouple (See note 1.): (±0.5% of indication value or ±1° C, whichever is greater) ±1 digit max. Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1° C, whichever is greater) ±1 digit max. Indication accuracy (ambient temperature of 23° C)
-
Page 6: Installation
3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CSV. 4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
-
Page 7: Operation
Remove the E5CSV from the case to make the settings. rubber is in place and push the E5CSV toward the rear case until 1. Insert the tool into the two tool insertion holes (one on the top and it snaps into position. While pushing the E5CSV into place, push one on the bottom) and release the hooks.
-
Page 8
-99 will be displayed as “[[[“ and values above 1,999 will be displayed as “]]].” Press for 2. If unit is changed to 1 degree when the SP and alarm value for at least 2 s. AT execution in progress the temperature range are displayed in 0.1-units from 0.0 to… -
Page 9: Operation Settings
Alarm output Note: Turn OFF the power before changing the DIP switch settings on the E5CSV. Each of the switch settings will be enabled after the power is turned ON. For details on the position of the temperature range switch, control mode switches, and alarm mode switch, refer to page 4.
-
Page 10
4. Using the Control Mode Switches (1) Using ON/OFF Control and PID Control (1.1) ON/OFF Control The control mode is set to ON/OFF control as the default setting. To perform cooling control of freezers, etc., turn ON switch 3. Switch 1 OFF: ON/OFF control… -
Page 11: Protect Switch
0 to 1999 0 to 400 Note: The control range for multi-input (thermocouple/platinum resistance thermometer) models is -40 to +40° F of each temperature range. The previous name J-DIN has been changed to L in accordance with revisions to DIN standards.
-
Page 12
OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.omron-industrial.com Austria France Netherlands Spain Tel: +43 (0) 1 80 19 00 Tel: +33 (0) 1 56 63 70 00…
- Manuals
- Brands
- Omron Manuals
- Temperature Controller
- E5CSV —
- Manual
-
Contents
-
Table of Contents
-
Bookmarks
Quick Links
E5CSV temperature controller
R e a d y, s e t , g o !
P e r f e c t c o n t r o l
»
E a sy s e t t i n g u p
»
E n h a n c e d f u n c t i o n a l i t y
»
Advanced Industrial Automation
Related Manuals for Omron E5CSV
Summary of Contents for Omron E5CSV
-
Page 1
P e r f e c t c o n t r o l » E a sy s e t t i n g u p » E n h a n c e d f u n c t i o n a l i t y » Advanced Industrial Automation… -
Page 2
ON/OFF or PID control with Self-Tuning. established itself throughout the world as the ideal What’s more, it still provides an indication of output and alarm status and direction of deviation from set point. choice for simple, cost-effective temperature control. -
Page 3
E5CSV series offers much more. Like an Auto-Tune function • Easy setting-up using DIP and rotary switches and the fact that as standard you can now select multiple input • Meets broad range of basic temperature-control types (thermocouple/RTD). A new 3.5 digit display also means… -
Page 4: Model Number Structure
Functions in DIN 48 x 48 mm-size Temperature Controllers • Easy setting using DIP and rotary switches. • Multi-input (thermocouple/platinum resistance thermometer). • Clearly visible digital display with character height of 13.5 mm. • RoHS compliant. Model Number Structure ■ Model Number Legend…
-
Page 5: Specifications
Thermocouple (See note 1.): (±0.5% of indication value or ±1° C, whichever is greater) ±1 digit max. Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1° C, whichever is greater) ±1 digit max. Indication accuracy (ambient temperature of 23° C)
-
Page 6: Installation
3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CSV. 4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
-
Page 7: Operation
Remove the E5CSV from the case to make the settings. rubber is in place and push the E5CSV toward the rear case until 1. Insert the tool into the two tool insertion holes (one on the top and it snaps into position. While pushing the E5CSV into place, push one on the bottom) and release the hooks.
-
Page 8
-99 will be displayed as “[[[“ and values above 1,999 will be displayed as “]]].” Press for 2. If unit is changed to 1 degree when the SP and alarm value for at least 2 s. AT execution in progress the temperature range are displayed in 0.1-units from 0.0 to… -
Page 9: Operation Settings
Alarm output Note: Turn OFF the power before changing the DIP switch settings on the E5CSV. Each of the switch settings will be enabled after the power is turned ON. For details on the position of the temperature range switch, control mode switches, and alarm mode switch, refer to page 4.
-