The following list gives a complete description of each alarm
code and its possible cause.
ALARM CODE DESCRIPTIONS
Code
Alarm name
1
Evaporator leaving water thermistor fault
2
Evaporator entering water thermistor fault
3
Condenser leaving water thermistor fault
4
Condenser entering water thermistor fault
5
Heat reclaim entering water thermistor fault
6
Heat reclaim leaving water thermistor fault
7
Outdoor temperature sensor fault
8
CHWS (master/slave) fluid thermistor fault
9
Suction thermistor fault, compressor A1
10
Suction thermistor fault, compressor B1
11
External 0-10 V dc signal fault
12
Discharge pressure sensor fault, circuit A
13
Discharge pressure sensor fault, circuit B
14
Suction pressure sensor fault, circuit A
15
Suction pressure sensor fault, circuit B
16
Oil pressure sensor fault, compressor A1
17
Oil pressure sensor fault, compressor B1
18
Oil pressure sensor fault, compressor A2
19
Oil pressure sensor fault, compressor B2
20
Oil pressure sensor fault, compressor A3
21
Oil pressure sensor fault, compressor B3
22
Oil pressure sensor fault, compressor A4
23
Oil pressure sensor fault, compressor B4
24
Pumpdown pressure sensor fault, circuit A
25
Pumpdown pressure sensor fault, circuit B
26
Loss of communication with compressor board A1
27
Loss of communication with compressor board A2
28
Loss of communication with compressor board A3
29
Loss of communication with compressor board A4
30
Loss of communication with compressor board B1
31
Loss of communication with compressor board B2
32
Loss of communication with compressor board B3
33
Loss of communication with compressor board B4
34
Loss of communication with EXV board
35
Loss of communication with NRCP board
36
Loss of communication with fan board 1
37
Loss of communication with fan board 2
38
Loss of communication with 4xAI — 2xAO board 1
39
Loss of communication with 4xAI — 2xAO board 2
40
Pumpdown fault, circuit A
41
Pumpdown fault, circuit B
42
Evaporator frost protection
43
Low evaporator water flow rate.
44
Low suction temperature, circuit A
45
Low suction temperature, circuit B
46
High suction overheat, circuit A
47
High suction overheat, circuit B
48
Low suction overheat, circuit A
Description
Action
Thermistor outside range
Unit shut down
Ditto
Unit shut down
Ditto
Heating mode: Unit shut down,
if control on leaving water.
Cooling mode: no action
Ditto
Heating mode: Unit shut down,
if control on entering water.
Cooling mode: no action
Ditto
Unit with heat recalaim option:
heat reclaim mode shut down,
unit changes over to standard
cooling mode. If not: no action
Ditto
None
Ditto
Reset: normal setpoint used.
Limitation or reset deactivated.
Ditto
Deactivated
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Reset signal outside range
Reset: normal setpoint used
Limitation or reset deactivated
Voltage transmitted by incorrect sensor Circuit A shut down
Ditto
Circuit B shut down
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Ditto
Compressor A2 shut down
Ditto
Compressor B2 shut down
Ditto
Compressor A3 shut down
Ditto
Compressor B3 shut down
Ditto
Compressor A4 shut down
Ditto
Compressor B4 shut down
Ditto
If circuit is in heat reclaim
mode, it goes to cooling mode.
If not, no action
Ditto
Ditto
Communication with the compressor
Circuit A shut down
board is lost
Ditto
Compressor A2 shut down
Ditto
Compressor A3 shut down
Ditto
Compressor A4 shut down
Ditto
Circuit B shut down
Ditto
Compressor B2 shut down
Ditto
Compressor B3 shut down
Ditto
Compressor B4 shut down
Ditto
Unit shut down
The board does not respond
Unit shut down, if heat reclaim mode No
is selected
Ditto
Unit shut down, if the number of
fan stages per circuit is less than 3.
If not, circuit A shut down
Ditto
Circuit B shut down
Ditto
Unit shut down or no action
Ditto
Compressors or circuit shut down
End of pumpdown conditions not
Circuit A shut down
satisfied
Ditto
Circuit B shut down
Unit operating: units shut down if
Unit shut down
temp. < defrost threshold.
Unit shut down: if temp < threshold
and evaporator heater on for more
than 10 mins.
Unit shut down
Circuit operating: saturated suction
Circuit A shut down
temp. < defrost threshold and < leaving
water -16°C for more than 10 mins.
Ditto
Circuit B shut down
EXV fully open
Circuit A shut down
Ditto
Circuit B shut down
EXV in min. position, and circuit
Circuit A shut down
superheat below superheat setpoint
-5.5 K, saturated suction temp. above
MOP for 5 mins.
Pumpdown
Reset type
Probable cause
Yes
Auto
Thermistor or wiring fault or
bad connection
Yes
Auto
Ditto
Yes
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto, if temp. mea-
Thermistor faulty
sured by sensor
returns to normal
—
Ditto
Themistor faulty
Yes
Auto
Ditto
Yes
Auto
Ditto
No
Auto
Signal incorrect, wiring error
Yes
Auto
Sensor fault or wiring error
Yes
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto, if press. mea-
sured by sensor
returns to normal
—
Ditto
Ditto
No
Auto
Wiring fault, faulty module,
incorrect module address
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
No
Auto
Wiring bus faulty, incorrect
address or board faulty
Auto, if board is
NRCP board faulty
again detected
No
Auto
Wiring bus faulty, incorrect
address or board faulty
No
Auto
Ditto
No
Auto
Ditto, depending on
configuration
No
Auto
Ditto, depending on
configuration
No
Manual
EXV or sensor faulty
No
Manual
Ditto
No
Auto first time,
Low water flow or
then manual
thermistor defective
No
Manual
Water pump faulty
No
Manual
Low charge, filter dirty
ot thermistor faulty
No
Manual
Ditto
Yes
Manual
Ditto
Yes
Manual
Ditto
Yes
Manual
EXV or thermistor or
transducer defective
33
- Manuals
- Brands
- Carrier Manuals
- Chiller
- PRO-DIALOG PLUS 30RW
- Manual
-
Contents
-
Table of Contents
-
Troubleshooting
-
Bookmarks
Quick Links
30RW — 30RWA
PRO-DIALOG
Control
AQUASNAP
Operation and maintenance instructions
Related Manuals for Carrier PRO-DIALOG PLUS 30RW
Summary of Contents for Carrier PRO-DIALOG PLUS 30RW
-
Page 1
30RW — 30RWA PRO-DIALOG Control AQUASNAP Operation and maintenance instructions… -
Page 2
The cover graphics are solely for illustration and forms no part of any offer for sale or any sale contract. The manufacturer reserves the right to change the design at any time without notice. -
Page 3: Table Of Contents
TABLE OF CONTENTS 1 — SAFETY CONSIDERATIONS …………………………4 1.1 — General ………………………………4 1.2 — Avoid electrocution …………………………..4 2 — GENERAL DESCRIPTION …………………………4 2.1 — General ………………………………4 2.2 — Abbreviations used …………………………..4 3 — HARDWARE DESCRIPTION …………………………5 3.1 — General ………………………………
-
Page 4: Safety Considerations
• CCN mode: the machine is controlled by commands from carefully and set them down gently. the Carrier Comfort Network (CCN). In this case, a data communication cable is used to connect the unit to the 1.2 — Avoid electrocution CCN communication bus.
-
Page 5: Hardware Description
3 — HARDWARE DESCRIPTION 3.2 — Electrical supply to boards 3.1 — General All boards are supplied from a common 24 V a.c. supply referred to earth. Figure 1 — Control board CAUTION: Maintain the correct polarity when connecting the power supply to the boards, otherwise the boards may be damaged.
-
Page 6: The Controls
3.5 — The controls 3.6 — Connections at the user’s terminal block Evaporator pump 3.6.1 — General description The controller can regulate one or two evaporator pumps and The contacts below are available at the user’s terminal block on takes care of the automatic change-over between pumps. the NRCP-BASE board (see figure 1).
-
Page 7
DUAL-CIRCUIT UNITS Description Connector/channel Terminal Board Remarks Remarks Alarm relay output J3 / CH24 30A — 31A Master NRCP- Indicates alarms, circuit A Volt-free contact 24 V a.c. circuit A BASE 48 V d.c. max, 20 V a.c. or min. 20 V d.c., 3 A max, 80 Alarm relay output J3 / CH24 30B — 31B… -
Page 8: Setting Up Pro-Dialog Plus Control
4 — SETTING UP PRO-DIALOG PLUS CONTROL 4.1 — Local interface general features MAIN INTERFACE SUMMARY INTERFACE MAIN INTERFACE SUMMARY INTERFACE MENU BLOCK DUAL-CIRCUIT 30RWA INTERFACE MENU BLOCK DUAL-CIRCUIT 30RW INTERFACE The local interface enables a number of operating parameters to Main interface be displayed and modified.
-
Page 9: Unit Start/Stop Control
The summary interface (right hand section) includes a mimic The following operating types can be selected using the diagram of the unit, together with push-buttons and LEDs. It Start/Stop button: gives quick access to the main operating parameters of the unit. OPERATING TYPES 4 DIGIT DISPLAY DESCRIPTION…
-
Page 10: Menus
4.3 — Menus 4.3.3 — Modifying the value of a parameter/access to a sub- menu 4.3.1 — Selecting a menu Press the Enter button for more than 2 seconds to enter the The MENU button authorises you to select a menu from the 10 modification mode or to select a sub-menu.
-
Page 11
MODIFYING THE VALUE OF A PARAMETER OPERATION PRESS BUTTON MENU LED ITEM NUMBER ITEM VALUE 2-DIGIT DISPLAY 4-DIGIT DISPLAY Hold on the MENU button until the LED for SETPOINT lights. Press one of the Arrow buttons until the two-digit display shows 1 (item number 1- cooling setpoint 2). -
Page 12
MAIN MENUS STATUS TEMPERATURES PRESSURES SETPOINTS INPUTS OUTPUTS CONFIGURATION ALARMS ALARMS HISTORY ALARMS SUB-MENUS SERVICE FACTORY RUNTIME 1 RUNTIME 2 MAINTENANCE USER [SErviCE] [FACtorY] [RuntiME 1] [RuntiME 2] [MAintEnAnCE] [USEr] SUB-SUB-MENUS USER 1 USER 2 SCHEDULE 1 SCHEDULE 2 HOLIDAYS HOUR + DATE BROADCAST SERVICE 1… -
Page 13
SETPOINTS OUTPUTS ITEM STATUS TEMP PRESSURES INPUTS CONFIG ALARMS ALARMS HIST RUNTIMES Default display Evaporator water Discharge pressure Cooling setpoint 1 Contact 1: on/off Compressor status SUB-MENU: User Number of active Historic alarm code SUB-MENU: entering temp. circuit A circuit A Configuration (USEr) alarms/resets** Runtimes 1… -
Page 14
4.3.5 — Description of the Information menu INFORMATION MENU (3) ITEM FORMAT UNITS DESCRIPTION Automatic display mode. It cycles through the following displays: ±nn.n °C Controlled water temperature: temperature of the water that the unit tries to maintain at the control point. Unit operating type LOFF Local Off… -
Page 15
INFORMATION MENU (3) continued ITEM FORMAT UNITS DESCRIPTION ±nn.n °C Active setpoint. This is the current cooling/heating setpoint: it refers to cooling setpoint 1 or cooling/heating setpoint 2. See section 5.6.1. ±nn.n Control point. This is the setpoint used by the controller to adjust the temperature of the leaving or entering water (according to Forc °C configuration). -
Page 16
4.3.6 — Description of the Temperatures menu 4.3.7 — Description of the Pressures menu TEMPERATURES MENU [2] PRESSURES MENU [2] ITEM FORMAT UNITS COMMENTS ITEM FORMAT UNITS COMMENTS ±nn.n °C Evaporator entering water temperature nnnn Discharge pressure, circuit A. Relative pressure. ±nn.n °C Evaporator leaving water temperature… -
Page 17
LEAVING WATER TEMPERATURE CONTROL RESET THRESHOLDS IN COOLING OR HEATING MODE SETPOINT — °C R-407C Reset threshold Zero Full Minimum cooling value Reset based on outdoor -10 to 51 °C -10 to 51 °C Water air temperature Medium brine Reset based on 0 to 11.1 °C 0 to 11.1 °C Brine… -
Page 18
4.3.10 — Description of the Outputs/Tests menu 4.3.10.1 — General This menu displays the status of the controller outputs. More- over, when the machine is fully stopped (LOFF) the outputs can be activated for manual tests (the access to the tests is password controlled). -
Page 19
4.3.10.3 — Tests CONFIGURATION This function allows the user to test the outputs individually, if the machine is completely shut down (LOFF). To carry out a USER [USEr] manual test use the arrow keys to access the output to be tested and press the Enter key (longer than 2 seconds) to activate the USER1 USER2… -
Page 20
SUB-MENU USER CONFIGURATION ITEM USER 1 USER 2 DATE SCHEDULE 1 SCHEDULE 2 HOLIDAYS BROADCAST [USER1] [USER2]* [dAtE]* [ScHEduLE 1MEnu]* [ScHEduLE 2 MEnu]* [HOLidAy MEnu]* [BrodCASt]* Return to previous menu Return to previous Return to previous Return to previous menu Return to previous Return to previous menu Return to previous menu… -
Page 21
4.3.11.3 — Description of the User 1 Configuration sub-menu USER 1 CONFIGURATION SUB-MENU [2] ITEM FORMAT UNITS DEFAULT COMMENTS USEr MEnu When selected this item authorises return to the previous menu. 1 [1] 0/1/2 Circuit sequence selection (two-circuit units). 0 = Balanced circuit loading 1 = Circuit A first 2 = Circuit B first 2 [1]… -
Page 22
4.3.11.4 — Description of the User 2 Configuration sub-menu This menu is only accessible if the unit is equipped with an optional CCN/clock board USER 1 CONFIGURATION SUB-MENU ITEM FORMAT UNITS DEFAULT COMMENTS USEr 2 Menu When selected this item authorises return to the previous menu. 1[1] YES/no Periodic pump quick-start of the water pump(s) -
Page 23
Program is in unoccupied mode unless a schedule time period 4.3.11.7 — Description of the Holidays sub-menus is in effect. If two periods overlap and are both active on the This function is used to define 16 public holiday periods. Each same day, the occupied mode takes priority over the period is defined with the aid of three parameters: the month, unoccupied period. -
Page 24
HOLIDAY PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 16) 4.3.11.8 — Description of the Broadcast sub-menu ITEM # FORMAT COMMENTS The controller provides a broadcast configuration menu which HoLidAy X Sub-menu When selected this item authorises a return you can use to configure the unit to be the CCN’s broadcaster, to the configuration menu. -
Page 25
4.3.12 — Description of the Alarms menu 4.3.14.1 — Description of the Runtimes 1 menu This menu is used to display and reset up to 5 active alarms. It also permits alarm reset. If no alarm is active this menu is not RUNTIMES MENU [2] accessible. -
Page 26: Pro-Dialog Plus Control Operation
5 — PRO-DIALOG PLUS CONTROL OPERATION 4.3.14.3 — Maintenance menu description To be active, the maintenance function must be preset in the 5.1 — Start/stop control Service configuration ITEM # FORMAT DESCRIPTION The table below summarises the unit control type and stop or MAintEnAnCE MEnu When selected this item authorises return to go status with regard to the following parameters.
-
Page 27
ACTIVE OPERATING TYPE PARAMETER STATUS CONTROL UNIT TYPE STATUS REMOTE MASTER UNIT START/STOP CCN GENERAL START/STOP CONTROL SCHEDULE EMERGENCY ALARM LOFF L-C L-SC MASt CHIL_S_S CONTACT TYPE MODE SHUTDOWN Enable Active — Local Active — Unoccupied Local Active — Remote Active — Unoccupied Remote… -
Page 28: Heating/Cooling Operation
5.2 — Heating/cooling operation 5.4 — Condenser water pump control 5.2.1 — General The unit can control one or two condenser water pumps. These The heating/cooling selection applies to 30RW (liquid chillers) pumps can be fixed-speed or variable-speed pumps. Depending units, controlling a boiler or equipped with a heat pump option.
-
Page 29
The following table summarises the possible selections REMOTE OPERATING MODE — DUAL-CIRCUIT UNITS depending on the control types (local, remote or CCN) and the PARAMETER STATUS following parameters: HEATING/COOLING CONTROL SCHEDULE 2 ACTIVE SETPOINT OPERATING MODE CONTACTS STATUS Setpoint select in local control: item #13 of the Infor- Cooling sp 1 Cooling setpoint 1… -
Page 30: Demand Limit
5.6.2 — Reset 5.8 — Night mode Reset means that the active setpoint is modified so that less machine capacity is required (in cooling mode, the setpoint is The night period is defined (see User configuration) by a start increased, in heating mode it is decreased). This modifica-tion is time and an end time that are the same for each day of the in general a reaction to a drop in the load.
-
Page 31: Control Of A Boiler
5.10.2 — 30RWA units One of the functions of the master unit (depending on its configuration) may be the designation, whether the master or The control offers two control modes (fan stages with or slave is to be the lead machine or the follower. The roles of without Varifan) lead machine and follower will be reversed when the differ- Automatic mode.
-
Page 32: Diagnostics — Troubleshooting
6 — DIAGNOSTICS — TROUBLESHOOTING A manual reset must be run from the main interface using the following procedure: 6.1 — General RESET OF ACTIVE ALARMS OPERATION ITEM NUMBER ITEM VALUE PRESS MENU The PRO-DIALOG Plus control system has many fault tracing 2-DIGIT DISPLAY 4-DIGIT DISPLAY BUTTON LED aid functions.
-
Page 33: Alarm Codes
6.4 — Alarm codes The following list gives a complete description of each alarm code and its possible cause. ALARM CODE DESCRIPTIONS ALARM NAME ALARM DESCRIPTION ACTION TAKEN BY RESET TYPE PROBABLE CAUSE ALARM THE CONTROL CODE Compressor A1 failure Motor safety input has opened due to Compressor is shut Manual…
-
Page 34
ALARM CODE DESCRIPTIONS (continued) ALARM NAME ALARM DESCRIPTION ACTION TAKEN BY RESET TYPE PROBABLE CAUSE ALARM THE CONTROL CODE Safety interlock open Safety interlock not closed before end of the Unit prevented to start or Manual Evaporator pump control or water flow start-up delay or opens during operation shut down switch failure… -
Page 36
Order No. R3432-76, 06.2004. Supersedes order No.: 13432-76, 03.2002 Manufactured by: Carrier s.a., Montluel, France. Manufacturer reserves the right to change any product specification without notice. Printed in the Netherlands on chlorine-free paper.
- Manuals
- Brands
- Carrier Manuals
- Chiller
- PRO-DIALOG PLUS 30RW
- Manual
-
Contents
-
Table of Contents
-
Troubleshooting
-
Bookmarks
Quick Links
30RW — 30RWA
PRO-DIALOG
Control
AQUASNAP
Operation and maintenance instructions
Related Manuals for Carrier PRO-DIALOG PLUS 30RW
Summary of Contents for Carrier PRO-DIALOG PLUS 30RW
-
Page 1
30RW — 30RWA PRO-DIALOG Control AQUASNAP Operation and maintenance instructions… -
Page 2
The cover graphics are solely for illustration and forms no part of any offer for sale or any sale contract. The manufacturer reserves the right to change the design at any time without notice. -
Page 3: Table Of Contents
TABLE OF CONTENTS 1 — SAFETY CONSIDERATIONS …………………………4 1.1 — General ………………………………4 1.2 — Avoid electrocution …………………………..4 2 — GENERAL DESCRIPTION …………………………4 2.1 — General ………………………………4 2.2 — Abbreviations used …………………………..4 3 — HARDWARE DESCRIPTION …………………………5 3.1 — General ………………………………
-
Page 4: Safety Considerations
• CCN mode: the machine is controlled by commands from carefully and set them down gently. the Carrier Comfort Network (CCN). In this case, a data communication cable is used to connect the unit to the 1.2 — Avoid electrocution CCN communication bus.
-
Page 5: Hardware Description
3 — HARDWARE DESCRIPTION 3.2 — Electrical supply to boards 3.1 — General All boards are supplied from a common 24 V a.c. supply referred to earth. Figure 1 — Control board CAUTION: Maintain the correct polarity when connecting the power supply to the boards, otherwise the boards may be damaged.
-
Page 6: The Controls
3.5 — The controls 3.6 — Connections at the user’s terminal block Evaporator pump 3.6.1 — General description The controller can regulate one or two evaporator pumps and The contacts below are available at the user’s terminal block on takes care of the automatic change-over between pumps. the NRCP-BASE board (see figure 1).
-
Page 7
DUAL-CIRCUIT UNITS Description Connector/channel Terminal Board Remarks Remarks Alarm relay output J3 / CH24 30A — 31A Master NRCP- Indicates alarms, circuit A Volt-free contact 24 V a.c. circuit A BASE 48 V d.c. max, 20 V a.c. or min. 20 V d.c., 3 A max, 80 Alarm relay output J3 / CH24 30B — 31B… -
Page 8: Setting Up Pro-Dialog Plus Control
4 — SETTING UP PRO-DIALOG PLUS CONTROL 4.1 — Local interface general features MAIN INTERFACE SUMMARY INTERFACE MAIN INTERFACE SUMMARY INTERFACE MENU BLOCK DUAL-CIRCUIT 30RWA INTERFACE MENU BLOCK DUAL-CIRCUIT 30RW INTERFACE The local interface enables a number of operating parameters to Main interface be displayed and modified.
-
Page 9: Unit Start/Stop Control
The summary interface (right hand section) includes a mimic The following operating types can be selected using the diagram of the unit, together with push-buttons and LEDs. It Start/Stop button: gives quick access to the main operating parameters of the unit. OPERATING TYPES 4 DIGIT DISPLAY DESCRIPTION…
-
Page 10: Menus
4.3 — Menus 4.3.3 — Modifying the value of a parameter/access to a sub- menu 4.3.1 — Selecting a menu Press the Enter button for more than 2 seconds to enter the The MENU button authorises you to select a menu from the 10 modification mode or to select a sub-menu.
-
Page 11
MODIFYING THE VALUE OF A PARAMETER OPERATION PRESS BUTTON MENU LED ITEM NUMBER ITEM VALUE 2-DIGIT DISPLAY 4-DIGIT DISPLAY Hold on the MENU button until the LED for SETPOINT lights. Press one of the Arrow buttons until the two-digit display shows 1 (item number 1- cooling setpoint 2). -
Page 12
MAIN MENUS STATUS TEMPERATURES PRESSURES SETPOINTS INPUTS OUTPUTS CONFIGURATION ALARMS ALARMS HISTORY ALARMS SUB-MENUS SERVICE FACTORY RUNTIME 1 RUNTIME 2 MAINTENANCE USER [SErviCE] [FACtorY] [RuntiME 1] [RuntiME 2] [MAintEnAnCE] [USEr] SUB-SUB-MENUS USER 1 USER 2 SCHEDULE 1 SCHEDULE 2 HOLIDAYS HOUR + DATE BROADCAST SERVICE 1… -
Page 13
SETPOINTS OUTPUTS ITEM STATUS TEMP PRESSURES INPUTS CONFIG ALARMS ALARMS HIST RUNTIMES Default display Evaporator water Discharge pressure Cooling setpoint 1 Contact 1: on/off Compressor status SUB-MENU: User Number of active Historic alarm code SUB-MENU: entering temp. circuit A circuit A Configuration (USEr) alarms/resets** Runtimes 1… -
Page 14
4.3.5 — Description of the Information menu INFORMATION MENU (3) ITEM FORMAT UNITS DESCRIPTION Automatic display mode. It cycles through the following displays: ±nn.n °C Controlled water temperature: temperature of the water that the unit tries to maintain at the control point. Unit operating type LOFF Local Off… -
Page 15
INFORMATION MENU (3) continued ITEM FORMAT UNITS DESCRIPTION ±nn.n °C Active setpoint. This is the current cooling/heating setpoint: it refers to cooling setpoint 1 or cooling/heating setpoint 2. See section 5.6.1. ±nn.n Control point. This is the setpoint used by the controller to adjust the temperature of the leaving or entering water (according to Forc °C configuration). -
Page 16
4.3.6 — Description of the Temperatures menu 4.3.7 — Description of the Pressures menu TEMPERATURES MENU [2] PRESSURES MENU [2] ITEM FORMAT UNITS COMMENTS ITEM FORMAT UNITS COMMENTS ±nn.n °C Evaporator entering water temperature nnnn Discharge pressure, circuit A. Relative pressure. ±nn.n °C Evaporator leaving water temperature… -
Page 17
LEAVING WATER TEMPERATURE CONTROL RESET THRESHOLDS IN COOLING OR HEATING MODE SETPOINT — °C R-407C Reset threshold Zero Full Minimum cooling value Reset based on outdoor -10 to 51 °C -10 to 51 °C Water air temperature Medium brine Reset based on 0 to 11.1 °C 0 to 11.1 °C Brine… -
Page 18
4.3.10 — Description of the Outputs/Tests menu 4.3.10.1 — General This menu displays the status of the controller outputs. More- over, when the machine is fully stopped (LOFF) the outputs can be activated for manual tests (the access to the tests is password controlled). -
Page 19
4.3.10.3 — Tests CONFIGURATION This function allows the user to test the outputs individually, if the machine is completely shut down (LOFF). To carry out a USER [USEr] manual test use the arrow keys to access the output to be tested and press the Enter key (longer than 2 seconds) to activate the USER1 USER2… -
Page 20
SUB-MENU USER CONFIGURATION ITEM USER 1 USER 2 DATE SCHEDULE 1 SCHEDULE 2 HOLIDAYS BROADCAST [USER1] [USER2]* [dAtE]* [ScHEduLE 1MEnu]* [ScHEduLE 2 MEnu]* [HOLidAy MEnu]* [BrodCASt]* Return to previous menu Return to previous Return to previous Return to previous menu Return to previous Return to previous menu Return to previous menu… -
Page 21
4.3.11.3 — Description of the User 1 Configuration sub-menu USER 1 CONFIGURATION SUB-MENU [2] ITEM FORMAT UNITS DEFAULT COMMENTS USEr MEnu When selected this item authorises return to the previous menu. 1 [1] 0/1/2 Circuit sequence selection (two-circuit units). 0 = Balanced circuit loading 1 = Circuit A first 2 = Circuit B first 2 [1]… -
Page 22
4.3.11.4 — Description of the User 2 Configuration sub-menu This menu is only accessible if the unit is equipped with an optional CCN/clock board USER 1 CONFIGURATION SUB-MENU ITEM FORMAT UNITS DEFAULT COMMENTS USEr 2 Menu When selected this item authorises return to the previous menu. 1[1] YES/no Periodic pump quick-start of the water pump(s) -
Page 23
Program is in unoccupied mode unless a schedule time period 4.3.11.7 — Description of the Holidays sub-menus is in effect. If two periods overlap and are both active on the This function is used to define 16 public holiday periods. Each same day, the occupied mode takes priority over the period is defined with the aid of three parameters: the month, unoccupied period. -
Page 24
HOLIDAY PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 16) 4.3.11.8 — Description of the Broadcast sub-menu ITEM # FORMAT COMMENTS The controller provides a broadcast configuration menu which HoLidAy X Sub-menu When selected this item authorises a return you can use to configure the unit to be the CCN’s broadcaster, to the configuration menu. -
Page 25
4.3.12 — Description of the Alarms menu 4.3.14.1 — Description of the Runtimes 1 menu This menu is used to display and reset up to 5 active alarms. It also permits alarm reset. If no alarm is active this menu is not RUNTIMES MENU [2] accessible. -
Page 26: Pro-Dialog Plus Control Operation
5 — PRO-DIALOG PLUS CONTROL OPERATION 4.3.14.3 — Maintenance menu description To be active, the maintenance function must be preset in the 5.1 — Start/stop control Service configuration ITEM # FORMAT DESCRIPTION The table below summarises the unit control type and stop or MAintEnAnCE MEnu When selected this item authorises return to go status with regard to the following parameters.
-
Page 27
ACTIVE OPERATING TYPE PARAMETER STATUS CONTROL UNIT TYPE STATUS REMOTE MASTER UNIT START/STOP CCN GENERAL START/STOP CONTROL SCHEDULE EMERGENCY ALARM LOFF L-C L-SC MASt CHIL_S_S CONTACT TYPE MODE SHUTDOWN Enable Active — Local Active — Unoccupied Local Active — Remote Active — Unoccupied Remote… -
Page 28: Heating/Cooling Operation
5.2 — Heating/cooling operation 5.4 — Condenser water pump control 5.2.1 — General The unit can control one or two condenser water pumps. These The heating/cooling selection applies to 30RW (liquid chillers) pumps can be fixed-speed or variable-speed pumps. Depending units, controlling a boiler or equipped with a heat pump option.
-
Page 29
The following table summarises the possible selections REMOTE OPERATING MODE — DUAL-CIRCUIT UNITS depending on the control types (local, remote or CCN) and the PARAMETER STATUS following parameters: HEATING/COOLING CONTROL SCHEDULE 2 ACTIVE SETPOINT OPERATING MODE CONTACTS STATUS Setpoint select in local control: item #13 of the Infor- Cooling sp 1 Cooling setpoint 1… -
Page 30: Demand Limit
5.6.2 — Reset 5.8 — Night mode Reset means that the active setpoint is modified so that less machine capacity is required (in cooling mode, the setpoint is The night period is defined (see User configuration) by a start increased, in heating mode it is decreased). This modifica-tion is time and an end time that are the same for each day of the in general a reaction to a drop in the load.
-
Page 31: Control Of A Boiler
5.10.2 — 30RWA units One of the functions of the master unit (depending on its configuration) may be the designation, whether the master or The control offers two control modes (fan stages with or slave is to be the lead machine or the follower. The roles of without Varifan) lead machine and follower will be reversed when the differ- Automatic mode.
-
Page 32: Diagnostics — Troubleshooting
6 — DIAGNOSTICS — TROUBLESHOOTING A manual reset must be run from the main interface using the following procedure: 6.1 — General RESET OF ACTIVE ALARMS OPERATION ITEM NUMBER ITEM VALUE PRESS MENU The PRO-DIALOG Plus control system has many fault tracing 2-DIGIT DISPLAY 4-DIGIT DISPLAY BUTTON LED aid functions.
-
Page 33: Alarm Codes
6.4 — Alarm codes The following list gives a complete description of each alarm code and its possible cause. ALARM CODE DESCRIPTIONS ALARM NAME ALARM DESCRIPTION ACTION TAKEN BY RESET TYPE PROBABLE CAUSE ALARM THE CONTROL CODE Compressor A1 failure Motor safety input has opened due to Compressor is shut Manual…
-
Page 34
ALARM CODE DESCRIPTIONS (continued) ALARM NAME ALARM DESCRIPTION ACTION TAKEN BY RESET TYPE PROBABLE CAUSE ALARM THE CONTROL CODE Safety interlock open Safety interlock not closed before end of the Unit prevented to start or Manual Evaporator pump control or water flow start-up delay or opens during operation shut down switch failure… -
Page 36
Order No. R3432-76, 06.2004. Supersedes order No.: 13432-76, 03.2002 Manufactured by: Carrier s.a., Montluel, France. Manufacturer reserves the right to change any product specification without notice. Printed in the Netherlands on chlorine-free paper.
Pro-Dialog Plus 30RB – это система управления одноконтурными, двухконтурными или трехконтурными жидкостными чиллерами с воздушным охлаждением 30RВ или тепловыми насосами воздух-вода 30RQ. Система Pro-Dialog Plus управляет пуском компрессоров, что необходимо для поддержания нужной температуры воды на входе и выходе теплообменника. В режиме охлаждения система управляет работой вентиляторов для поддержания требуемого давления конденсации в каждом контуре.
Документация
В режиме охлаждения система управляет работой вентиляторов для поддержания требуемого давления конденсации в каждом контуре. В тепловых насосах система регулирует и оптимизирует циклы размораживания каждого контура с целью минимизации уменьшения теплопроизводительности. Система Pro-Dialog Plus осуществляет постоянный мониторинг предохранительных устройств для обеспечения их надежной работы. Система Pro-Dialog Plus также обеспечивает доступ к программе Quick Test (быстрое тестирование), контролирующей все входы и выходы.
Все системы Pro-Dialog Plus могут работать в трех независимых режимах:
— Режим местного управления: управление машиной осуществляется командами с интерфейса пользователя.
— Режим дистанционного управления: управление машиной осуществляется удаленными контактами (контактами без напряжения).
— Режим CCN: управление машиной осуществляется командами из сети Carrier Comfort Network (CCN). В этом случае используется кабель передачи данных для соединения агрегата с коммуникационной шиной CCN.
Выбор режима работы осуществляется кнопкой Start/Stop(пуск/остановка). В случае автономной работы системы PRO-DIALOG Plus (в режиме местного или дистанционного управления) она сохраняет все свои возможности управления, но при этом не предусмотрено использование каких-либо возможностей сети CCN.
Электропитание всех плат осуществляется от общей шины 24 В переменного тока с заземленным нулем.
Предупреждение: При подключении плат к системе электропитания обеспечивайте правильную полярность, поскольку неправильное подключение приводит к повреждению платы.
В случае перерыва в подаче электропитания автоматически осуществляется повторный пуск агрегата без внешней команды. Но если в момент прекращения подачи электропитания имели место какие-либо ошибки, то они сохраняются и в некоторых случаях могут воспрепятствовать повторному пуску контура или агрегата. Все платы непрерывно осуществляют контроль и индикацию работы своих электронных схем. При нормальной работе на каждой плате светится светодиод.
— На плате NRCP-BASE красный светодиод мерцает с интервалом 2 секунды, что свидетельствует о нормальной работе платы. Другая периодичность мерцания светодиода указывает на наличие неисправности платы или программного обеспечения.
— Непрерывное мерцание зеленого светодиода на всех платах свидетельствует о наличии правильной связи платы по своей внутренней шине. Отсутствие мерцания светодиода указывает на наличие неисправности в электромонтаже шины LEN.
— Оранжевый светодиод ведущей платы мерцает в течение сеанса связи через шину CCN.
Датчики давления
Для измерения давлений нагнетания и всасывания в каждомконтуре используются электронные датчики двух типов.
Термисторы
Датчики температуры воды испарителя установлены навходе и выходе. Датчик температуры наружного воздуха установлен под блоком управления. Для регулирования работы комплекса «ведомый/ведущий» (в случае необходимости регулирования выходящей воды) может быть
установлен дополнительный датчик температуры в системе циркуляции воды.