Siemens lme73 000a2 коды ошибок

Siemens LME73.000A2 Pdf User Manuals. View online or download Siemens LME73.000A2 Basic Documentation
  1. Manuals
  2. Brands
  3. Siemens Manuals
  4. Controller
  5. LME73.000A2

Manuals and User Guides for Siemens LME73.000A2. We have 2 Siemens LME73.000A2 manuals available for free PDF download: Basic Documentation

Siemens LME73.000A2 Basic Documentation

Siemens LME73.000A2 Basic Documentation (245 pages)

Burner Control

Brand: Siemens
|
Category: Controller
|
Size: 4.99 MB

Table of Contents
    • Electrical Connection of Flame Detectors

      17

    • Standards and Certificates

      19

    • Typographical Conventions

      20

  • 2 System Makeup/Function Description

    21

    • External Display and Operating Units

      26

    • Connector Sets for LME7

      28

    • Test Case and Accessories

      29

    • Terminal Rating Inputs

      30

    • Terminal Rating Outputs

      31

    • Environmental Conditions

      33

    • Preconditions for Burner Startup

      38

    • Controlled Intermittent Operation

      38

    • Control Sequence in the Event of Fault

      39

    • Resetting the Burner Control

      39

    • Limitation of Repetitions (Can be Parameterized)

      40

  • 7 Operation, Indication, Diagnostics

    41

    • Indication of Operating State

      41

    • Diagnostics of Cause of Fault

      42

    • Description of Inputs and Outputs

      45

    • Safety Loop X3-04, Terminal 1 and 2

      46

    • Input for External Controller (ON/OFF) X5-03, Terminal 1

      46

    • Air Pressure Switch X3-02

      47

    • Program Sequence PME71.401

      48

    • Connection Diagrams for Fuel Train Applications (Examples)

      50

    • Gas Direct Ignition (G), 1-Stage

      50

    • Gas Direct Ignition (G), 2-Stage

      50

    • Time Table and Settings for Program Sequence PME71.401

      51

    • Parameter List PME71.401

      53

    • Program Sequence PME71.402

      55

    • Connection Diagrams for Fuel Train Applications (Examples)

      57

    • Gas Direct Ignition (G), 1-Stage

      57

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      57

    • Time Table and Settings for Program Sequence PME71.402

      58

    • Parameter List PME71.402

      60

    • Program Sequence PME71.901

      63

    • Connection Diagrams for Fuel Train Applications (Examples)

      65

    • Gas Direct Ignition (G), 1-Stage

      65

    • Gas Direct Ignition (G), 1-Stage and Valve Proving

      65

      • Valve Proving with Separate Pressure Switch

        66

      • Valve Proving — Calculation of Leakage Rate

        67

    • Time Table and Settings for Program Sequence PME71.901

      68

    • Parameter List PME71.901

      70

    • Program Sequence PME72.521

      75

    • Connection Diagrams for Fuel Train Applications (Examples)

      77

    • Gas Direct Ignition (G), 1-Stage

      77

    • Gas Direct Ignition 1 (Gp1/1), 2-Stage

      77

    • Connection Diagram for LME72.000

      78

    • Connection Diagram for LME72.000

      79

    • Time Table and Settings for Program Sequence PME72.521

      80

    • Parameter List PME72.521

      82

    • Program Sequence PME72.541

      84

    • Connection Diagrams for Fuel Train Applications (Examples)

      86

    • Gas Direct Ignition (G), 1-Stage

      86

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      86

    • Connection Diagram for LME72.000

      87

    • Connection Diagram for LME72.000

      88

    • Time Table and Settings for Program Sequence PME72.541

      89

    • Parameter List PME72.541

      91

    • Program Sequence PME73.810

      93

    • Connection Diagrams for Fuel Train Applications (Examples)

      95

    • Gas Direct Ignition (G), 1-Stage

      95

    • Gas Direct Ignition (G), 2-Stage

      95

    • Gas Direct Ignition (G), 1-Stage, with Valve Proving

      96

    • Gas Direct Ignition (G), 2-Stage, with Valve Proving

      96

      • Valve Proving with Separate Pressure Switch

        97

      • Valve Proving — Calculation of Leakage Rate

        98

    • Connection Diagram for LME73.000

      99

    • Time Table and Settings for Program Sequence PME73.810

      100

    • Parameter List PME73.810

      102

    • Program Sequence PME73.820

      105

    • Connection Diagrams for Fuel Train Applications (Examples)

      107

    • Gas Direct Ignition (G), 1-Stage

      107

    • Gas Direct Ignition 1 (G), 2-Stage

      107

    • Gas Direct Ignition 1 (G), 1-Stage, with Valve Proving

      108

    • Gas Direct Ignition (G), 2-Stage, with Valve Proving

      108

      • Valve Proving with Separate Pressure Switch

        109

      • Valve Proving — Calculation of Leakage Rate

        110

    • Connection Diagram for LME73.000

      111

    • Connection Diagram for LME73.000

      112

    • Time Tables and Settings for Program Sequence PME73.820

      113

    • Parameter List PME73.820

      115

    • Program Sequence PME73.830

      118

    • Connection Diagrams for Fuel Train Applications (Examples)

      120

    • Gas Direct Ignition (G), 1-Stage

      120

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      120

    • Gas Pilot Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      121

    • Gas Direct Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      121

      • Valve Proving with Separate Pressure Switch

        122

      • Valve Proving — Calculation of Leakage Rate

        123

    • Connection Diagram for LME73.000

      124

    • Time Table and Settings for Program Sequence PME73.830

      125

    • Parameter List PME73.830

      127

    • Program Sequence PME73.831

      130

    • Connection Diagrams for Fuel Applications (Examples)

      135

    • Gas Direct Ignition (G), 1-Stage, Without Valve Proving

      135

    • Gas Pilot Ignition 2 (Gp2), 1-Stage, Without Valve Proving, Simultaneously Ignition Burner

      135

    • Gas Pilot Ignition 1 (Gp1), 1-Stage, with Valve Proving, Alternate Burning Ignition Burner

      136

    • Gas Direct Ignition 1 (G), 1-Stage, with Valve Proving

      136

    • Valve Proving of Gas Valves

      137

      • Valve Proving with Separate Pressure Switch

        137

      • Valve Proving — Calculation of Leakage Rate

        138

    • Connection Diagram for LME73.000

      139

    • Connection Diagram for LME73.000

      140

    • Time Table and Settings for Program Sequence PME73.831

      141

    • Parameter List PME73.831

      144

    • Program Sequence PME73.840

      148

    • Connection Diagrams for Fuel Train Applications (Examples)

      150

    • Gas Direct Ignition (G), 1-Stage

      150

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      150

    • Gas Pilot Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      151

    • Gas Direct Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      151

      • Valve Proving with Separate Pressure Switch

        152

      • Valve Proving — Calculation of Leakage Rate

        153

    • Connection Diagram for LME73.000

      154

    • Connection Diagram for LME73.000

      155

    • Time Table and Settings for Program Sequence PME73.840

      156

    • Parameter List PME73.840

      158

  • 21 Multistage or Modulating Mode

    163

    • Connection Diagram for Feedback Potentiometer ASZ12.33

      163

    • Connection Diagram for Load Controller

      164

    • Load Controller Inputs

      165

    • 3-Position Step Input X5-03

      165

    • Selection Source Preset Output Analog/3-Position Step Input (P654)

      165

    • Actuator Output X2-09

      165

    • Setting the Maximum Running Time of the Actuator (P259/P260 Timeout)

      165

    • Multistage/Modulating Mode Via 3-Position Step Input X5-03

      166

    • Maximum Possible Resolution

      166

    • Modulating Mode Via Analog Input Signal X65

      166

    • Standardization of Modulation Range

      166

    • Setting the Minimum Power Control Step (Dead Band) (P123) in Modulating Mode Via Analog Input Signal X65

      167

  • 22 Safety Notes Relating to Operation of AZL2

    168

    • Building Technologies Division Basic Documentation LME7

      169

  • 23 Operation Via AZL2

    169

    • Description of the Unit/Display and Buttons

      169

    • Meaning of Symbols on the Display

      170

    • Display in Standby Mode

      171

    • Display During Startup/Shutdown

      171

      • Display of Program Phases

        171

      • List of Phase Display (Display Depending on Program)

        172

    • Display of Operating Position

      173

    • Fault Status Messages, Display of Errors and Info

      174

      • Display of Errors (Faults) with Lockout

        174

    • Menu-Driven Operation

      175

    • Display of Info Level

      177

    • Display of Info Values

      177

    • Identification Number

      177

    • Identification of Burner

      178

    • Number of Startups Resettable

      179

    • Total Number of Startups

      180

    • Display of the Service Level

      181

    • Display of Service Values

      182

    • Entering the Password

      184

    • Changing the Heating Engineer’s Password

      186

    • Changing the Oem’s Password

      187

    • Operating Variants of the Parameters

      192

    • Parameters Without Index, with Direct Display

      192

    • Example of Parameter 225 (Prepurge Time) on the Parameter Level

      192

    • Parameters Without Index, with no Direct Display

      194

    • Example of Parameter 224 (Specified Time Air Pressure Switch) on the Parameter Level

      194

    • Parameters with Index, with or Without Direct Display

      196

    • Example of Parameter 701: Actual Error on the Service Level

      196

  • 24 Error Code List with Operation Via External AZL2

    199

  • 25 Operation Via Internal LED

    201

    • Description of Display and Buttons

      201

    • Display in Standby Mode

      202

    • Display During Startup/Shutdown

      202

    • Display of Program Phases

      202

    • List of Phase Display

      203

    • Display of Operating Position

      205

    • Fault Status Messages, Display of Errors

      206

    • Display of Errors (Faults) with Lockout

      206

    • Display of Flame Current ION or QRA

      207

    • Display of Flame Current QRB

      208

    • Display of Preset Output

      209

    • Manual Adjustment (Depending on Program Module)

      210

    • Position of Actuator or Speed of PWM Fan in Modulating Operation with Analog Signal

      210

    • First Startup with a New Program Module or in Case of Replacement of Program Module

      213

    • Error During Backup Process

      216

    • Errors During the Restore Process

      218

  • 26 Error Code List with Operation Via Internal LED

    219

    • PWM Control Parameters

      223

    • PWM Safety Parameters

      224

    • Initial PWM Parameter Settings

      225

    • Initial Settings of PWM Basic Parameters

      225

    • Reading the Value of Parameter 920 in the Prepurge Phase (P30) and Ignition Load Phase (P38, P40 and P44)

      228

    • Final Settings of PWM Safety Parameters

      229

      • Checking the Ignition Load

        230

    • Setting Safety Parameters 675.00/675.01 and Checking the Safety Settings under Worst-Case Conditions

      231

      • Checking the Ignition Load

        232

    • Matching the Working Points «Speeds for Low-Fire (P1), Ignition Load (P0) and High-Fire (P2) for the Heating Engineer to the Application

      232

    • Via the Onboard Operating Panel of the LME7

      233

    • Overview of PWM Fan Parameters (Value Range Refers to PME71.901)

      236

Siemens LME73.000A2 Basic Documentation

Siemens LME73.000A2 Basic Documentation (116 pages)

Burner control

Brand: Siemens
|
Category: Safety Equipment
|
Size: 2.94 MB

Table of Contents
    • Electrical Connection of Flame Detectors

      11

    • Standards and Certificates

      13

    • Typographical Conventions

      15

  • 2 System Makeup / Function Description

    16

    • PME7 with Mains Voltage AC 120 V

      19

    • PME7 with Mains Voltage AC 230 V

      21

    • External Display and Operating Units

      23

    • Connector Sets for LME7

      26

    • Terminal Rating Inputs

      29

    • Terminal Rating Outputs

      30

    • Environmental Conditions

      35

    • QRA2 / QRA4 / QRA10 (LME71 / LME73 Only)

      38

    • Preconditions for Burner Startup

      43

    • Controlled Intermittent Operation

      43

    • Control Sequence in the Event of Fault

      44

    • Restart in the Event of Loss of Flame

      45

    • Repetition in Case of no Flame Is Established by the End of Safety Time (TSA)

      45

  • 7 Operation, Indication, Diagnostics

    46

    • Indication of Operating State

      46

    • Diagnostics of Cause of Fault

      47

  • 9 Connection Diagram AGG9 Connector

    50

  • 10 LME7 Burner Control

    53

    • Description of Inputs and Outputs

      53

    • Safety Loop Terminal X3-04 Pin 1 and 2

      54

    • Input for External Controller (ON/OFF) Terminal X5-03 Pin 1

      54

    • Air Pressure Switch Terminal X3-02

      55

    • Input Gas Pressure Switch-Min

      55

  • 11 Multistage or Modulating Mode with Actuator

    56

    • Connection Diagram for Feedback Potentiometer ASZ12.33

      56

    • Connection Diagram for Load Controller (LME71/LME73 Only)

      57

    • Load Controller Inputs

      58

    • 3-Position Step Input Terminal X5-03

      58

    • Analog Input Terminal X65 (LME71/LME73 Only)

      58

    • Selection Source Preset Output Analog / 3-Position Step Input (Parameter 654) (LME71/LME73 Only)

      58

    • Actuator Output Terminal X2-09

      58

    • Setting the Maximum Running Time of the Actuator (Parameter 259 / 260 Timeout)

      58

    • Multistage / Modulating Mode Via 3-Position Step Input Terminal X5-03

      59

    • Maximum Possible Resolution

      59

    • Modulating Mode Via Analog Input Signal Terminal X65 (LME71/LME73 Only)

      59

    • Standardization of Modulation Range

      59

    • Setting the Minimum Power Control Step (Dead Band) (Parameter 123)

      60

      • User Limitations / Application Examples

        61

  • 12 Safety Notes Relating to Operation of AZL2

    62

    • Description of the Unit / Display and Buttons

      63

    • Meaning of Symbols on the Display

      64

    • Display in Standby Mode

      65

    • Display During Startup / Shutdown

      65

      • Display of Program Phases

        65

      • List of Phase Display (Display Depending on Program)

        66

    • Display of Operating Position

      67

    • Fault Status Messages, Display of Errors and Info

      68

      • Display of Errors (Faults) with Lockout

        68

    • Display of Info Values

      71

    • Identification of Burner

      72

    • Number of Startups Resettable

      73

    • Total Number of Startups

      74

    • Display of the Service Level

      75

    • Display of Service Values

      76

    • Changing the Heating Engineer’s Password

      80

    • Changing the Oem’s Password

      82

    • Operating Variants of the Parameters

      87

    • Parameters Without Index, with Direct Display

      87

    • Example of Parameter 225 (Prepurge Time) on the Parameter Level

      87

    • Parameters Without Index, with no Direct Display

      89

    • Example of Parameter 224 (Specified Time Air Pressure Switch) on the Parameter Level

      89

    • Parameters with Index, with or Without Direct Display

      91

    • Example of Parameter 701: Actual Error on the Service Level

      91

  • 14 Error Code List with Operation Via External AZL2 Display

    94

  • 15 Operation Via Internal LED

    96

    • Description of Display and Buttons

      96

    • Display in Standby Mode

      97

    • Display During Startup / Shutdown

      97

    • Display of Program Phases

      97

    • Display of Operating Position

      100

    • Fault Status Messages, Display of Errors

      101

    • Display of Errors (Faults) with Lockout

      101

    • Display of Flame Current ION or QRA

      102

    • Display of Preset Output

      103

    • Manual Adjustment (Depending on the PME7)

      104

    • Position of Actuator or Speed of PWM Fan in Modulating Operation with Analog Signal

      104

    • Initial Startup with a New PME7 or in Case of Replacement of the PME7

      107

    • Error During Backup Process

      110

    • Errors During the Restore Process

      112

Related Products

  • Siemens LME73

  • Siemens LME73.000A1

  • Siemens LME7 Series

  • Siemens LME75

  • Siemens LME71

  • Siemens LME71.000A1

  • Siemens LME71.000A2

  • Siemens LME72.000A2

  • Siemens LME41.071A2

  • Siemens LME39.400C1

Siemens Categories

Controller

Control Unit

Industrial Equipment

Washer
Washer

Switch
Switch

More Siemens Manuals

  1. Manuals
  2. Brands
  3. Siemens Manuals
  4. Controller
  5. LME73.000A2

Manuals and User Guides for Siemens LME73.000A2. We have 2 Siemens LME73.000A2 manuals available for free PDF download: Basic Documentation

Siemens LME73.000A2 Basic Documentation

Siemens LME73.000A2 Basic Documentation (245 pages)

Burner Control

Brand: Siemens
|
Category: Controller
|
Size: 4.99 MB

Table of Contents
    • Electrical Connection of Flame Detectors

      17

    • Standards and Certificates

      19

    • Typographical Conventions

      20

  • 2 System Makeup/Function Description

    21

    • External Display and Operating Units

      26

    • Connector Sets for LME7

      28

    • Test Case and Accessories

      29

    • Terminal Rating Inputs

      30

    • Terminal Rating Outputs

      31

    • Environmental Conditions

      33

    • Preconditions for Burner Startup

      38

    • Controlled Intermittent Operation

      38

    • Control Sequence in the Event of Fault

      39

    • Resetting the Burner Control

      39

    • Limitation of Repetitions (Can be Parameterized)

      40

  • 7 Operation, Indication, Diagnostics

    41

    • Indication of Operating State

      41

    • Diagnostics of Cause of Fault

      42

    • Description of Inputs and Outputs

      45

    • Safety Loop X3-04, Terminal 1 and 2

      46

    • Input for External Controller (ON/OFF) X5-03, Terminal 1

      46

    • Air Pressure Switch X3-02

      47

    • Program Sequence PME71.401

      48

    • Connection Diagrams for Fuel Train Applications (Examples)

      50

    • Gas Direct Ignition (G), 1-Stage

      50

    • Gas Direct Ignition (G), 2-Stage

      50

    • Time Table and Settings for Program Sequence PME71.401

      51

    • Parameter List PME71.401

      53

    • Program Sequence PME71.402

      55

    • Connection Diagrams for Fuel Train Applications (Examples)

      57

    • Gas Direct Ignition (G), 1-Stage

      57

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      57

    • Time Table and Settings for Program Sequence PME71.402

      58

    • Parameter List PME71.402

      60

    • Program Sequence PME71.901

      63

    • Connection Diagrams for Fuel Train Applications (Examples)

      65

    • Gas Direct Ignition (G), 1-Stage

      65

    • Gas Direct Ignition (G), 1-Stage and Valve Proving

      65

      • Valve Proving with Separate Pressure Switch

        66

      • Valve Proving — Calculation of Leakage Rate

        67

    • Time Table and Settings for Program Sequence PME71.901

      68

    • Parameter List PME71.901

      70

    • Program Sequence PME72.521

      75

    • Connection Diagrams for Fuel Train Applications (Examples)

      77

    • Gas Direct Ignition (G), 1-Stage

      77

    • Gas Direct Ignition 1 (Gp1/1), 2-Stage

      77

    • Connection Diagram for LME72.000

      78

    • Connection Diagram for LME72.000

      79

    • Time Table and Settings for Program Sequence PME72.521

      80

    • Parameter List PME72.521

      82

    • Program Sequence PME72.541

      84

    • Connection Diagrams for Fuel Train Applications (Examples)

      86

    • Gas Direct Ignition (G), 1-Stage

      86

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      86

    • Connection Diagram for LME72.000

      87

    • Connection Diagram for LME72.000

      88

    • Time Table and Settings for Program Sequence PME72.541

      89

    • Parameter List PME72.541

      91

    • Program Sequence PME73.810

      93

    • Connection Diagrams for Fuel Train Applications (Examples)

      95

    • Gas Direct Ignition (G), 1-Stage

      95

    • Gas Direct Ignition (G), 2-Stage

      95

    • Gas Direct Ignition (G), 1-Stage, with Valve Proving

      96

    • Gas Direct Ignition (G), 2-Stage, with Valve Proving

      96

      • Valve Proving with Separate Pressure Switch

        97

      • Valve Proving — Calculation of Leakage Rate

        98

    • Connection Diagram for LME73.000

      99

    • Time Table and Settings for Program Sequence PME73.810

      100

    • Parameter List PME73.810

      102

    • Program Sequence PME73.820

      105

    • Connection Diagrams for Fuel Train Applications (Examples)

      107

    • Gas Direct Ignition (G), 1-Stage

      107

    • Gas Direct Ignition 1 (G), 2-Stage

      107

    • Gas Direct Ignition 1 (G), 1-Stage, with Valve Proving

      108

    • Gas Direct Ignition (G), 2-Stage, with Valve Proving

      108

      • Valve Proving with Separate Pressure Switch

        109

      • Valve Proving — Calculation of Leakage Rate

        110

    • Connection Diagram for LME73.000

      111

    • Connection Diagram for LME73.000

      112

    • Time Tables and Settings for Program Sequence PME73.820

      113

    • Parameter List PME73.820

      115

    • Program Sequence PME73.830

      118

    • Connection Diagrams for Fuel Train Applications (Examples)

      120

    • Gas Direct Ignition (G), 1-Stage

      120

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      120

    • Gas Pilot Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      121

    • Gas Direct Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      121

      • Valve Proving with Separate Pressure Switch

        122

      • Valve Proving — Calculation of Leakage Rate

        123

    • Connection Diagram for LME73.000

      124

    • Time Table and Settings for Program Sequence PME73.830

      125

    • Parameter List PME73.830

      127

    • Program Sequence PME73.831

      130

    • Connection Diagrams for Fuel Applications (Examples)

      135

    • Gas Direct Ignition (G), 1-Stage, Without Valve Proving

      135

    • Gas Pilot Ignition 2 (Gp2), 1-Stage, Without Valve Proving, Simultaneously Ignition Burner

      135

    • Gas Pilot Ignition 1 (Gp1), 1-Stage, with Valve Proving, Alternate Burning Ignition Burner

      136

    • Gas Direct Ignition 1 (G), 1-Stage, with Valve Proving

      136

    • Valve Proving of Gas Valves

      137

      • Valve Proving with Separate Pressure Switch

        137

      • Valve Proving — Calculation of Leakage Rate

        138

    • Connection Diagram for LME73.000

      139

    • Connection Diagram for LME73.000

      140

    • Time Table and Settings for Program Sequence PME73.831

      141

    • Parameter List PME73.831

      144

    • Program Sequence PME73.840

      148

    • Connection Diagrams for Fuel Train Applications (Examples)

      150

    • Gas Direct Ignition (G), 1-Stage

      150

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      150

    • Gas Pilot Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      151

    • Gas Direct Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      151

      • Valve Proving with Separate Pressure Switch

        152

      • Valve Proving — Calculation of Leakage Rate

        153

    • Connection Diagram for LME73.000

      154

    • Connection Diagram for LME73.000

      155

    • Time Table and Settings for Program Sequence PME73.840

      156

    • Parameter List PME73.840

      158

  • 21 Multistage or Modulating Mode

    163

    • Connection Diagram for Feedback Potentiometer ASZ12.33

      163

    • Connection Diagram for Load Controller

      164

    • Load Controller Inputs

      165

    • 3-Position Step Input X5-03

      165

    • Selection Source Preset Output Analog/3-Position Step Input (P654)

      165

    • Actuator Output X2-09

      165

    • Setting the Maximum Running Time of the Actuator (P259/P260 Timeout)

      165

    • Multistage/Modulating Mode Via 3-Position Step Input X5-03

      166

    • Maximum Possible Resolution

      166

    • Modulating Mode Via Analog Input Signal X65

      166

    • Standardization of Modulation Range

      166

    • Setting the Minimum Power Control Step (Dead Band) (P123) in Modulating Mode Via Analog Input Signal X65

      167

  • 22 Safety Notes Relating to Operation of AZL2

    168

    • Building Technologies Division Basic Documentation LME7

      169

  • 23 Operation Via AZL2

    169

    • Description of the Unit/Display and Buttons

      169

    • Meaning of Symbols on the Display

      170

    • Display in Standby Mode

      171

    • Display During Startup/Shutdown

      171

      • Display of Program Phases

        171

      • List of Phase Display (Display Depending on Program)

        172

    • Display of Operating Position

      173

    • Fault Status Messages, Display of Errors and Info

      174

      • Display of Errors (Faults) with Lockout

        174

    • Menu-Driven Operation

      175

    • Display of Info Level

      177

    • Display of Info Values

      177

    • Identification Number

      177

    • Identification of Burner

      178

    • Number of Startups Resettable

      179

    • Total Number of Startups

      180

    • Display of the Service Level

      181

    • Display of Service Values

      182

    • Entering the Password

      184

    • Changing the Heating Engineer’s Password

      186

    • Changing the Oem’s Password

      187

    • Operating Variants of the Parameters

      192

    • Parameters Without Index, with Direct Display

      192

    • Example of Parameter 225 (Prepurge Time) on the Parameter Level

      192

    • Parameters Without Index, with no Direct Display

      194

    • Example of Parameter 224 (Specified Time Air Pressure Switch) on the Parameter Level

      194

    • Parameters with Index, with or Without Direct Display

      196

    • Example of Parameter 701: Actual Error on the Service Level

      196

  • 24 Error Code List with Operation Via External AZL2

    199

  • 25 Operation Via Internal LED

    201

    • Description of Display and Buttons

      201

    • Display in Standby Mode

      202

    • Display During Startup/Shutdown

      202

    • Display of Program Phases

      202

    • List of Phase Display

      203

    • Display of Operating Position

      205

    • Fault Status Messages, Display of Errors

      206

    • Display of Errors (Faults) with Lockout

      206

    • Display of Flame Current ION or QRA

      207

    • Display of Flame Current QRB

      208

    • Display of Preset Output

      209

    • Manual Adjustment (Depending on Program Module)

      210

    • Position of Actuator or Speed of PWM Fan in Modulating Operation with Analog Signal

      210

    • First Startup with a New Program Module or in Case of Replacement of Program Module

      213

    • Error During Backup Process

      216

    • Errors During the Restore Process

      218

  • 26 Error Code List with Operation Via Internal LED

    219

    • PWM Control Parameters

      223

    • PWM Safety Parameters

      224

    • Initial PWM Parameter Settings

      225

    • Initial Settings of PWM Basic Parameters

      225

    • Reading the Value of Parameter 920 in the Prepurge Phase (P30) and Ignition Load Phase (P38, P40 and P44)

      228

    • Final Settings of PWM Safety Parameters

      229

      • Checking the Ignition Load

        230

    • Setting Safety Parameters 675.00/675.01 and Checking the Safety Settings under Worst-Case Conditions

      231

      • Checking the Ignition Load

        232

    • Matching the Working Points «Speeds for Low-Fire (P1), Ignition Load (P0) and High-Fire (P2) for the Heating Engineer to the Application

      232

    • Via the Onboard Operating Panel of the LME7

      233

    • Overview of PWM Fan Parameters (Value Range Refers to PME71.901)

      236

Siemens LME73.000A2 Basic Documentation

Siemens LME73.000A2 Basic Documentation (116 pages)

Burner control

Brand: Siemens
|
Category: Safety Equipment
|
Size: 2.94 MB

Table of Contents
    • Electrical Connection of Flame Detectors

      11

    • Standards and Certificates

      13

    • Typographical Conventions

      15

  • 2 System Makeup / Function Description

    16

    • PME7 with Mains Voltage AC 120 V

      19

    • PME7 with Mains Voltage AC 230 V

      21

    • External Display and Operating Units

      23

    • Connector Sets for LME7

      26

    • Terminal Rating Inputs

      29

    • Terminal Rating Outputs

      30

    • Environmental Conditions

      35

    • QRA2 / QRA4 / QRA10 (LME71 / LME73 Only)

      38

    • Preconditions for Burner Startup

      43

    • Controlled Intermittent Operation

      43

    • Control Sequence in the Event of Fault

      44

    • Restart in the Event of Loss of Flame

      45

    • Repetition in Case of no Flame Is Established by the End of Safety Time (TSA)

      45

  • 7 Operation, Indication, Diagnostics

    46

    • Indication of Operating State

      46

    • Diagnostics of Cause of Fault

      47

  • 9 Connection Diagram AGG9 Connector

    50

  • 10 LME7 Burner Control

    53

    • Description of Inputs and Outputs

      53

    • Safety Loop Terminal X3-04 Pin 1 and 2

      54

    • Input for External Controller (ON/OFF) Terminal X5-03 Pin 1

      54

    • Air Pressure Switch Terminal X3-02

      55

    • Input Gas Pressure Switch-Min

      55

  • 11 Multistage or Modulating Mode with Actuator

    56

    • Connection Diagram for Feedback Potentiometer ASZ12.33

      56

    • Connection Diagram for Load Controller (LME71/LME73 Only)

      57

    • Load Controller Inputs

      58

    • 3-Position Step Input Terminal X5-03

      58

    • Analog Input Terminal X65 (LME71/LME73 Only)

      58

    • Selection Source Preset Output Analog / 3-Position Step Input (Parameter 654) (LME71/LME73 Only)

      58

    • Actuator Output Terminal X2-09

      58

    • Setting the Maximum Running Time of the Actuator (Parameter 259 / 260 Timeout)

      58

    • Multistage / Modulating Mode Via 3-Position Step Input Terminal X5-03

      59

    • Maximum Possible Resolution

      59

    • Modulating Mode Via Analog Input Signal Terminal X65 (LME71/LME73 Only)

      59

    • Standardization of Modulation Range

      59

    • Setting the Minimum Power Control Step (Dead Band) (Parameter 123)

      60

      • User Limitations / Application Examples

        61

  • 12 Safety Notes Relating to Operation of AZL2

    62

    • Description of the Unit / Display and Buttons

      63

    • Meaning of Symbols on the Display

      64

    • Display in Standby Mode

      65

    • Display During Startup / Shutdown

      65

      • Display of Program Phases

        65

      • List of Phase Display (Display Depending on Program)

        66

    • Display of Operating Position

      67

    • Fault Status Messages, Display of Errors and Info

      68

      • Display of Errors (Faults) with Lockout

        68

    • Display of Info Values

      71

    • Identification of Burner

      72

    • Number of Startups Resettable

      73

    • Total Number of Startups

      74

    • Display of the Service Level

      75

    • Display of Service Values

      76

    • Changing the Heating Engineer’s Password

      80

    • Changing the Oem’s Password

      82

    • Operating Variants of the Parameters

      87

    • Parameters Without Index, with Direct Display

      87

    • Example of Parameter 225 (Prepurge Time) on the Parameter Level

      87

    • Parameters Without Index, with no Direct Display

      89

    • Example of Parameter 224 (Specified Time Air Pressure Switch) on the Parameter Level

      89

    • Parameters with Index, with or Without Direct Display

      91

    • Example of Parameter 701: Actual Error on the Service Level

      91

  • 14 Error Code List with Operation Via External AZL2 Display

    94

  • 15 Operation Via Internal LED

    96

    • Description of Display and Buttons

      96

    • Display in Standby Mode

      97

    • Display During Startup / Shutdown

      97

    • Display of Program Phases

      97

    • Display of Operating Position

      100

    • Fault Status Messages, Display of Errors

      101

    • Display of Errors (Faults) with Lockout

      101

    • Display of Flame Current ION or QRA

      102

    • Display of Preset Output

      103

    • Manual Adjustment (Depending on the PME7)

      104

    • Position of Actuator or Speed of PWM Fan in Modulating Operation with Analog Signal

      104

    • Initial Startup with a New PME7 or in Case of Replacement of the PME7

      107

    • Error During Backup Process

      110

    • Errors During the Restore Process

      112

Related Products

  • Siemens LME73

  • Siemens LME73.000A1

  • Siemens LME7 Series

  • Siemens LME75

  • Siemens LME71

  • Siemens LME71.000A1

  • Siemens LME71.000A2

  • Siemens LME72.000A2

  • Siemens LME41.071A2

  • Siemens LME39.400C1

Siemens Categories

Controller

Control Unit

Industrial Equipment

Washer
Washer

Switch
Switch

More Siemens Manuals

Error code

Clear text

Fault of compatibility program module to

bAC Er3

basic unit during backup process

Err PrC

Fault of program module

No establishment of flame at the end of the

safety time

Loc 2

Air pressure faulty (air pressure switch

welded in no-load position), decrease to

Loc 3

specified time (air pressure switch) response

time)

Loc 4

Extraneous light

Air pressure faulty, air pressure switch

Loc 5

welded in working position

Loc 6

Fault of actuator

Loss of flame

Loc 7

Loc 8

Loc 9

Error not relatable (application), internal error

Loc 10

Loc 12

Valve proving

Loc 13

Valve proving

Loc 14

POC error

Loc 20

Gas pressure switch min open

Loc 22

Safety loop open

Loc 60

Analog power source 4…20 mA, I <4 mA

Loc: 83

Faulty PWM fan

Loc 138

Restore process successful

Loc 139

No program module detected

Loc 167

Manual locking

Loc: 206

AZL2… incompatible

Building Technologies Division

Infrastructure & Cities Sector

26 Error code list with operation via

internal LED

Note:

Display depends on program!

Basic Documentation LME7…

Possible cause

Program sequence of program module does not

match the basic unit

— Error in data content of program module

— No program module fitted

— Faulty or soiled fuel valves

— Faulty or soiled flame detector

— Poor adjustment of burner, no fuel

— Faulty ignition equipment

Air pressure switch faulty

— Loss of air pressure signal after specified time

— Air pressure switch is welded in no-load position

Extraneous light when burner startup

Time out air pressure switch

— Air pressure switch is welded in working position

— Actuator faulty or blocked

— Faulty connection

— Wrong adjustment

Too many losses of flame during operation

(limitation of repetitions)

— Faulty or soiled fuel valves

— Faulty or soiled flame detector

— Poor adjustment of burner

Free

Free

Wiring error or internal error, output contacts,

other faults

Fuel valve 1 leak

Fuel valve 2 leak

Error valve closure control POC

Gas shortage

— Gas pressure switch-max open

— Safety limit thermostat cut out

Wire breakage

— PWM fan does not reach the target speed within

the preset period of time, or

— After reaching the target speed, the PWM fan

leaves the tolerance band again (P650) for a

time exceeding the tolerance time speed

deviation (P660)

Restore process successful

No program module identified

Manual locking

Use the latest version

219/245

CC1P7105en

29.11.2011

  1. Manuals
  2. Brands
  3. Siemens Manuals
  4. Controller
  5. LME73.000A2

Manuals and User Guides for Siemens LME73.000A2. We have 2 Siemens LME73.000A2 manuals available for free PDF download: Basic Documentation

Siemens LME73.000A2 Basic Documentation

Siemens LME73.000A2 Basic Documentation (245 pages)

Burner Control

Brand: Siemens
|
Category: Controller
|
Size: 4.99 MB

Table of Contents
  • Table of Contents

    5

  • 1 Safety Notes

    13

    • Warning Notes

      13

    • Mounting Notes

      15

    • Installation Notes

      16

    • Electrical Connection of Flame Detectors

      17

    • Commissioning Notes

      18

    • Standards and Certificates

      19

    • Lifetime

      19

    • Disposal Notes

      19

    • Typographical Conventions

      20

    • Safety Notes

      20

  • 2 System Makeup/Function Description

    21

    • Features

      22

  • 3 Type Summary

    23

    • Burner Controls

      23

    • Program Module

      24

    • External Display and Operating Units

      26

    • Flame Detectors

      26

    • Actuators

      27

    • Pressure Switch

      27

    • Dummy Plugs for RJ11

      28

    • Connector Sets for LME7

      28

    • Service- Tools

      28

    • Test Case and Accessories

      29

  • 4 Technical Data

    30

    • Basic Unit LME7

      30

    • Terminal Rating Inputs

      30

    • Terminal Rating Outputs

      31

    • Cable Lengths

      32

    • Actuators

      32

    • Cross-Sectional Areas

      32

    • Signal Cable AGV50

      33

    • Azl2

      33

    • Dummy Plug for RJ11

      33

    • Environmental Conditions

      33

    • Flame Supervision

      34

    • Ionization Probe

      34

    • Flame Detector QRA2

      36

  • 5 Dimensions

    37

  • 6 Function

    38

    • Preconditions for Burner Startup

      38

    • Undervoltage

      38

    • Controlled Intermittent Operation

      38

    • Control Sequence in the Event of Fault

      39

    • Resetting the Burner Control

      39

    • Limitation of Repetitions (Can be Parameterized)

      40

      • Parameter 240)

        40

    • Parameter 240/240.00

      40

    • Parameter 240.01

      40

  • 7 Operation, Indication, Diagnostics

    41

    • Operation

      41

    • Indication of Operating State

      41

    • Diagnostics of Cause of Fault

      42

  • 8 Inputs/Outputs

    44

  • 9 Basic Unit

    45

    • Description of Inputs and Outputs

      45

    • Digital Input

      46

    • Safety Loop X3-04, Terminal 1 and 2

      46

    • Input for External Controller (ON/OFF) X5-03, Terminal 1

      46

    • Air Pressure Switch X3-02

      47

  • 10 Pme71.401

    48

    • Program Sequence PME71.401

      48

    • Connection Diagrams for Fuel Train Applications (Examples)

      50

    • Gas Direct Ignition (G), 1-Stage

      50

    • Gas Direct Ignition (G), 2-Stage

      50

    • Time Table and Settings for Program Sequence PME71.401

      51

    • Lme71.000

      52

    • Parameter List PME71.401

      53

  • 11 Pme71.402

    55

    • Program Sequence PME71.402

      55

    • Connection Diagrams for Fuel Train Applications (Examples)

      57

    • Gas Direct Ignition (G), 1-Stage

      57

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      57

    • Time Table and Settings for Program Sequence PME71.402

      58

    • Lme71.000

      59

    • Parameter List PME71.402

      60

  • 12 Pme71.901

    63

    • Program Sequence PME71.901

      63

    • Connection Diagrams for Fuel Train Applications (Examples)

      65

    • Gas Direct Ignition (G), 1-Stage

      65

    • Gas Direct Ignition (G), 1-Stage and Valve Proving

      65

    • Gas Valve Proving

      66

      • Valve Proving with Separate Pressure Switch

        66

      • Valve Proving — Calculation of Leakage Rate

        67

    • Time Table and Settings for Program Sequence PME71.901

      68

    • Lme71.000

      69

    • Parameter List PME71.901

      70

  • 13 Pme72.521

    75

    • Program Sequence PME72.521

      75

    • Connection Diagrams for Fuel Train Applications (Examples)

      77

    • Gas Direct Ignition (G), 1-Stage

      77

    • Gas Direct Ignition 1 (Gp1/1), 2-Stage

      77

    • Connection Diagram for LME72.000

      78

    • Connection Diagram for LME72.000

      79

    • Time Table and Settings for Program Sequence PME72.521

      80

    • Lme72.000

      81

    • Parameter List PME72.521

      82

  • 14 Pme72.541

    84

    • Program Sequence PME72.541

      84

    • Connection Diagrams for Fuel Train Applications (Examples)

      86

    • Gas Direct Ignition (G), 1-Stage

      86

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      86

    • Connection Diagram for LME72.000

      87

    • Connection Diagram for LME72.000

      88

    • Time Table and Settings for Program Sequence PME72.541

      89

    • Lme72.000

      90

    • Parameter List PME72.541

      91

  • 15 Pme73.810

    93

    • Program Sequence PME73.810

      93

    • Connection Diagrams for Fuel Train Applications (Examples)

      95

    • Gas Direct Ignition (G), 1-Stage

      95

    • Gas Direct Ignition (G), 2-Stage

      95

    • Gas Direct Ignition (G), 1-Stage, with Valve Proving

      96

    • Gas Direct Ignition (G), 2-Stage, with Valve Proving

      96

    • Gas Valve Proving

      97

      • Valve Proving with Separate Pressure Switch

        97

      • Valve Proving — Calculation of Leakage Rate

        98

    • Connection Diagram for LME73.000

      99

    • Time Table and Settings for Program Sequence PME73.810

      100

    • Lme73.000

      101

    • Parameter List PME73.810

      102

  • 16 Pme73.820

    105

    • Program Sequence PME73.820

      105

    • Connection Diagrams for Fuel Train Applications (Examples)

      107

    • Gas Direct Ignition (G), 1-Stage

      107

    • Gas Direct Ignition 1 (G), 2-Stage

      107

    • Gas Direct Ignition 1 (G), 1-Stage, with Valve Proving

      108

    • Gas Direct Ignition (G), 2-Stage, with Valve Proving

      108

    • Gas Valve Proving

      109

      • Valve Proving with Separate Pressure Switch

        109

      • Valve Proving — Calculation of Leakage Rate

        110

    • Connection Diagram for LME73.000

      111

    • Connection Diagram for LME73.000

      112

    • Time Tables and Settings for Program Sequence PME73.820

      113

    • Lme73.000

      114

    • Parameter List PME73.820

      115

  • 17 Pme73.830

    118

    • Program Sequence PME73.830

      118

    • Connection Diagrams for Fuel Train Applications (Examples)

      120

    • Gas Direct Ignition (G), 1-Stage

      120

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      120

    • Gas Pilot Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      121

    • Gas Direct Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      121

    • Gas Valve Proving

      122

      • Valve Proving with Separate Pressure Switch

        122

      • Valve Proving — Calculation of Leakage Rate

        123

    • Connection Diagram for LME73.000

      124

    • Time Table and Settings for Program Sequence PME73.830

      125

    • Lme73.000

      126

    • Parameter List PME73.830

      127

  • 18 Pme73.831

    130

    • Program Sequence PME73.831

      130

    • Connection Diagrams for Fuel Applications (Examples)

      135

    • Gas Direct Ignition (G), 1-Stage, Without Valve Proving

      135

    • Gas Pilot Ignition 2 (Gp2), 1-Stage, Without Valve Proving, Simultaneously Ignition Burner

      135

    • Gas Pilot Ignition 1 (Gp1), 1-Stage, with Valve Proving, Alternate Burning Ignition Burner

      136

    • Gas Direct Ignition 1 (G), 1-Stage, with Valve Proving

      136

    • Valve Proving of Gas Valves

      137

      • Valve Proving with Separate Pressure Switch

        137

      • Valve Proving — Calculation of Leakage Rate

        138

    • Connection Diagram for LME73.000

      139

    • Connection Diagram for LME73.000

      140

    • Time Table and Settings for Program Sequence PME73.831

      141

    • Lme73.000

      143

    • Parameter List PME73.831

      144

  • 19 Pme73.840

    148

    • Program Sequence PME73.840

      148

    • Connection Diagrams for Fuel Train Applications (Examples)

      150

    • Gas Direct Ignition (G), 1-Stage

      150

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      150

    • Gas Pilot Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      151

    • Gas Direct Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      151

    • Gas Valve Proving

      152

      • Valve Proving with Separate Pressure Switch

        152

      • Valve Proving — Calculation of Leakage Rate

        153

    • Connection Diagram for LME73.000

      154

    • Connection Diagram for LME73.000

      155

    • Time Table and Settings for Program Sequence PME73.840

      156

    • Lme73.000

      157

    • Parameter List PME73.840

      158

  • 20 Legend

    161

  • 21 Multistage or Modulating Mode

    163

    • Relevant Parameters

      163

    • Connection Diagram for Feedback Potentiometer ASZ12.33

      163

    • Connection Diagram for Load Controller

      164

    • Actuators

      164

    • Function

      164

    • Load Controller Inputs

      165

    • 3-Position Step Input X5-03

      165

    • Analog Input X65

      165

    • Selection Source Preset Output Analog/3-Position Step Input (P654)

      165

    • Actuator Output X2-09

      165

    • Setting the Maximum Running Time of the Actuator (P259/P260 Timeout)

      165

    • Multistage/Modulating Mode Via 3-Position Step Input X5-03

      166

    • Maximum Possible Resolution

      166

    • Modulating Mode Via Analog Input Signal X65

      166

    • Standardization of Modulation Range

      166

    • Setting the Minimum Power Control Step (Dead Band) (P123) in Modulating Mode Via Analog Input Signal X65

      167

  • 22 Safety Notes Relating to Operation of AZL2

    168

    • Building Technologies Division Basic Documentation LME7

      169

  • 23 Operation Via AZL2

    169

    • Description of the Unit/Display and Buttons

      169

    • Meaning of Symbols on the Display

      170

    • Special Functions

      170

    • Manual Lockout

      170

    • Operation

      171

    • Normal Display

      171

    • Display in Standby Mode

      171

    • Display During Startup/Shutdown

      171

      • Display of Program Phases

        171

      • List of Phase Display (Display Depending on Program)

        172

    • Display of Operating Position

      173

    • Fault Status Messages, Display of Errors and Info

      174

      • Display of Errors (Faults) with Lockout

        174

      • Reset

        174

    • Menu-Driven Operation

      175

    • Assignment of Levels

      175

    • Info Level

      176

    • Display of Info Level

      177

    • Display of Info Values

      177

    • Identification Date

      177

    • Identification Number

      177

    • Identification of Burner

      178

    • Number of Startups Resettable

      179

    • Total Number of Startups

      180

    • End of Info Level

      180

    • Service Level

      181

    • Display of the Service Level

      181

    • Display of Service Values

      182

    • Error History

      182

    • Mains Voltage

      182

    • Intensity of Flame

      182

    • End of Service Level

      182

    • Parameter Level

      183

    • Entering the Password

      184

    • Changing the Heating Engineer’s Password

      186

    • Changing the Oem’s Password

      187

    • Backup

      188

    • Restore

      190

    • Operating Variants of the Parameters

      192

    • Parameters Without Index, with Direct Display

      192

    • Example of Parameter 225 (Prepurge Time) on the Parameter Level

      192

    • Parameters Without Index, with no Direct Display

      194

    • Example of Parameter 224 (Specified Time Air Pressure Switch) on the Parameter Level

      194

    • Parameters with Index, with or Without Direct Display

      196

    • Example of Parameter 701: Actual Error on the Service Level

      196

  • 24 Error Code List with Operation Via External AZL2

    199

  • 25 Operation Via Internal LED

    201

    • Description of Display and Buttons

      201

    • Normal Display

      202

    • Display in Standby Mode

      202

    • Display During Startup/Shutdown

      202

    • Display of Program Phases

      202

    • List of Phase Display

      203

    • Display of Operating Position

      205

    • Special Functions

      205

    • Manual Lockout

      205

    • Fault Status Messages, Display of Errors

      206

    • Display of Errors (Faults) with Lockout

      206

    • Display of Flame Current ION or QRA

      207

    • Reset

      207

    • Display of Flame Current QRB

      208

    • Display of Preset Output

      209

    • Manual Adjustment (Depending on Program Module)

      210

    • Position of Actuator or Speed of PWM Fan in Modulating Operation with Analog Signal

      210

    • First Startup with a New Program Module or in Case of Replacement of Program Module

      213

    • Manual Backup

      215

    • Error During Backup Process

      216

    • Manual Restore

      217

    • Errors During the Restore Process

      218

    • Reset

      218

  • 26 Error Code List with Operation Via Internal LED

    219

  • 27 PWM Settings

    221

    • Relevant Parameters

      221

    • PWM Control Parameters

      223

    • PWM Safety Parameters

      224

    • Initial PWM Parameter Settings

      225

    • Initial Settings of PWM Basic Parameters

      225

      • Prerequisites

        225

      • Operating Steps

        225

    • Reading the Value of Parameter 920 in the Prepurge Phase (P30) and Ignition Load Phase (P38, P40 and P44)

      228

      • Procedure

        228

    • Final Settings of PWM Safety Parameters

      229

      • Procedure

        229

      • Follow These Steps

        229

      • Checking Prepurging

        230

      • Checking the Ignition Load

        230

    • Setting Safety Parameters 675.00/675.01 and Checking the Safety Settings under Worst-Case Conditions

      231

      • Procedure

        231

      • Follow These Steps

        231

      • Checking Prepurging

        231

      • Checking the Ignition Load

        232

    • Matching the Working Points «Speeds for Low-Fire (P1), Ignition Load (P0) and High-Fire (P2) for the Heating Engineer to the Application

      232

      • Prerequisites

        232

    • Via the Onboard Operating Panel of the LME7

      233

    • Via the AZL2

      234

    • Overview of PWM Fan Parameters (Value Range Refers to PME71.901)

      236

  • 28 List of Figures

    242

Advertisement

Siemens LME73.000A2 Basic Documentation

Siemens LME73.000A2 Basic Documentation (116 pages)

Burner control

Brand: Siemens
|
Category: Safety Equipment
|
Size: 2.94 MB

Table of Contents
  • Table of Contents

    3

  • 1 Safety Notes

    8

    • Warning Notes

      8

    • Mounting Notes

      9

    • Installation Notes

      10

    • Electrical Connection of Flame Detectors

      11

    • Commissioning Notes

      12

    • Standards and Certificates

      13

    • Lifetime

      14

    • Disposal Notes

      14

    • Typographical Conventions

      15

    • Safety Notes

      15

    • Qualified Personnel

      15

    • Correct Use

      15

  • 2 System Makeup / Function Description

    16

    • Features

      17

  • 3 Type Summary

    18

    • Burner Controls

      18

    • Program Module

      19

    • PME7 with Mains Voltage AC 120 V

      19

    • PME7 with Mains Voltage AC 230 V

      21

    • External Display and Operating Units

      23

    • Flame Detectors

      24

    • Actuators

      25

    • Pressure Switch

      25

    • Dummy Plugs for RJ11

      25

    • Connector Sets for LME7

      26

    • Service- Tools

      27

  • 4 Technical Data

    28

    • Basic Unit LME7

      28

    • Terminal Rating Inputs

      29

    • Terminal Rating Outputs

      30

    • Cable Lengths

      32

    • Actuators

      33

    • Cross-Sectional Areas

      33

    • RAST5 Connector

      34

    • RAST3.5 Connector

      34

    • Signal Cable AGV50

      34

    • Azl2  Bci

      34

    • Dummy Plug for RJ11

      34

    • Environmental Conditions

      35

    • Flame Supervision

      36

    • Ionization Probe

      36

    • QRA2 / QRA4 / QRA10 (LME71 / LME73 Only)

      38

    • Qrb1/Qrb3/ Qrb4

      39

    • Qrc

      41

  • 5 Dimensions

    42

  • 6 Function

    43

    • Preconditions for Burner Startup

      43

    • Undervoltage

      43

    • Controlled Intermittent Operation

      43

    • Control Sequence in the Event of Fault

      44

    • Resetting the LME7

      44

    • Restart Limitation

      45

    • Restart in the Event of Loss of Flame

      45

    • Repetition in Case of no Flame Is Established by the End of Safety Time (TSA)

      45

  • 7 Operation, Indication, Diagnostics

    46

    • Operation

      46

    • Indication of Operating State

      46

    • Diagnostics of Cause of Fault

      47

  • 8 Inputs / Outputs

    49

  • 9 Connection Diagram AGG9 Connector

    50

    • Lme71

      50

    • Lme72

      51

    • Lme73

      52

  • 10 LME7 Burner Control

    53

    • Description of Inputs and Outputs

      53

    • Digital Input

      54

    • Safety Loop Terminal X3-04 Pin 1 and 2

      54

    • Input for External Controller (ON/OFF) Terminal X5-03 Pin 1

      54

    • Air Pressure Switch Terminal X3-02

      55

    • Input Gas Pressure Switch-Min

      55

  • 11 Multistage or Modulating Mode with Actuator

    56

    • Relevant Parameters

      56

    • Connection Diagram for Feedback Potentiometer ASZ12.33

      56

    • Connection Diagram for Load Controller (LME71/LME73 Only)

      57

    • Actuators

      57

    • Function

      57

    • Load Controller Inputs

      58

    • 3-Position Step Input Terminal X5-03

      58

    • Analog Input Terminal X65 (LME71/LME73 Only)

      58

    • Selection Source Preset Output Analog / 3-Position Step Input (Parameter 654) (LME71/LME73 Only)

      58

    • Actuator Output Terminal X2-09

      58

    • Setting the Maximum Running Time of the Actuator (Parameter 259 / 260 Timeout)

      58

    • Multistage / Modulating Mode Via 3-Position Step Input Terminal X5-03

      59

    • Maximum Possible Resolution

      59

    • Modulating Mode Via Analog Input Signal Terminal X65 (LME71/LME73 Only)

      59

    • Standardization of Modulation Range

      59

    • Setting the Minimum Power Control Step (Dead Band) (Parameter 123)

      60

      • (LME71/LME73 Only)

        60

      • User Limitations / Application Examples

        61

  • 12 Safety Notes Relating to Operation of AZL2

    62

  • 13 Operation Via AZL2

    63

    • Description of the Unit / Display and Buttons

      63

    • Meaning of Symbols on the Display

      64

    • Special Functions

      64

    • Manual Lockout

      64

    • Operation

      65

    • Normal Display

      65

    • Display in Standby Mode

      65

    • Display During Startup / Shutdown

      65

      • Display of Program Phases

        65

      • List of Phase Display (Display Depending on Program)

        66

    • Display of Operating Position

      67

    • Fault Status Messages, Display of Errors and Info

      68

      • Display of Errors (Faults) with Lockout

        68

      • Reset

        68

    • Menu-Driven Operation

      69

    • Assignment of Levels

      69

    • Info Level

      70

    • Display of Info Level

      70

    • Display of Info Values

      71

    • Identification Date

      71

    • Identification Number

      71

    • Identification of Burner

      72

    • Number of Startups Resettable

      73

    • Total Number of Startups

      74

    • End of Info Level

      74

    • Service Level

      75

    • Display of the Service Level

      75

    • Display of Service Values

      76

    • Error History

      76

    • Mains Voltage

      76

    • Intensity of Flame

      76

    • End of Service Level

      76

    • Parameter Level

      77

    • Entering the Password

      78

    • Changing the Heating Engineer’s Password

      80

    • Changing the Oem’s Password

      82

    • Backup

      83

    • Restore

      85

    • Operating Variants of the Parameters

      87

    • Parameters Without Index, with Direct Display

      87

    • Example of Parameter 225 (Prepurge Time) on the Parameter Level

      87

    • Parameters Without Index, with no Direct Display

      89

    • Example of Parameter 224 (Specified Time Air Pressure Switch) on the Parameter Level

      89

    • Parameters with Index, with or Without Direct Display

      91

    • Example of Parameter 701: Actual Error on the Service Level

      91

  • 14 Error Code List with Operation Via External AZL2 Display

    94

  • 15 Operation Via Internal LED

    96

    • Description of Display and Buttons

      96

    • Normal Display

      97

    • Display in Standby Mode

      97

    • Display During Startup / Shutdown

      97

    • Display of Program Phases

      97

    • List of Phase Display

      98

    • Display of Operating Position

      100

    • Special Functions

      100

    • Manual Lockout

      100

    • Fault Status Messages, Display of Errors

      101

    • Display of Errors (Faults) with Lockout

      101

    • Display of Flame Current ION or QRA

      102

    • Reset

      102

    • Display of Preset Output

      103

    • Manual Adjustment (Depending on the PME7)

      104

    • Position of Actuator or Speed of PWM Fan in Modulating Operation with Analog Signal

      104

    • Initial Startup with a New PME7 or in Case of Replacement of the PME7

      107

    • Manual Backup

      109

    • Error During Backup Process

      110

    • Manual Restore

      111

    • Errors During the Restore Process

      112

    • Reset

      112

  • 16 List of Figures

    116

Advertisement

Related Products

  • Siemens LME73

  • Siemens LME73.000A1

  • Siemens LME7 Series

  • Siemens LME75

  • Siemens LME71

  • Siemens LME71.000A1

  • Siemens LME71.000A2

  • Siemens LME72.000A2

  • Siemens LME41.071A2

  • Siemens LME39.400C1

Siemens Categories

Controller

Control Unit

Industrial Equipment

Washer
Washer

Switch
Switch

More Siemens Manuals

  1. Manuals
  2. Brands
  3. Siemens Manuals
  4. Controller
  5. LME73.000A2

Manuals and User Guides for Siemens LME73.000A2. We have 2 Siemens LME73.000A2 manuals available for free PDF download: Basic Documentation

Siemens LME73.000A2 Basic Documentation

Siemens LME73.000A2 Basic Documentation (245 pages)

Burner Control

Brand: Siemens
|
Category: Controller
|
Size: 4.99 MB

Table of Contents
  • Table of Contents

    5

  • 1 Safety Notes

    13

    • Warning Notes

      13

    • Mounting Notes

      15

    • Installation Notes

      16

    • Electrical Connection of Flame Detectors

      17

    • Commissioning Notes

      18

    • Standards and Certificates

      19

    • Lifetime

      19

    • Disposal Notes

      19

    • Typographical Conventions

      20

    • Safety Notes

      20

  • 2 System Makeup/Function Description

    21

    • Features

      22

  • 3 Type Summary

    23

    • Burner Controls

      23

    • Program Module

      24

    • External Display and Operating Units

      26

    • Flame Detectors

      26

    • Actuators

      27

    • Pressure Switch

      27

    • Dummy Plugs for RJ11

      28

    • Connector Sets for LME7

      28

    • Service- Tools

      28

    • Test Case and Accessories

      29

  • 4 Technical Data

    30

    • Basic Unit LME7

      30

    • Terminal Rating Inputs

      30

    • Terminal Rating Outputs

      31

    • Cable Lengths

      32

    • Actuators

      32

    • Cross-Sectional Areas

      32

    • Signal Cable AGV50

      33

    • Azl2

      33

    • Dummy Plug for RJ11

      33

    • Environmental Conditions

      33

    • Flame Supervision

      34

    • Ionization Probe

      34

    • Flame Detector QRA2

      36

  • 5 Dimensions

    37

  • 6 Function

    38

    • Preconditions for Burner Startup

      38

    • Undervoltage

      38

    • Controlled Intermittent Operation

      38

    • Control Sequence in the Event of Fault

      39

    • Resetting the Burner Control

      39

    • Limitation of Repetitions (Can be Parameterized)

      40

      • Parameter 240)

        40

    • Parameter 240/240.00

      40

    • Parameter 240.01

      40

  • 7 Operation, Indication, Diagnostics

    41

    • Operation

      41

    • Indication of Operating State

      41

    • Diagnostics of Cause of Fault

      42

  • 8 Inputs/Outputs

    44

  • 9 Basic Unit

    45

    • Description of Inputs and Outputs

      45

    • Digital Input

      46

    • Safety Loop X3-04, Terminal 1 and 2

      46

    • Input for External Controller (ON/OFF) X5-03, Terminal 1

      46

    • Air Pressure Switch X3-02

      47

  • 10 Pme71.401

    48

    • Program Sequence PME71.401

      48

    • Connection Diagrams for Fuel Train Applications (Examples)

      50

    • Gas Direct Ignition (G), 1-Stage

      50

    • Gas Direct Ignition (G), 2-Stage

      50

    • Time Table and Settings for Program Sequence PME71.401

      51

    • Lme71.000

      52

    • Parameter List PME71.401

      53

  • 11 Pme71.402

    55

    • Program Sequence PME71.402

      55

    • Connection Diagrams for Fuel Train Applications (Examples)

      57

    • Gas Direct Ignition (G), 1-Stage

      57

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      57

    • Time Table and Settings for Program Sequence PME71.402

      58

    • Lme71.000

      59

    • Parameter List PME71.402

      60

  • 12 Pme71.901

    63

    • Program Sequence PME71.901

      63

    • Connection Diagrams for Fuel Train Applications (Examples)

      65

    • Gas Direct Ignition (G), 1-Stage

      65

    • Gas Direct Ignition (G), 1-Stage and Valve Proving

      65

    • Gas Valve Proving

      66

      • Valve Proving with Separate Pressure Switch

        66

      • Valve Proving — Calculation of Leakage Rate

        67

    • Time Table and Settings for Program Sequence PME71.901

      68

    • Lme71.000

      69

    • Parameter List PME71.901

      70

  • 13 Pme72.521

    75

    • Program Sequence PME72.521

      75

    • Connection Diagrams for Fuel Train Applications (Examples)

      77

    • Gas Direct Ignition (G), 1-Stage

      77

    • Gas Direct Ignition 1 (Gp1/1), 2-Stage

      77

    • Connection Diagram for LME72.000

      78

    • Connection Diagram for LME72.000

      79

    • Time Table and Settings for Program Sequence PME72.521

      80

    • Lme72.000

      81

    • Parameter List PME72.521

      82

  • 14 Pme72.541

    84

    • Program Sequence PME72.541

      84

    • Connection Diagrams for Fuel Train Applications (Examples)

      86

    • Gas Direct Ignition (G), 1-Stage

      86

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      86

    • Connection Diagram for LME72.000

      87

    • Connection Diagram for LME72.000

      88

    • Time Table and Settings for Program Sequence PME72.541

      89

    • Lme72.000

      90

    • Parameter List PME72.541

      91

  • 15 Pme73.810

    93

    • Program Sequence PME73.810

      93

    • Connection Diagrams for Fuel Train Applications (Examples)

      95

    • Gas Direct Ignition (G), 1-Stage

      95

    • Gas Direct Ignition (G), 2-Stage

      95

    • Gas Direct Ignition (G), 1-Stage, with Valve Proving

      96

    • Gas Direct Ignition (G), 2-Stage, with Valve Proving

      96

    • Gas Valve Proving

      97

      • Valve Proving with Separate Pressure Switch

        97

      • Valve Proving — Calculation of Leakage Rate

        98

    • Connection Diagram for LME73.000

      99

    • Time Table and Settings for Program Sequence PME73.810

      100

    • Lme73.000

      101

    • Parameter List PME73.810

      102

  • 16 Pme73.820

    105

    • Program Sequence PME73.820

      105

    • Connection Diagrams for Fuel Train Applications (Examples)

      107

    • Gas Direct Ignition (G), 1-Stage

      107

    • Gas Direct Ignition 1 (G), 2-Stage

      107

    • Gas Direct Ignition 1 (G), 1-Stage, with Valve Proving

      108

    • Gas Direct Ignition (G), 2-Stage, with Valve Proving

      108

    • Gas Valve Proving

      109

      • Valve Proving with Separate Pressure Switch

        109

      • Valve Proving — Calculation of Leakage Rate

        110

    • Connection Diagram for LME73.000

      111

    • Connection Diagram for LME73.000

      112

    • Time Tables and Settings for Program Sequence PME73.820

      113

    • Lme73.000

      114

    • Parameter List PME73.820

      115

  • 17 Pme73.830

    118

    • Program Sequence PME73.830

      118

    • Connection Diagrams for Fuel Train Applications (Examples)

      120

    • Gas Direct Ignition (G), 1-Stage

      120

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      120

    • Gas Pilot Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      121

    • Gas Direct Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      121

    • Gas Valve Proving

      122

      • Valve Proving with Separate Pressure Switch

        122

      • Valve Proving — Calculation of Leakage Rate

        123

    • Connection Diagram for LME73.000

      124

    • Time Table and Settings for Program Sequence PME73.830

      125

    • Lme73.000

      126

    • Parameter List PME73.830

      127

  • 18 Pme73.831

    130

    • Program Sequence PME73.831

      130

    • Connection Diagrams for Fuel Applications (Examples)

      135

    • Gas Direct Ignition (G), 1-Stage, Without Valve Proving

      135

    • Gas Pilot Ignition 2 (Gp2), 1-Stage, Without Valve Proving, Simultaneously Ignition Burner

      135

    • Gas Pilot Ignition 1 (Gp1), 1-Stage, with Valve Proving, Alternate Burning Ignition Burner

      136

    • Gas Direct Ignition 1 (G), 1-Stage, with Valve Proving

      136

    • Valve Proving of Gas Valves

      137

      • Valve Proving with Separate Pressure Switch

        137

      • Valve Proving — Calculation of Leakage Rate

        138

    • Connection Diagram for LME73.000

      139

    • Connection Diagram for LME73.000

      140

    • Time Table and Settings for Program Sequence PME73.831

      141

    • Lme73.000

      143

    • Parameter List PME73.831

      144

  • 19 Pme73.840

    148

    • Program Sequence PME73.840

      148

    • Connection Diagrams for Fuel Train Applications (Examples)

      150

    • Gas Direct Ignition (G), 1-Stage

      150

    • Gas Pilot Ignition 1 (Gp1/1), 1-Stage

      150

    • Gas Pilot Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      151

    • Gas Direct Ignition 1 (Gp1/2), 1-Stage, with Valve Proving

      151

    • Gas Valve Proving

      152

      • Valve Proving with Separate Pressure Switch

        152

      • Valve Proving — Calculation of Leakage Rate

        153

    • Connection Diagram for LME73.000

      154

    • Connection Diagram for LME73.000

      155

    • Time Table and Settings for Program Sequence PME73.840

      156

    • Lme73.000

      157

    • Parameter List PME73.840

      158

  • 20 Legend

    161

  • 21 Multistage or Modulating Mode

    163

    • Relevant Parameters

      163

    • Connection Diagram for Feedback Potentiometer ASZ12.33

      163

    • Connection Diagram for Load Controller

      164

    • Actuators

      164

    • Function

      164

    • Load Controller Inputs

      165

    • 3-Position Step Input X5-03

      165

    • Analog Input X65

      165

    • Selection Source Preset Output Analog/3-Position Step Input (P654)

      165

    • Actuator Output X2-09

      165

    • Setting the Maximum Running Time of the Actuator (P259/P260 Timeout)

      165

    • Multistage/Modulating Mode Via 3-Position Step Input X5-03

      166

    • Maximum Possible Resolution

      166

    • Modulating Mode Via Analog Input Signal X65

      166

    • Standardization of Modulation Range

      166

    • Setting the Minimum Power Control Step (Dead Band) (P123) in Modulating Mode Via Analog Input Signal X65

      167

  • 22 Safety Notes Relating to Operation of AZL2

    168

    • Building Technologies Division Basic Documentation LME7

      169

  • 23 Operation Via AZL2

    169

    • Description of the Unit/Display and Buttons

      169

    • Meaning of Symbols on the Display

      170

    • Special Functions

      170

    • Manual Lockout

      170

    • Operation

      171

    • Normal Display

      171

    • Display in Standby Mode

      171

    • Display During Startup/Shutdown

      171

      • Display of Program Phases

        171

      • List of Phase Display (Display Depending on Program)

        172

    • Display of Operating Position

      173

    • Fault Status Messages, Display of Errors and Info

      174

      • Display of Errors (Faults) with Lockout

        174

      • Reset

        174

    • Menu-Driven Operation

      175

    • Assignment of Levels

      175

    • Info Level

      176

    • Display of Info Level

      177

    • Display of Info Values

      177

    • Identification Date

      177

    • Identification Number

      177

    • Identification of Burner

      178

    • Number of Startups Resettable

      179

    • Total Number of Startups

      180

    • End of Info Level

      180

    • Service Level

      181

    • Display of the Service Level

      181

    • Display of Service Values

      182

    • Error History

      182

    • Mains Voltage

      182

    • Intensity of Flame

      182

    • End of Service Level

      182

    • Parameter Level

      183

    • Entering the Password

      184

    • Changing the Heating Engineer’s Password

      186

    • Changing the Oem’s Password

      187

    • Backup

      188

    • Restore

      190

    • Operating Variants of the Parameters

      192

    • Parameters Without Index, with Direct Display

      192

    • Example of Parameter 225 (Prepurge Time) on the Parameter Level

      192

    • Parameters Without Index, with no Direct Display

      194

    • Example of Parameter 224 (Specified Time Air Pressure Switch) on the Parameter Level

      194

    • Parameters with Index, with or Without Direct Display

      196

    • Example of Parameter 701: Actual Error on the Service Level

      196

  • 24 Error Code List with Operation Via External AZL2

    199

  • 25 Operation Via Internal LED

    201

    • Description of Display and Buttons

      201

    • Normal Display

      202

    • Display in Standby Mode

      202

    • Display During Startup/Shutdown

      202

    • Display of Program Phases

      202

    • List of Phase Display

      203

    • Display of Operating Position

      205

    • Special Functions

      205

    • Manual Lockout

      205

    • Fault Status Messages, Display of Errors

      206

    • Display of Errors (Faults) with Lockout

      206

    • Display of Flame Current ION or QRA

      207

    • Reset

      207

    • Display of Flame Current QRB

      208

    • Display of Preset Output

      209

    • Manual Adjustment (Depending on Program Module)

      210

    • Position of Actuator or Speed of PWM Fan in Modulating Operation with Analog Signal

      210

    • First Startup with a New Program Module or in Case of Replacement of Program Module

      213

    • Manual Backup

      215

    • Error During Backup Process

      216

    • Manual Restore

      217

    • Errors During the Restore Process

      218

    • Reset

      218

  • 26 Error Code List with Operation Via Internal LED

    219

  • 27 PWM Settings

    221

    • Relevant Parameters

      221

    • PWM Control Parameters

      223

    • PWM Safety Parameters

      224

    • Initial PWM Parameter Settings

      225

    • Initial Settings of PWM Basic Parameters

      225

      • Prerequisites

        225

      • Operating Steps

        225

    • Reading the Value of Parameter 920 in the Prepurge Phase (P30) and Ignition Load Phase (P38, P40 and P44)

      228

      • Procedure

        228

    • Final Settings of PWM Safety Parameters

      229

      • Procedure

        229

      • Follow These Steps

        229

      • Checking Prepurging

        230

      • Checking the Ignition Load

        230

    • Setting Safety Parameters 675.00/675.01 and Checking the Safety Settings under Worst-Case Conditions

      231

      • Procedure

        231

      • Follow These Steps

        231

      • Checking Prepurging

        231

      • Checking the Ignition Load

        232

    • Matching the Working Points «Speeds for Low-Fire (P1), Ignition Load (P0) and High-Fire (P2) for the Heating Engineer to the Application

      232

      • Prerequisites

        232

    • Via the Onboard Operating Panel of the LME7

      233

    • Via the AZL2

      234

    • Overview of PWM Fan Parameters (Value Range Refers to PME71.901)

      236

  • 28 List of Figures

    242

Advertisement

Siemens LME73.000A2 Basic Documentation

Siemens LME73.000A2 Basic Documentation (116 pages)

Burner control

Brand: Siemens
|
Category: Safety Equipment
|
Size: 2.94 MB

Table of Contents
  • Table of Contents

    3

  • 1 Safety Notes

    8

    • Warning Notes

      8

    • Mounting Notes

      9

    • Installation Notes

      10

    • Electrical Connection of Flame Detectors

      11

    • Commissioning Notes

      12

    • Standards and Certificates

      13

    • Lifetime

      14

    • Disposal Notes

      14

    • Typographical Conventions

      15

    • Safety Notes

      15

    • Qualified Personnel

      15

    • Correct Use

      15

  • 2 System Makeup / Function Description

    16

    • Features

      17

  • 3 Type Summary

    18

    • Burner Controls

      18

    • Program Module

      19

    • PME7 with Mains Voltage AC 120 V

      19

    • PME7 with Mains Voltage AC 230 V

      21

    • External Display and Operating Units

      23

    • Flame Detectors

      24

    • Actuators

      25

    • Pressure Switch

      25

    • Dummy Plugs for RJ11

      25

    • Connector Sets for LME7

      26

    • Service- Tools

      27

  • 4 Technical Data

    28

    • Basic Unit LME7

      28

    • Terminal Rating Inputs

      29

    • Terminal Rating Outputs

      30

    • Cable Lengths

      32

    • Actuators

      33

    • Cross-Sectional Areas

      33

    • RAST5 Connector

      34

    • RAST3.5 Connector

      34

    • Signal Cable AGV50

      34

    • Azl2  Bci

      34

    • Dummy Plug for RJ11

      34

    • Environmental Conditions

      35

    • Flame Supervision

      36

    • Ionization Probe

      36

    • QRA2 / QRA4 / QRA10 (LME71 / LME73 Only)

      38

    • Qrb1/Qrb3/ Qrb4

      39

    • Qrc

      41

  • 5 Dimensions

    42

  • 6 Function

    43

    • Preconditions for Burner Startup

      43

    • Undervoltage

      43

    • Controlled Intermittent Operation

      43

    • Control Sequence in the Event of Fault

      44

    • Resetting the LME7

      44

    • Restart Limitation

      45

    • Restart in the Event of Loss of Flame

      45

    • Repetition in Case of no Flame Is Established by the End of Safety Time (TSA)

      45

  • 7 Operation, Indication, Diagnostics

    46

    • Operation

      46

    • Indication of Operating State

      46

    • Diagnostics of Cause of Fault

      47

  • 8 Inputs / Outputs

    49

  • 9 Connection Diagram AGG9 Connector

    50

    • Lme71

      50

    • Lme72

      51

    • Lme73

      52

  • 10 LME7 Burner Control

    53

    • Description of Inputs and Outputs

      53

    • Digital Input

      54

    • Safety Loop Terminal X3-04 Pin 1 and 2

      54

    • Input for External Controller (ON/OFF) Terminal X5-03 Pin 1

      54

    • Air Pressure Switch Terminal X3-02

      55

    • Input Gas Pressure Switch-Min

      55

  • 11 Multistage or Modulating Mode with Actuator

    56

    • Relevant Parameters

      56

    • Connection Diagram for Feedback Potentiometer ASZ12.33

      56

    • Connection Diagram for Load Controller (LME71/LME73 Only)

      57

    • Actuators

      57

    • Function

      57

    • Load Controller Inputs

      58

    • 3-Position Step Input Terminal X5-03

      58

    • Analog Input Terminal X65 (LME71/LME73 Only)

      58

    • Selection Source Preset Output Analog / 3-Position Step Input (Parameter 654) (LME71/LME73 Only)

      58

    • Actuator Output Terminal X2-09

      58

    • Setting the Maximum Running Time of the Actuator (Parameter 259 / 260 Timeout)

      58

    • Multistage / Modulating Mode Via 3-Position Step Input Terminal X5-03

      59

    • Maximum Possible Resolution

      59

    • Modulating Mode Via Analog Input Signal Terminal X65 (LME71/LME73 Only)

      59

    • Standardization of Modulation Range

      59

    • Setting the Minimum Power Control Step (Dead Band) (Parameter 123)

      60

      • (LME71/LME73 Only)

        60

      • User Limitations / Application Examples

        61

  • 12 Safety Notes Relating to Operation of AZL2

    62

  • 13 Operation Via AZL2

    63

    • Description of the Unit / Display and Buttons

      63

    • Meaning of Symbols on the Display

      64

    • Special Functions

      64

    • Manual Lockout

      64

    • Operation

      65

    • Normal Display

      65

    • Display in Standby Mode

      65

    • Display During Startup / Shutdown

      65

      • Display of Program Phases

        65

      • List of Phase Display (Display Depending on Program)

        66

    • Display of Operating Position

      67

    • Fault Status Messages, Display of Errors and Info

      68

      • Display of Errors (Faults) with Lockout

        68

      • Reset

        68

    • Menu-Driven Operation

      69

    • Assignment of Levels

      69

    • Info Level

      70

    • Display of Info Level

      70

    • Display of Info Values

      71

    • Identification Date

      71

    • Identification Number

      71

    • Identification of Burner

      72

    • Number of Startups Resettable

      73

    • Total Number of Startups

      74

    • End of Info Level

      74

    • Service Level

      75

    • Display of the Service Level

      75

    • Display of Service Values

      76

    • Error History

      76

    • Mains Voltage

      76

    • Intensity of Flame

      76

    • End of Service Level

      76

    • Parameter Level

      77

    • Entering the Password

      78

    • Changing the Heating Engineer’s Password

      80

    • Changing the Oem’s Password

      82

    • Backup

      83

    • Restore

      85

    • Operating Variants of the Parameters

      87

    • Parameters Without Index, with Direct Display

      87

    • Example of Parameter 225 (Prepurge Time) on the Parameter Level

      87

    • Parameters Without Index, with no Direct Display

      89

    • Example of Parameter 224 (Specified Time Air Pressure Switch) on the Parameter Level

      89

    • Parameters with Index, with or Without Direct Display

      91

    • Example of Parameter 701: Actual Error on the Service Level

      91

  • 14 Error Code List with Operation Via External AZL2 Display

    94

  • 15 Operation Via Internal LED

    96

    • Description of Display and Buttons

      96

    • Normal Display

      97

    • Display in Standby Mode

      97

    • Display During Startup / Shutdown

      97

    • Display of Program Phases

      97

    • List of Phase Display

      98

    • Display of Operating Position

      100

    • Special Functions

      100

    • Manual Lockout

      100

    • Fault Status Messages, Display of Errors

      101

    • Display of Errors (Faults) with Lockout

      101

    • Display of Flame Current ION or QRA

      102

    • Reset

      102

    • Display of Preset Output

      103

    • Manual Adjustment (Depending on the PME7)

      104

    • Position of Actuator or Speed of PWM Fan in Modulating Operation with Analog Signal

      104

    • Initial Startup with a New PME7 or in Case of Replacement of the PME7

      107

    • Manual Backup

      109

    • Error During Backup Process

      110

    • Manual Restore

      111

    • Errors During the Restore Process

      112

    • Reset

      112

  • 16 List of Figures

    116

Advertisement

Related Products

  • Siemens LME73

  • Siemens LME73.000A1

  • Siemens LME7 Series

  • Siemens LME75

  • Siemens LME71

  • Siemens LME71.000A1

  • Siemens LME71.000A2

  • Siemens LME72.000A2

  • Siemens LME41.071A2

  • Siemens LME39.400C1

Siemens Categories

Controller

Control Unit

Industrial Equipment

Washer
Washer

Switch
Switch

More Siemens Manuals

Понравилась статья? Поделить с друзьями:
  • Sim error 203f
  • Setupui dll autocad ошибка
  • Siemens iq700 сушильная машина ошибки
  • Setuptools install error
  • Sim error 201f