Twincat error 4120

I've got problem with TwinCAT3 (Win10 64bit) when I try to active TC3. Error message is : Severity Code Description Project File Line Suppression State Error 19-Jan-19 11:42:34 AM ...

I’ve got problem with TwinCAT3 (Win10 64bit) when I try to active TC3.

Error message is :

Severity Code Description Project File Line Suppression State Error
19-Jan-19 11:42:34 AM 545 ms | ‘TwinCAT System’ (10000): Sending ams
command >> Init4RTime: Start Interrupt: Ticker started >> AdsWarning:
4115 (0x1013, RTIME: system clock setup fails. Hint: On Windows8
system and above execute win8settick.bat in TwinCAT3.1System as
administrator and reboot.) << failed!

I also try to run «win8settick.bat» and reboot TC but it doesn’t work!

Is there any recommend to solve this ? Thanks a lot!

M Reza's user avatar

M Reza

17.6k14 gold badges66 silver badges71 bronze badges

asked Jan 19, 2019 at 4:54

talpham's user avatar

1

I have had the problem few times. In all those situations, the BIOS settings have been OK. Executing the .bat file didn’t help, until I ran it as an administrator and rebooted. Few times I have had to do it couple of times before it started working.

So try this

  1. Open start menu and search for «Command prompt»
  2. Right click it and select run as administrator
  3. Navigate to «C:TwinCAT3.1System» by writing «cd C:TwinCAT3.1System»
  4. Execute .bat by writing «win8settick.bat»
  5. Reboot — Repeat if not working

For me, this has always fixed the problem. If you have incorrect BIOS settings, you would get different error that states something about virtualization (as far as I know).

answered Jan 19, 2019 at 11:09

Quirzo's user avatar

QuirzoQuirzo

1,0518 silver badges9 bronze badges

3

I suspect you may have Hyper-V enabled. Because of the way that 64-bit TwinCAT interacts with the processor (using Intel VT-x), it doesn’t play well when hypervisors are running at the same time. Most hypervisors, like VMware, stop running when you close their window. However, Hyper-V (if enabled) is always running in the background so it must be disabled before using TwinCAT.

To Enable or Disable Hyper-V:

  1. Right click on the Windows button and select ‘Apps and Features’.
  2. Select Programs and Features on the right under related settings.
  3. Select Turn Windows Features on or off.
  4. Check or Uncheck Hyper-V and click OK.

Screenshot of Windows Features Window, arrow pointing to Hyper-V checkbox

source

answered Jan 22, 2019 at 5:57

Seth's user avatar

SethSeth

3381 silver badge9 bronze badges

In my case, installing TwinCAT 2 on top of an existing TwinCAT 3 installation was the problem.

According to Beckhoff, you need to «deactivate» TwinCAT 3 via «SwitchRuntime.exe» before installing TwinCAT 2, if installed in this order. In case of installing TwinCAT 3 on top of TwinCAT 2, you don’t need this step.

https://infosys.beckhoff.com/english.php?content=../content/1033/tc3_installation/179471755.html&id=

If forgot this, which probably destroyed parts of my TwinCAT 3 installation in the background.
Even tough I set the installation directory to a new folder «C:TwinCATTwinCAT_2» and not the default «C:TwinCAT«.
The installation process locked fine at first, only after trying to set a project into RUN while having TwinCAT 3 active as runtime, I got the above mentioned «AdsWarning: 4115».

Running «win8settick.bat» as admin and rebooting did not help, neither via explorer or command line.

Only re-installing TwinCAT3 did the trick for me.

answered Oct 22, 2021 at 11:33

Markus Wurm's user avatar

What worked for me was to disable the Virtual machine platform in Windows Features.

answered Oct 25, 2021 at 11:36

Yomi1984's user avatar

Yomi1984Yomi1984

1642 silver badges9 bronze badges

In addition to the other answers, you’ll get this error if you haven’t setup the real-time cores to match the computer you’re activating to:
enter image description here

answered Feb 16, 2022 at 22:35

Witman's user avatar

WitmanWitman

1,4582 gold badges14 silver badges18 bronze badges

I got the same issues. But I didn’t try any of the above methods.
bcz I am scared about warning ‘BitLocker trigger’ from a user above!

Then I changed the real-time system settings:

error :

Severity Code Description Project File Line Suppression State
Error 27/08/2022 16:40:58 279 ms | ‘TwinCAT System’ (10000): Sending ams command >> Init4RTime: Start Interrupt: Ticker started >> AdsError: 4115 (0x1013, RTIME: system clock setup fails.
Hint: On Windows8 system and above execute win8settick.bat in TwinCAT3.1System as administrator and reboot.) << failed!

settings: shared core 80%
old setting_shared core

new real-time setting: Isolated core 100 %
new setting _isolated core

No error:
enter image description here

I didn’t know the reason behind this!

answered Aug 27, 2022 at 14:48

ravi's user avatar

raviravi

214 bronze badges

3 ноября 2022

Бесплатная консультация специалиста

Инженер перезвонит
за 15 минут

Аккредитованный сервисный центр Эвотор

Удаленно устраняем ошибки на кассе

Терминал Сбербнка сообщает о неисправности с помощью кодов. Код ошибки 4120 говорит о том, что пин-пад не получил ключ KLK. Причин такой проблемы может быть много, и от причины зависит способ решения. Расскажем подробнее о том, что делать с такой неполадкой.

Поможем устранить ошибку на Эвотор

Бесплатная консультация специалиста8 (800) 700 50 85

whatsapp

whatsapp

Содержание

Ошибка 4120 на Эвотор

На Эвотор ошибка 4120 возникает на терминале Сбербанка. Код такой ошибки расшифровывается так: ПИН-пад не получил код KLK. Некоторые терминалы вместо кода показывают на экране этот текст. Ключ KLK — это транспортный криптографический ключ, который нужен для удаленной загрузки.

Причин появления такой проблемы несколько:

  • Неисправность пин-пада
  • Сбой в системе
  • Отсутствие подключения
  • Отсутствуют ключи

Чаще всего такая ошибка 4120 на пин-паде появляется сразу после подключения, так как сотрудник банка неверно настроил устройство. Иногда, такая проблема появляется во время работы. Если это ваш случай, то причина в неисправности пин-пада, поэтому она будет появляться постоянно, пока вы не замените терминал.

Ошибка 4120 терминала Сбербанка — что делать на Эвотор

Если такая ошибка появилась сразу после подключения пин-пада, то звоните в банк. Сотрудник банка неверно подключил устройство и настройку необходимо провести заново.
Если 4120 ошибка терминала возникла в процессе работы, то можно попытаться решить проблему самостоятельною. На решение проблемы может уйти немало времени. Поэтому, советуем принять оплату другим способом — наличными или по QR-коду.

Чтобы принять оплату наличными:

  1. Нажмите на значок «←» в верхнем углу экрана → Выберите «Наличные»
  2. Наличные

Чтобы принять оплату по QR-коду, вам потребуется приложение «Плати QR». Если у вас не подключена данная функция, то советуем это исправить, так как функция может быть очень полезной, особенно в случае неисправности пин-пада. Подробнее об этом мы писали в статье «Оплата QR Эвотор».
После того, как вы рассчитали клиента, то можно перейти к следующему шагу.

Оплата QR

Первое, что вам следует сделать — позвоните в техподдержку банка и сообщите об ошибке 4142 Сбербанка. Эта ошибка является системной, поэтому исправить ее самостоятельно не выйдет. Вероятнее всего, вам потребуется замена устройства. Для этого, к вам должен будет приехать специалист.

Проблему можно ликвидировать до приезда специалиста. Для этого выполните перезагрузку пин-пада. Узнать, как это сделать, вы можете на горячей линии банка. Но предупреждаем, после перезагрузки терминал может начать работать, так как сбой был устранен. Но через день-два, проблема снова возникнет на терминале. Так как причина, вызвавшая неисправность, не устранена, для этого нужно перенастроить пин-пад, а возможно и заменить его.

Устраним неисправность смарт-терминала

Бесплатная консультация специалиста8 (800) 700 50 85

whatsapp

whatsapp

Другие записи блога

Как сделать разные списки товаров для разных магазинов на Эвотор

Как сделать общий список товаров для нескольких Эвоторов

Предупреждение «Проверка компонентов» на Эвотор

Смарт-карта не отображается в «Кассовых сервисах»

I’ve got problem with TwinCAT3 (Win10 64bit) when I try to active TC3.

Error message is :

Severity Code Description Project File Line Suppression State Error
19-Jan-19 11:42:34 AM 545 ms | ‘TwinCAT System’ (10000): Sending ams
command >> Init4RTime: Start Interrupt: Ticker started >> AdsWarning:
4115 (0x1013, RTIME: system clock setup fails. Hint: On Windows8
system and above execute win8settick.bat in TwinCAT3.1System as
administrator and reboot.) << failed!

I also try to run «win8settick.bat» and reboot TC but it doesn’t work!

Is there any recommend to solve this ? Thanks a lot!

M Reza's user avatar

M Reza

17.6k14 gold badges66 silver badges71 bronze badges

asked Jan 19, 2019 at 4:54

talpham's user avatar

1

I have had the problem few times. In all those situations, the BIOS settings have been OK. Executing the .bat file didn’t help, until I ran it as an administrator and rebooted. Few times I have had to do it couple of times before it started working.

So try this

  1. Open start menu and search for «Command prompt»
  2. Right click it and select run as administrator
  3. Navigate to «C:TwinCAT3.1System» by writing «cd C:TwinCAT3.1System»
  4. Execute .bat by writing «win8settick.bat»
  5. Reboot — Repeat if not working

For me, this has always fixed the problem. If you have incorrect BIOS settings, you would get different error that states something about virtualization (as far as I know).

answered Jan 19, 2019 at 11:09

Quirzo's user avatar

QuirzoQuirzo

1,0518 silver badges9 bronze badges

3

I suspect you may have Hyper-V enabled. Because of the way that 64-bit TwinCAT interacts with the processor (using Intel VT-x), it doesn’t play well when hypervisors are running at the same time. Most hypervisors, like VMware, stop running when you close their window. However, Hyper-V (if enabled) is always running in the background so it must be disabled before using TwinCAT.

To Enable or Disable Hyper-V:

  1. Right click on the Windows button and select ‘Apps and Features’.
  2. Select Programs and Features on the right under related settings.
  3. Select Turn Windows Features on or off.
  4. Check or Uncheck Hyper-V and click OK.

Screenshot of Windows Features Window, arrow pointing to Hyper-V checkbox

source

answered Jan 22, 2019 at 5:57

Seth's user avatar

SethSeth

3381 silver badge9 bronze badges

In my case, installing TwinCAT 2 on top of an existing TwinCAT 3 installation was the problem.

According to Beckhoff, you need to «deactivate» TwinCAT 3 via «SwitchRuntime.exe» before installing TwinCAT 2, if installed in this order. In case of installing TwinCAT 3 on top of TwinCAT 2, you don’t need this step.

https://infosys.beckhoff.com/english.php?content=../content/1033/tc3_installation/179471755.html&id=

If forgot this, which probably destroyed parts of my TwinCAT 3 installation in the background.
Even tough I set the installation directory to a new folder «C:TwinCATTwinCAT_2» and not the default «C:TwinCAT«.
The installation process locked fine at first, only after trying to set a project into RUN while having TwinCAT 3 active as runtime, I got the above mentioned «AdsWarning: 4115».

Running «win8settick.bat» as admin and rebooting did not help, neither via explorer or command line.

Only re-installing TwinCAT3 did the trick for me.

answered Oct 22, 2021 at 11:33

Markus Wurm's user avatar

What worked for me was to disable the Virtual machine platform in Windows Features.

answered Oct 25, 2021 at 11:36

Yomi1984's user avatar

Yomi1984Yomi1984

1642 silver badges9 bronze badges

In addition to the other answers, you’ll get this error if you haven’t setup the real-time cores to match the computer you’re activating to:
enter image description here

answered Feb 16, 2022 at 22:35

Witman's user avatar

WitmanWitman

1,4582 gold badges14 silver badges18 bronze badges

I got the same issues. But I didn’t try any of the above methods.
bcz I am scared about warning ‘BitLocker trigger’ from a user above!

Then I changed the real-time system settings:

error :

Severity Code Description Project File Line Suppression State
Error 27/08/2022 16:40:58 279 ms | ‘TwinCAT System’ (10000): Sending ams command >> Init4RTime: Start Interrupt: Ticker started >> AdsError: 4115 (0x1013, RTIME: system clock setup fails.
Hint: On Windows8 system and above execute win8settick.bat in TwinCAT3.1System as administrator and reboot.) << failed!

settings: shared core 80%
old setting_shared core

new real-time setting: Isolated core 100 %
new setting _isolated core

No error:
enter image description here

I didn’t know the reason behind this!

answered Aug 27, 2022 at 14:48

ravi's user avatar

raviravi

214 bronze badges

Old
April 24th, 2018, 09:56 PM

 
#1

Member

Malaysia

derickloo is offline

 

Join Date: Mar 2015

Location: Malaysia

Posts: 33

Twincat 2 64 bit re-engineering not able to start


I have install latest twincat 2 64 bit(build 2301) into my computer running Windows 7 64 bit. After complete install and restart my computer, I found that the twincat icon is grey in color. I try to start it but it give me an error «Error 0x426 starting Twincat system!». I try to go to Services and manually start all the services related to twincat. When I start the Twincat System Services, it gave me «The dependency service or group failed to start» This computer have install old version twincat 2 64 bit and it work OK. But the latest version is not work. I need install latest version of twincat because the Embedded PC already change and it need latest version twincat system manager to communicate with it. Old version not able to communicate with it.
Any one face the same problem and any work around?
Thanks.

 

Reply With Quote

Old
April 24th, 2018, 10:36 PM

 
#2

Member

United States

Archie is offline

 

Join Date: May 2002

Location: Orangeburg, SC

Posts: 1,941

To my knowledge TwinCAT 2 run time has never been able to run on a 64 bit machine. That is why they have the x64 engineering version which basically lets you put the system in config mode only for programming remote run time systems.

 

Reply With Quote

Old
April 25th, 2018, 04:16 AM

 
#3

Member

Denmark

CommissioningMan is offline

 

Join Date: Sep 2017

Location: Denmark

Posts: 146

You’ll need to run TC2 runtime in a 32-bit virtual machine and connect to that. Since you are on Windows 7 you can use Windows Virtual PC from Microsoft, or you can also use VMware Player or VirtualBox. Of course you need both a Windows License and a TC2 license for the system.

__________________
All things Siemens and Beckhoff. Please let it be Beckhoff.

 

Reply With Quote

Old
April 30th, 2018, 12:34 AM

 
#4

Member

Malaysia

derickloo is offline

 

Join Date: Mar 2015

Location: Malaysia

Posts: 33

Quote:

Originally Posted by Archie
View Post

To my knowledge TwinCAT 2 run time has never been able to run on a 64 bit machine. That is why they have the x64 engineering version which basically lets you put the system in config mode only for programming remote run time systems.

Yup, I install Twincat 2 x64 engineering version 2.11(build 2241). It not able to start. The icon is grey in color. Previously this version is able to start in the same machine, after I uninstall it and install latest build 2301 and found this latest build not able to start; I re-install back the old version but this time the old version not able to start also. Anything I can do? Please help. Thanks.

 

Reply With Quote

Old
April 30th, 2018, 12:42 AM

 
#5

Member

Malaysia

derickloo is offline

 

Join Date: Mar 2015

Location: Malaysia

Posts: 33

I just worry when I uninstall the twincat 2.11(build 2241) not clean and cause the problem. If it is the issue, how I can fixed the problem?

 

Reply With Quote

Old
April 30th, 2018, 09:08 AM

 
#6

Member

Croatia

karlek is offline

 

karlek's Avatar

 

Join Date: Jul 2014

Location: Varazdin, Croatia

Posts: 68

Quote:

Originally Posted by CommissioningMan
View Post

You’ll need to run TC2 runtime in a 32-bit virtual machine and connect to that. Since you are on Windows 7 you can use Windows Virtual PC from Microsoft, or you can also use VMware Player or VirtualBox. Of course you need both a Windows License and a TC2 license for the system.

But he doesn’t need runtime if I understand correctly. He just needs to connect to an Embedded PC so he can program it. And if the icon is grey (it should be blue, and TwinCAT should be in config mode) he won’t be able to establish route to the PLC, am I correct?

So there is obviously some problem with the installation of the TwinCAT, as derickloo states.

 

Reply With Quote

Old
April 30th, 2018, 10:04 AM

 
#7

Member

Denmark

CommissioningMan is offline

 

Join Date: Sep 2017

Location: Denmark

Posts: 146

Ahh, right. I understand the first post now.
Try using Run->msconfig and set startup selection to Normal startup and reboot. Then try and start the TC system service.

See if you can open SystemManager in [Twincat installation folder]IoTCatSysManager.Exe by itself.

__________________
All things Siemens and Beckhoff. Please let it be Beckhoff.

 

Reply With Quote

Old
May 1st, 2018, 09:52 PM

 
#8

Member

Malaysia

derickloo is offline

 

Join Date: Mar 2015

Location: Malaysia

Posts: 33

I try to set the startup selection to normal startup and reboot it but the TC system service still not able to start. The icon still grey in color.
I can start TCatSysManager.Exe itself.

 

Reply With Quote

Old
May 2nd, 2018, 06:01 AM

 
#9

Member

Belgium

ivo.maenen is offline

 

ivo.maenen's Avatar

 

Join Date: Nov 2003

Posts: 663

I had the same problem (grey icon) on WIN7.

I de-installed KS2000 + TC2.

Re-installed everything and it worked again. Only sometimes the TC-icon does not appear. I can start the system manager on PLC-control manually (see post 7) and it works fine.

After a reboot or on a next reboot the TC-icon most times appears.

__________________
Assumptio mater errorum est.

 

Reply With Quote

Old
May 6th, 2018, 09:30 PM

 
#10

Member

Malaysia

derickloo is offline

 

Join Date: Mar 2015

Location: Malaysia

Posts: 33

Quote:

Originally Posted by ivo.maenen
View Post

I had the same problem (grey icon) on WIN7.

I de-installed KS2000 + TC2.

Re-installed everything and it worked again. Only sometimes the TC-icon does not appear. I can start the system manager on PLC-control manually (see post 7) and it works fine.

After a reboot or on a next reboot the TC-icon most times appears.

Sorry, I’m new in Twincat and Beckhoff, may I know what is KS2000?

 

Reply With Quote

Old
May 7th, 2018, 04:00 AM

 
#11

Member

Denmark

CommissioningMan is offline

 

Join Date: Sep 2017

Location: Denmark

Posts: 146

https://www.beckhoff.com/english.asp?ks2000/default.htm
It’s configuration software for fieldbus boxes. It’s not used that much on new projects, since you can put KL modules on EtherCat couplers.
But you might see a project from time to time with a BC9000 where’d you use it.

Have you been able to connect to the Embedded PC by opening the manager directly?

__________________
All things Siemens and Beckhoff. Please let it be Beckhoff.

 

Reply With Quote

Old
May 7th, 2018, 05:21 PM

 
#12

Member

Czech_Republic

AivisNewBie is offline

 

Join Date: Mar 2018

Location: None

Posts: 9

Hi I had this problem and wrote about it in this forum (cant find it now… no option for finding your own threads, or i just cant find it.).
I tried a lot of things with win 7 64 bit but it didin’t work.

The solution for this problem is to use win 10 or win 8.1 (dont remember if i tried it on 8 or 8.1 but i think both would be fine, and win 10 will work for sure) and it will work as a charm.

 

Reply With Quote

Old
May 9th, 2018, 10:18 PM

 
#13

Member

Malaysia

derickloo is offline

 

Join Date: Mar 2015

Location: Malaysia

Posts: 33

Quote:

Originally Posted by CommissioningMan
View Post

https://www.beckhoff.com/english.asp?ks2000/default.htm
It’s configuration software for fieldbus boxes. It’s not used that much on new projects, since you can put KL modules on EtherCat couplers.
But you might see a project from time to time with a BC9000 where’d you use it.

Have you been able to connect to the Embedded PC by opening the manager directly?

Cant connect the Embedded PC by System Manager. I use broadcast search but can’t find the Embedded PC.

 

Reply With Quote

Old
May 9th, 2018, 10:22 PM

 
#14

Member

Malaysia

derickloo is offline

 

Join Date: Mar 2015

Location: Malaysia

Posts: 33

Quote:

Originally Posted by AivisNewBie
View Post

Hi I had this problem and wrote about it in this forum (cant find it now… no option for finding your own threads, or i just cant find it.).
I tried a lot of things with win 7 64 bit but it didin’t work.

The solution for this problem is to use win 10 or win 8.1 (dont remember if i tried it on 8 or 8.1 but i think both would be fine, and win 10 will work for sure) and it will work as a charm.

Previously I run version 2.11(build 2241) and it work fine. After I change the Embedded PC and it required twincat new version. But after i install new version, it not work. Icon grey in color. I try to re-install old version but the problem still the same. Beside upgrade Windows OS, is there any way can fix this?

 

Reply With Quote

Old
May 16th, 2018, 01:38 AM

 
#15

Member

Czech_Republic

AivisNewBie is offline

 

Join Date: Mar 2018

Location: None

Posts: 9

Don’t know. You could contact Beckhoff and ask about this (I thinks this might be a bug). As someone mentioned before you don’t have to upgrade your OS just install it in virtual PC (I tested both I prefer VirtualBox) and install windows 10 or 8 here. or use win7 32 bit with TC2 32bit

 

Reply With Quote